Frequency converters are widely used equipment in modern industry. If you want to complete the functions of soft stop, soft start, stepless speed regulation or special requirements for speed rise and fall, you need the more advanced speed control equipment in modern asynchronous motors - frequency converters. The main circuit of the equipment is AC-DC-AC circuit, and the operating frequency is 0 - 400 Hz. The output voltage of the low-voltage universal inverter is 380-460 V, and the output power is 0.37-400 kW. Inverter-operated devices are widely used because they offer significant energy savings. However, the inverter has become the primary source of pollution in the power grid due to serious harmonic currents during operation. The more common fault phenomena caused by harmonics are damage to reactive power compensation equipment, tripping, transformer overheating, etc.
1. Choose a reasonable inverter
During the use of the inverter, there are problems such as abnormal operation and equipment failure. , resulting in production shutdown and unnecessary economic losses, is often caused by improper inverter selection and installation. Therefore, we should choose an inverter that is economical and useful and can better meet the basic conditions and requirements of production and skills.
1.1 The specified index parameters of the inverter and the motor are matched.
As the primary drag object of the motor, the type of inverter should match the operating parameters of the motor.
(1) Voltage matching: The additional voltage of the inverter is the same as the load voltage of the motor.
(2) Current matching: The capacity of the inverter depends on the additional current output of the inverter. When selecting the inverter, the motor that needs to regulate the speed must select the inverter with additional current greater than the additional current when the motor is operating with additional parameters, and there is a quantitative margin; Generally, the inverter with more than 4 poles can not be selected according to the capacity of the motor, but should be selected according to the current seat inspection specification of the motor. Even if the motor load is light and the current is less than the additional current of the inverter, the selected inverter cannot be much smaller than the motor capacity.
(3) Capacity matching: According to the different load characteristics of the motor, there are different requirements for the selection of inverter capacity.
2. The control method of the inverter
At present, the primary control methods of the inverter are mainly as follows.
(1) The first generation selects U/f=C control, also known as sinusoidal pulse width modulation (SPWM) control method. Its characteristic control circuit is simple in structure, low in cost, good in mechanical characteristics and hardness, and can meet the requirements of stable speed regulation of general transmission. However, at low frequencies, the output voltage is low, which reduces the large output torque and worsens stability at low speeds. It is characterized by the fact that the speed ratio Ni of the non-reactive equipment is less than 1/40, and Ni = 1/60 when there is a reaction. Suitable for general fans and pumps.
(2) The second generation selects voltage space vector manipulation (magnetic flux orbit method), also known as SVPWM manipulation method. Under the premise that the three-phase waveform is fully functional, the three-phase modulated waveform occurs at one time, and is controlled by the method of approximating the circle with the internal polygon. In order to eliminate the effect of stator resistance at low speeds, the output voltage and current are closed to improve dynamic accuracy and stability. Its features: non-reactive equipment, speed ratio NI=1/100, suitable for general industrial speed regulation.
(3) Three generations of vector control. The essence of frequency conversion speed regulation vector control is that the communication motor is equivalent to the DC motor, and the two weights of speed and magnetic field are controlled independently. After manipulating the rotor flux, and then differentiating the stator current, the two weights of torque and magnetic field are obtained, and the orthogonal or decoupled manipulation is completed through coordinate transformation. It is characterized by a speed ratio of NI=1/100 when there is no response, a speed ratio NI=1/1000 when there is a reaction, and a starting torque of 150% at zero speed. It can be seen that this method is suitable for all speed control, and is suitable for high-precision transmission control with reaction.
(4) Direct torque control. Direct torque control is another high-performance variable frequency speed regulation method that is different from vector control. The flux and torque data are obtained from the flux simulation model and the electromagnetic torque model, which are compared with the given values, and the hysteresis comparison condition signal is generated, and then the constant flux flux control and electromagnetic torque control are completed by switching the status through logical manipulation. There is no need to imitate the DC motor control, and this skill has been successfully applied to the communication transmission of traction electric locomotives. Its characteristics: the speed ratio of non-reaction equipment is Ni = 1/100, the speed ratio of reaction equipment is Ni = 1/1000, and the starting torque at zero speed can reach 150% - 200%. It is suitable for heavy load starting and large load with stable torque fluctuation.
