1. About the management of higher harmonics on the output side of the inverter
The magnetic noise skills brought about by the communication harmonic components contained in the output waveform controlled by PWM reduction have been increasingly used in various inverters, such as the selection of higher frequency switching components, the installation of filter equipment at the output end of the inverter, and the use of random method to adjust the switching frequency and closed-loop control to improve the higher harmonics.
2. About the management of higher harmonics on the input side of the inverter
(1) A communication reactor is set on the communication input side of the inverter to increase the rectifier impedance, so that the rectifier overlap angle increases and the higher harmonics are reduced.
(2) The communication filter equipment is used in parallel in the power circuit, which can divert the weight of the higher harmonics from the inverter and the power supply system.
(3) For the occasion of installing multiple inverters, each can be equipped with a special transformer, and the method of staggering the phase of the input transformer can be used to press the higher harmonics.
3. Use passive filters or active filters
The use of passive filters is mainly to change the impedance of the power supply at a special frequency, which is suitable for a stable and unchanged system. The use of active filters is primarily used to compensate for nonlinear loads.
The traditional method mostly uses passive filters, and passive filters are the earliest, because of their simple structure, low investment, high operation reliability and low operating costs, they are still the primary method of harmonic pressing. LC filter is a traditional passive harmonic pressing equipment, which is properly composed of filter capacitors, reactors and resistors, and is connected in parallel with the harmonic source, in addition to the filtering effect, there is also the role of reactive power compensation. This kind of equipment has some shortcomings that are difficult to overcome, first of all, it is easy to overload, and it will be burned when overloaded, which may constitute a power factor over-introduction and compensation and be fined; In addition, passive filters cannot be controlled, so over time, the resonant frequency will change due to the aging of accessories or changes in the load of the grid, and the filtering effect will decrease. More importantly, the passive filter can only filter one harmonic component (if there is a filter that can only filter out the third harmonic), if the filter is different harmonic frequency, it is necessary to use different filters and add equipment investment.
There are a variety of active filters at home and abroad, which can track and compensate for harmonics with varying frequency and amplitude, and the compensation characteristics are not affected by the impedance of the power grid. The active power filter (APF) theory was formed in the 60s of the 20th century, and later with the maturity of large and medium power fully controlled semiconductor devices, the progress of pulse width modulation (PWM) control skills and the proposal of the instantaneous detection method of harmonic current according to the instantaneous reactive power theory, the active power filter has developed rapidly. The basic principle is to detect the harmonic current from the compensation target, and the compensation equipment generates a compensation current spectrum that is equal to the size of the harmonic current and has the opposite polarity, so as to cancel the harmonics generated by the harmonic source of the original line, so that the grid current only contains the fundamental weight. THE CENTRAL PART IS THE HARMONIC CURRENT GENERATOR AND CONTROL SYSTEM, THAT IS, ITS OPERATION IS COMPLETED BY DIGITAL SIGNAL PROCESSING (DSP) SKILLS TO CONTROL THE FAST INSULATED BIPOLAR TRANSISTOR (1GBT).
Now, in terms of detailed harmonic management, the method of passive filter (LC filter) and active filter complementary and mixed use is presented, giving full play to the advantages of LC filter simple structure, easy to complete, low cost, good compensation performance of active power filter, and overcoming the shortcomings of large capacity and high cost of active power filter, and the combination of the two is used, so that the whole system can obtain outstanding performance.
4. Reduce the impedance of the loop and block the transmission line
The basic cause of harmonic generation is due to the use of nonlinear loads, so the basic solution is to separate the power supply line of the load where harmonics occur and the power supply line of the load that is sensitive to harmonics (as shown in Figure 2). The distortion current caused by the nonlinear load causes a distortion voltage drop on the impedance of the cable, and the resulting distortion voltage waveform is applied to other loads connected to the same line, causing the harmonic current to flow over it (as shown in Figure 3). Therefore, the method of reducing harmonic damage can also be completed by increasing the cross-sectional area of the cable and reducing the impedance of the loop. Now, the domestic more selection to improve the capacity of the transformer, increase the cable cross-section, especially to increase the neutral cable cross-section, as well as the selection of the setting value of the larger circuit breaker, fuse and other maintenance elements and other methods, but this method can not eliminate harmonics from the bottom, but reduce the maintenance characteristics and functions, and increase the investment, add the hidden dangers of the power supply system. As can be seen in Figure 2, it is possible to transfer both linear and non-linear loads from the same source
The interface point (PCC) is supplied to the discrete circuit, so that the distorted voltage caused by the non-linear load is not transmitted to the linear load. This is now the more ambitious solution to manage harmonic problems.
