Siemens APT transformer – common faults and analysis of voltage transformers

Create Date: 2024-8-30 12:03:23|Source: APT/Siemens Shanghai Ergong

(1) The insulation between the iron chips is damaged

Problem: The temperature rises during operation.

Possible causes of the problem:

(1) Poor insulation between iron chips

(2) The use of harsh environmental conditions or long-term operation at high temperature to promote the aging of insulation between iron chips.

(2) Poor contact between the grounding piece and the iron core

Fault phenomenon: There is a discharge sound between the iron core and the fuel tank during operation.

The cause of the problem: the grounding lug is not plugged in tightly, and the installation screws are loose.

(3) The iron core is loose

Fault phenomenon: abnormal vibration or noise during operation.

The cause of the problem: the core clamp is not clamped, and the iron chips are loose.

(4) Winding inter-turn short circuit

Symptom:

(1) During operation, the temperature rises and there is a discharge sound;

(2) The high-voltage fuse is fused, and the secondary side voltmeter indication is unstable, high and low.

Causes of the problem:

(1) System overvoltage;

(2) Long-term overload operation;

(3) Aging insulation or poor manufacturing process.

(5) Winding disconnection

Fault phenomenon: During operation, there may be an arc at the disconnection point, there is a discharge sound and the voltmeter indication of the disconnected phase is reduced or zero.

Causes of the problem:

(1) Poor welding process;

(2) The mechanical strength is not good or the lead wire is unqualified, and the winding lead wire is broken.

(6) Winding interphase short circuit

Problem: The fuse on the high voltage side is blown off, the oil temperature increases sharply, and there is even smoke from the fuel injection.

Causes of the problem:

(1) Aging of winding insulation;

(2) The insulating oil is damp;

(7) Insulation breakdown of windings to ground

Problem: The high-voltage side fuse is continuously fused, and there may be a discharge sound.

Causes of the problem:

(1) The winding insulation is aging or there are conductive debris in the winding;

(2) The insulating oil is damp;

(3) Overvoltage breakdown, etc.

(8) Discharge flashover between casings

Fault phenomenon: the fuse on the high voltage side is blown and the bushing flashover is discharged.

Causes of the problem:

(1) Mechanical damage occurs when the casing is subjected to external force;

(2) There are foreign bodies or small animals entering between the casings;

(3) The casing is seriously polluted, resulting in the decline of insulation performance.
Siemens APT transformer – common faults and analysis of voltage transformers




More on that
Siemens APT Relays – The Difference Between Solid State Relays and AC Contactors Siemens APT Relays – The Difference Between Solid State Relays and AC Contactors

1. First of all, solid-state relays have a long service life and strong reliability. The solid state relay corresponds to the CDG1 series delicacy. This solid-state relay has no mechanical parts and solid-state devices to complete the contact function. Since the parts do not move, they can work in high shock and vibration environments. Because...

Siemens APT Relays – Classified by relay load Siemens APT Relays – Classified by relay load

(1) Micro-power relay: when the contact open circuit voltage is DC 28V, the (resistivity) is 0.1A, 0.2A relay. (2) Weak power relay: when the contact open circuit voltage is DC 28V, (resistivity) is 0.5A, 1A relay. (3) Medium power relay ...

Siemens APT current transformer - classification of current transformer and its function Siemens APT current transformer - classification of current transformer and its function

1. Current transformers are classified according to the installation method According to the installation method, the current transformer can be divided into through-type current transformer, pillar type current transformer, bushing type current transformer, and busbar type current transformer. Through-type current transformer: used to pass through the screen or wall...

Siemens APT - FM series metal button indicator frequently asked questions Siemens APT - FM series metal button indicator frequently asked questions

1. Which series of metal buttons can produce two-color buttons with light? FM25N 2. Which series can produce knobs? FM-N series 3. Which type of metal illuminated button needs an external resistor for step-down? FM16E 4. What is the material of the shell ...

Siemens APT Relays - What are the common faults of relays? Siemens APT Relays - What are the common faults of relays?

1. Contact failure (1) The phenomenon that cannot be disconnected due to mechanical occlusion of the contact (the needle-like protrusion and pit formed on the contact bite each other), fusion welding, or cold welding. (2) The contact wear of the relay is caused by the absence of arc extinguishing devices or measures, or improper parameter selection, ...

Siemens APT limit switches – what are the limits used for? Siemens APT limit switches – what are the limits used for?

daily life There are many applications of travel switches, and it is found in many electrical appliances. So what does such a simple switch do? It mainly plays the role of chain protection. The most common example is its use in washing machines and tape recorders (VCRs). ...

Siemens apt - TL series police lights frequently asked questions Siemens apt - TL series police lights frequently asked questions

1. How many light sources are there for the TL-70 police light? There are 3 types, namely LED, incandescent and xenon. 2. What are the colors of the TL-70 police light? There are 5 types, which are red, yellow, green, blue, and white. 3. What are the types of TL-70 police lights? 3 ...

