1. The position of the auxiliary contact is not suitable.
After the switch has been tripped, the mechanical part has the phenomenon of moving and wearing, resulting in the position of the auxiliary contact being offset to the correct position, when the protective action trips, when the auxiliary contact is not disconnected, the outlet electrical appliance, electrical appliance and relay have returned, that is, the intermediate electrical appliance and relay contact are disconnected before the auxiliary contact.
As a result, the DC power supply is disconnected by intermediate appliances and relay contacts and burned. Therefore, in the event of an accident, although the protection has been activated, the switch has not been activated, resulting in skipping tripping.
2. The switch tripping mechanism is stuck.
Due to the lack of maintenance, the switch mechanism does not work well when operating, and there is a place where there is jamming, and it cannot trip normally, so that the intermediate electrical appliances and relay coils are charged for a long time, and the coils of the intermediate appliances and relays are burned out for a long time, and they cannot act correctly.
3. The core of the switch coil falls off or is stuck.
Due to the normal operation of the switch for many times and the fault after the switch, the top wire of the switch core is loosened, causing the switch core to fall off, and in the event of a failure, the switch can not be dropped, so that the outlet intermediate electrical appliances and relays are charged for a long time, and the electrical appliances and relay coils or contacts are burned.
|
More on that
|
Siemens apt - TL series police lights frequently asked questions
1. How many light sources are there for the TL-70 police light?
There are 3 types, namely LED, incandescent and xenon.
2. What are the colors of the TL-70 police light?
There are 5 types, which are red, yellow, green, blue, and white.
3. What are the types of TL-70 police lights?
3 ...
|
|
Siemens APT - ALS series limit switch FAQ
1. What are the installation methods of ALS limit switches?
Usually the limit switch is divided into front of the board installation or board back installation, all of which are installed by screws.
2. What are the different modes of limit switch action?
According to the action mode of the limit switch head, it is divided into ...
|
|
Siemens APT Relays - Selection Method for Solid State Relays
1. When selecting the solid-state relay used in the printed circuit board with small current specifications, because the lead terminal is made of high thermal conductivity material, the soldering should be carried out under the condition that the temperature is less than 250 °C and the time is less than 10S.
|
|
Siemens APT relay - the cause and solution of the fault of the high-voltage relay
1. Some common faults of high-voltage relay coils
1. The common fault cause of the coil is often disconnected: whether the ultrasonic wave is used to clean the high-voltage relay, or whether the overvoltage is added to the coil will also promote the probability of the coil being disconnected.
2 ...
|
|
Siemens APT Relays - a detailed introduction to the classification of relays
Classified according to the working principle or structural characteristics of relays:
1) Electromagnetic relay: an electrical relay that works by using the suction force generated by the current in the input circuit between the electromagnet core and the armature.
2) Solid state relay: refers to the electronic components that perform their functions without mechanical ...
|
|
Siemens APT limit switches – what are the limits used for?
daily life
There are many applications of travel switches, and it is found in many electrical appliances. So what does such a simple switch do? It mainly plays the role of chain protection. The most common example is its use in washing machines and tape recorders (VCRs). ...
|
|
Siemens APT Relays – a commonly used detection method for high and low voltage relays
1. Visual inspection method: observe the appearance of the relay by the naked eye, check whether it is damaged or deformed, observe whether the contacts are tightly contacted, and whether there are copper slag and other substances attached to the contacts.
2. Parameter detection method: use test instruments to detect the parameters of the relay, such as: ...
|
|
Siemens APT - LW39 series 10,000 revolutions FAQ
1. What are the current specifications of universal transfer switches?
At present, there are four forms: 10A, 16A, 25A, and 63A
2. What are the positioning angles of the universal transfer switch?
At present, it is divided into four angles: 30°, 45°, 60° and 90°
3. There is no customer's ...
|
|
Siemens APT Relays – the solution to common faults in solid state relays
1. The simplest and most effective way is to use a new solid state relay.
2. The other is to determine the voltage of the coil to avoid the voltage provided by the coil being less than the operating voltage.