5. Use green inverter without harmonic pollution
The quality standard of the green inverter is: the input and output current are sine waves, the input power factor is controllable, and the power factor can be 1 when any load is used, and the output frequency can be controlled by any power frequency. The communication reactor built in the inverter, it can press the harmonics well, and together can maintain the rectifier bridge from the influence of the instantaneous sharp wave of the power supply voltage, and the practice shows that the harmonic current without the reactor is significantly higher than the harmonic current generated by the reactor. In order to reduce the disturbance caused by harmonic pollution, a noise filter is installed in the output circuit of the inverter. And if the inverter allows, the carrier frequency of the inverter is reduced. In addition, in high-power inverters, 12-pulse or 18-pulse rectification is generally used, so that in the power supply, the harmonic content is reduced by eliminating the lowest harmonics. For example, with 12 pulses, the lowest harmonics are the 11th, 13th, 23rd, and 25th harmonics. By analogy, about 18 pulses, the lowest harmonics are the 17th and 19th harmonics.
The low harmonic skills used in the inverter can be summarized as follows: (1) The parallel multiplication of the inverter unit, two or more inverter units are selected to be connected in parallel, and the harmonic weight is offset by the superposition of waveforms. (2) For the multiplexing of the rectifier circuit, 121 pulses, 18 pulses or 24 pulses are selected in the PWM inverter to reduce harmonics. (3) The series multiplexing of the inverter unit, the 30-pulse series inverter unit multiplexing line is selected, and the harmonics can be reduced to very small. (4) Choose new frequency conversion modulation methods, such as diamond modulation of voltage vectors. At present, many inverter manufacturers have attached great importance to the harmonic problem, and have ensured the greening of the inverter from the technical approach when designing, so as to solve the harmonic problem at the foundation.
6. No matter what method is chosen, it is impossible to completely solve the problem of higher harmonic management, in order to eliminate the disturbance of the higher harmonics of the inverter to the electrical equipment in actual industrial production, it is mainly solved from three aspects: conduction, radiation and coupling. The general principle is to press and block the source of disturbance, intercept the coupling channel of the disturbance to the system, and reduce the sensitivity of the disturbance signal. To solve the conduction disturbance is to filter out or block the conduction high-frequency current in the circuit, to solve the radiation disturbance is to shield the radiation source or the disturbed line, and to solve the coupling disturbance is to reasonably place the interval and direction of the disturbance source and the disturbed line to avoid coupling.
In addition to the selection of skills such as blocking, shielding, grounding, reasonable wiring, etc., it can also take the skills of evasion and guidance, such as filtering, absorption and bypass, etc., these evasion and guidance skills are simple and wonderful, and sometimes can replace the expensive and large quality of the hardware method, and receive twice the result with half the effort.
|
More on that
|
Schneider appeared at the 5th China Power Distribution Technology Summit Forum
Beijing, China, September 14, 2020 – Today, the 5th China Power Distribution Technology Summit Forum 2021, held by China Electric Power Research Institute Co., Ltd. and the Science and Technology Development Service Center of China Electric Power Council, opened in Beijing. The theme of this forum is "Supporting the Strategic Policy of Carbon Peaking and Carbon Neutrality, Building a ...
|
|
Advantages of the Schneider Magelis GXU touchscreen
1. Save capital contribution
Focus on central function (true color LCD, serial communication interface, USB connection, Ethernet interface, etc.)
2. Save space
Compact structure planning, only 38mm thick
The fuselage is reserved for communication wiring ...
|
|
Schneider circuit breaker maintenance method
1. Insist that the air is moist or unclean, and the pipes are not clean, which may have the following consequences:
(1) The wet gas is decomposed into mixed gases such as hydrogen and oxygen under the effect of arcing, destroying the insulation between the fractures after the main contact is broken, which is difficult to arc or arc re-ignition, and in severe cases, arc extinguishing will be formed.
|
|
The cause of leakage in the motor using the inverter - Schneider
1. The output of the inverter is controlled by PWM (pulse width modulation, similar to high-speed switching), so high-frequency leakage current will occur.
The PE points of the three transmission equipment of the inverter, the pre-power supply transformer and the motor must be connected together and then grounded consistently.
Frequency conversion...
|
|
Schneider inverter frequency signal source mode
In order for the inverter to operate normally, it must have two basic conditions, that is, the frequency signal and the operating signal, let's talk about the first condition, which is the frequency signal of the inverter.