Siemens APT warning light - the role of LED warning light in life Siemens APT warning light - the role of LED warning light in life

LED warning light function 1. The luminous method selection items are: solid light, shiny, burst flash, constant/shiny mix. 2. The installation base is: L rod, straight rod, folding, and barrel type. Effect of LED warning light_Effect in different scenes 1. Construction unit On the road ...

Siemens APT Pushbutton Switches – How Many Types of Pushbutton Switches Are There? Siemens APT Pushbutton Switches – How Many Types of Pushbutton Switches Are There?

There are several types of pushbutton switches: Pushbutton switches can be classified according to the way they are protected and how they are operated. It can be divided into open type and protected type, as well as waterproof type and anti-corrosion type, etc. And explosion-proof, knob-type, key-type, emergency-type, are also its ...

Siemens APT transformer - the use, principle and selection of current transformer Siemens APT transformer - the use, principle and selection of current transformer

The principle of the current transformer is based on the principle of electromagnetic induction. A current transformer is composed of a closed core and windings. Its primary side winding turns are very small, string in the line of the current that needs to be measured, so it often has all the current of the line flowing through, the number of turns of the secondary side winding is relatively large, and the series ...

Siemens APT Current Transformer - The difference between voltage transformer and current transformer Siemens APT Current Transformer - The difference between voltage transformer and current transformer

The difference between the voltage transformer and the current transformer in terms of effect principle The primary difference is that the operating conditions are very different during normal operation, and the main performance is as follows: 1) The current transformer can be short-circuited twice, but it cannot be opened; The voltage transformer can be opened twice, but it must not be short-circuited 2) ...

What are the main problems with Siemens APT Relays – Solid State Relays? What are the main problems with Siemens APT Relays – Solid State Relays?

When the solid state relay is open and there is voltage at the load end, there will be a certain leakage current at the output end, and care should be taken to prevent electric shock when using or designing. When the solid-state relay fails to be replaced, the original model or the product with the same technical parameters should be selected as far as possible, so as to match the original application line and ensure that the system ...

Siemens APT current transformer - inspection content of current transformer Siemens APT current transformer - inspection content of current transformer

1. Regularly check whether the current transformer is overheated, check whether there is discoloration in the terminal, and check whether there are sundries in the terminal box. 2. Check whether there is oil leakage in the oil level gauge in time to ensure that the oil level meets the use standard and there is no oil leakage.

APT won the 2014 Top Ten Cutting-edge Enterprises in China's Automation Field APT won the 2014 Top Ten Cutting-edge Enterprises in China's Automation Field

On April 22, 2015, the "2015 China Automation Industry Annual Conference and the 10th China Automation Industry Century Event" sponsored by the Chinese Association of Automation was held in Beijing. At the conference, APT won the "2014 Top Ten New Enterprises in China's Automation Field" award, which was awarded by APT last year.

Siemens APT new x. The new product of R series relay was released Siemens APT new x. The new product of R series relay was released

On May 8, 2019, APT held a grand online conference in Shanghai, Beijing, Guangzhou, Nanjing, Changsha and Tiantai...... and more than 20 cities across the country witnessed the new Siemens APT x. The new product of R series relay was released. ...

Siemens APT - AD16 series indicator frequently asked questions Siemens APT - AD16 series indicator frequently asked questions

1. Why does the indicator light still glow after the control power supply has been disconnected? This situation is caused by the presence of interference voltage, and this problem can be solved by ordering our anti-interference indicator light 2. What are the operating hours of the AD16 series indicators? More than 30000 small ...

Siemens APT current transformer - introduction to the classification of current transformers Siemens APT current transformer - introduction to the classification of current transformers

Categorized by use According to different uses, current transformers can be roughly divided into two categories: Current transformer for measurement (or measurement winding of current transformer): provides current information of the power grid to measurement, metering and other devices within the normal working current range. Protecting Electricity ...

Siemens APT Relays – The Cause of Solid State Relays Burnout Siemens APT Relays – The Cause of Solid State Relays Burnout

1. Poor design (low margin of voltage or current reservation during selection, insufficient heat dissipation conditions, etc.). 2. The fuse is too large or the fast fuse is not used as required. 3. The radiator is full of dust or the cooling fan fails. 4. Solid State Relay ...

Siemens APT Relays – The difference between signal relays and power relays Siemens APT Relays – The difference between signal relays and power relays

Signal relays are used more in secondary maintenance circuit circuits. It tells the right people exactly what is wrong with the maintenance. The power relay is a bit like a discriminant sentence in mathematics. When a constant is entered, the satisfactory and unsatisfactory conditions will output different results. Merit...

Introduction to the advantages and disadvantages of Siemens APT relays - solid state relays Introduction to the advantages and disadvantages of Siemens APT relays - solid state relays

merit 1. High life, high reliability: solid state relay has no mechanical parts, the contact function is completed by solid devices, because there are no moving parts, so it can work in a high impact and vibration environment.

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top