3. Check whether the polarity is reversed.
4. Reasonable power-on time for the solid state relay coil, if ...
|
|
Siemens APT Relays – the working principle and function of relays
How relays work
Relays generally refer to electromagnetic relays, that is, mechanical actions. The working principle of the relay is essentially to use one loop (generally a small current) to control the on/off of another circuit (generally a large current), and in this control process, ...
|
|
Siemens APT Relays – The Cause of Solid State Relays Burnout
1. Poor design (low margin of voltage or current reservation during selection, insufficient heat dissipation conditions, etc.).
2. The fuse is too large or the fast fuse is not used as required.
3. The radiator is full of dust or the cooling fan fails.
4. Solid State Relay ...
|
|
Introduction to the features of Siemens APT DY2 miniature relay
Various specifications, with indicator light, with manual test button, with surge suppression loop and other functions
Coil control voltage DC6V-220V, AC6V-240V(50/60HZ)
The rail type is equipped with a variety of adapting sockets
LED indicator, DC is green, AC is red
Illuminating...
|
|
TL series police lights frequently asked questions
1. How many light sources are there for the TL-70 police light?
There are 3 types, namely LED, incandescent and xenon.
2. What are the colors of the TL-70 police light?
There are 5 types, which are red, yellow, green, blue, and white.
3. What are the types of TL-70 police lights?
3 ...
|
|
Siemens APT Relays – Analysis of Common Faults and Causes of Relays
1. Overhaul of the sensing mechanism
For electromagnetic (voltage, current, intermediate) relays, the sensing mechanism is the electromagnetic system. The faults of the electromagnetic system are mainly concentrated in the coil and the moving and static iron cores.
(1) Coil fault maintenance
Coil failure usually has a coil absolute...
|
|
ALH-0.66 series transformer FAQ
1. What is the maximum voltage that can be used for an ALH transformer?
AC low voltage up to 720V
2. Is there a protective grade product for ALH transformers?
II-P AND III-P are available in both protective grades
3. What is the maximum primary current of ALH transformer?
The maximum primary side current is 8 ...
|
|
Siemens APT Limit Switches - Introduction to the types and characteristics of limit switches
Conventional domestic travel switch
LX19-001/111 in the LX19 series, LXK3-20S/T in the LXK3 series, JLXK1 series JLXK1-111/411/511 in the conventional travel switch are the most representative.
|
|
Siemens APT Pushbutton Switches - Introduction to the types of metal pushbutton switches
Common types of metal button switches include self-locking switches, self-reset switches, knob gear switches, lever gear switches, locking switches, etc.; Because the metal button switch is small in size, easy to install, metal material, voltage can be used from 9-220V, and the appearance of metal texture ...
|
|
Siemens APT Relays – Selection Principles for High Voltage Relays
1. Electrical parameter matching: The rated voltage and current of the high-voltage relay need to match the circuit demand, too small will lead to the failure of the switch, too large will waste the cost.
2. Mechanical parameter adaptation: the external dimensions, pin arrangement and wiring mode of the high-voltage relay need to be adapted to the actual installation ring.
|
|
Siemens APT transformer – common faults and analysis of voltage transformers
(1) The insulation between the iron chips is damaged
Problem: The temperature rises during operation.
Possible causes of the problem:
(1) Poor insulation between iron chips
(2) The use of harsh environmental conditions or long-term operation at high temperature to promote the aging of insulation between iron chips.
( ...
|
|
Siemens APT Relays – Testing of Relays
(1) Measure the resistance of the contact: use the resistance of the multimeter to measure the resistance of the normally closed contact and the moving point, and the resistance value should be 0; The resistance between the normally open contact and the moving point is infinite. From this, it is possible to distinguish which is a normally closed contact and which is normally open.
(2) Coil resistance: multimeter R...
|
|