Our intention to use the inverter is to change the ...
|
|
How Schneider UPS properly configures the backup battery
In order to ensure that the APCUPS power supply can continue to supply high-quality power to the computer even in the event of a power outage, it is important to equip the battery backup battery. When the load is not allowed to be powered, the UPS battery backup time in the communication room should be greater than the time from the mains power interruption to the rehabilitation or to the generator set is positive.
|
|
Features of Schneider explosion-proof inverter boxes
1. Aluminum alloy shell or steel plate welding, plastic spraying on the surface;
2. Built-in inverters, circuit breakers, signal lights and other components produced by domestic or Schneider and other companies;
3. It mainly regulates the general three-phase difference by changing its output frequency.
|
|
Schneider inverter maintenance power settings, waveform test problems
1. After the inverter is repaired, the power number needs to be modified, don't forget it
Generally, an inverter corresponds to a power number (also known as the number of horsepower), for example, a 75 kilowatt inverter is set under heavy load, and 100 kilowatts is set under light load. In this way, the customer will not use it to present ...
|
|
Maintenance of Schneider circuit breakers
In order to keep the main Schneider circuit breaker in excellent operating condition, it is necessary to strengthen the maintenance management.
1. Insist that the air is moist or unclean, and the pipes are not clean, may have the following consequences:
(1) The wet gas is decomposed into mixed gases such as hydrogen and oxygen under the action of electric arc, which damages the ...
|
|
Line leakage detection method - Schneider
Line leakage detection method, leakage check method summary, if a closing, leakage switch will trip, this kind of front leakage, check the method is as follows:
1. Disconnect all the separation gates, close the main gate, close the separation gates one by one, and close them to ...
|
|
Diode selection and substitution method - Schneider
1. Selection of detection diode
Point-contact germanium diodes are generally used for detection diodes, such as 2AP series. When selecting, the detection diode with high operating frequency, small reverse current and large forward current should be selected according to the specific requirements of the circuit. Despite the ...
|
|
Schneider circuit board maintenance work commonly used instrumentation
Before preparing to do circuit board repair work, you should prepare some things and appearances to help repairers better carry out circuit board repair operations, according to our circuit board repair training center for many years of experience has shown that prepare some necessary circuit board repair things and appearance, to be able to reach ...
|
|
Inverter maintenance mantra method - Schneider
Don't worry about the damage of the frequency conversion, disassemble the machine after the discharge;
It is indispensable to ask for a diagnosis and clarify the problem at the beginning of the test;
Input and output PN junction, three-phase balance and then unshelling;
Look at the nameplate before powering on, the wrong voltage will blow up;
The bus has no electricity to see that it is safe, and the rectifier filter is wrong ...
|
|
A brief description of the working principle of Schneider power soft starter
Schneider ATS48 soft starter is composed of three opposite parallel thyristors, which are connected in series between the three-phase power supply and the motor, by changing the trigger angle of the thyristor gate pulse, the conduction angle of the thyristor gradually increases from zero, according to the pre-set soft starter parameter curve, the motor output torque ...
|
|
Schneider PLC intelligent parameter features
Characteristic:
1. NEZA PLC (TSX08 series)
EZA series is a small PLC with rich functions, high performance-to-price ratio, small size and strong versatility.
A new generation of handheld programmer - Chinese PDA PL707WinCE, supports Chinese interface, whether it is programming, ...
|
|
Selection and control of the inverter installation - Schneider
Frequency converters are widely used equipment in modern industry. If you want to complete the functions of soft stop, soft start, stepless speed regulation or special requirements for speed rise and fall, you need the more advanced speed control equipment in modern asynchronous motors - frequency converters. The main circuit of the equipment is selected to communicate - DC - communication ...
|
|
Precautions for trial operation of Schneider motors
1. Check during the test run of the motor
1.1 Before the motor starts
It is necessary to carefully check whether the insulation resistance is qualified, check whether the wiring of the secondary circuit is correct, and the inside of the motor should be boring, clean and free of debris. Investigate whether the fastening bolts of the motor are loose and the bearing is ...
|
|
Schneider relay model introduction
RM4 Series Control Relay (Three-phase Power Control)
RM4 series voltage steerable relays
RM4 current operated relay
RM4 level control relay
RM17 three-phase power controller
RM35 3-phase power control relay
RM17 Voltage Steerable Relay ...
|
|
Features of Schneider elliptical gear flowmeter
Elliptical gear flowmeter (also known as displacement flowmeter, gear flowmeter), classified as a positive displacement flowmeter, is a class with high accuracy in the flow surface. It uses a mechanical measuring element to continuously cut the fluid into a single known volume part, and according to the measuring chamber, it is repeated and repeated.
|
|
The role of Schneider thermal relays
The effect of the thermal relay is mainly used to carry out overload maintenance on the asynchronous motor, his operating principle is that after the overload current passes through the thermal element, the bimetal sheet is heated and bent to advance the action mechanism to drive the contact action, so as to disconnect the motor control circuit to complete the motor power-off thermal relay ...
|
|