3. Device environmental requirements
(1) Ambient temperature: The ambient temperature of the inverter refers to the temperature adjacent to the cross-section of the inverter. Since the drive is primarily composed of high-power power electronics that are susceptible to temperature, the lifetime and reliability of the drive is highly dependent on the temperature, generally between -10°C and +40°C. In addition, it is necessary to consider the extreme conditions that may be presented by the inverter itself and the surrounding environment, and the temperature generally requires a certain margin.
(2) Ambient humidity: The relative humidity of the environment around the inverter does not exceed 90% (no condensation on the surface).
(3) Oscillation and impact: In the process of installation and operation, attention should be paid to prevent oscillation and impact. Prevent serious faults such as poor electrical contact and even short circuits caused by loose solder joints and parts of the internal components of the inverter. Therefore, it is generally required that the oscillation acceleration at the device site should be limited to less than 0.6 g, and anti-seismic measures such as shockproof rubber can be added in special places.
(4) Device location: The maximum promised output current and voltage of the inverter are affected by its heat dissipation capacity. However, if the altitude exceeds 1000 m, the heat dissipation capacity of the inverter will be reduced, so the inverter is generally required to be installed below 1000 m above sea level.
(5) The general requirements of the inverter for the device site: no corrosion, no flammable and explosive gas or liquid; Dust-free, floating fibers and metal particles; Protect from direct sunlight; There is no electromagnetic interference.
4. Conclusion
The study of variable frequency speed regulation was an active and useful operation in the research of electric transmission at that time. The inverter industry has great potential and is widely used in air conditioning, elevator, metallurgy, machinery and other industries. Inverter motors and their supporting inverters are developing rapidly.
|
More on that
|
Precautions for the selection of Schneider molded case circuit breaker
1. Shell current and rated current
The size of the shell current is 100 (rated current 16 25 32 40 63 80 100) 250 (rated current 160 250 400 (rated current 250 400) 630 (rated current 630A.)
...
|
|
Introduction to Schneider inverter inverter
The inch movement in Schneider inverter means that the control signal can drive the motor intermittently according to a certain law, and the motor strictly follows the dynamic and stop command action of the control signal, and the motor does not roll by inertia during the shutdown. It's like moving an inch and then stopping.
The full name of Schneider inverter is "...
|
|
Schneider inverter motor control mode
Fundamentals of magnetic flux vector manipulation
The control of a three-phase asynchronous motor is much more messy than that of a DC motor because the current, voltage, induced potential, magnetic flux, etc., of the stator and rotor are all alternating.
However, the stator winding of the three-phase asynchronous motor is a symmetrical three-phase winding, which exerts a ...
|
|
Schneider servo drive fault code
1. AL001: overcurrent, the current value of the main 2113 circuit exceeds the motor instantaneous 5261*** high current value 1.5 times when the action is 4102.
2. AL002: overvoltage, the voltage value of the main return 1653 channel is higher than the standard value.
3. AL003: low voltage, the voltage value of the main circuit is lower than the standard.
|
|
Schneider improves plant performance with automated control
1. Engineering planning one by oneWith data at their fingertips and intelligent and sensitive functions, engineers can easily plan and test equipment, improve process availability, and easily complete system integration together – ultimately reducing the planning time by up to 25%.
...
|
|
Schneider low-voltage circuit breaker selection method
1. Determine the type and maintenance situation of Schneider circuit breaker according to the maintenance requirements of the line, and determine the selection of frame type, device type or current limiting type. Generally speaking, the short-circuit current breaking ability of Schneider frame circuit breaker is larger and larger than that of device type. Usually, the branch line chooses ...
|
|
How to operate the transformer DC resistance tester – Schneider
1. The instrument test has a total of YN winding three-phase test, YN winding three-phase phase-by-phase test, low-voltage winding magnetization method test of iron-core five-column low-voltage angular transformer, low-voltage winding phase selection test and general four-terminal method of ironcore three-column low-voltage angular transformer.
...
|
|
Schneider circuit breaker maintenance method
1. Insist that the air is moist or unclean, and the pipes are not clean, which may have the following consequences:
(1) The wet gas is decomposed into mixed gases such as hydrogen and oxygen under the effect of arcing, destroying the insulation between the fractures after the main contact is broken, which is difficult to arc or arc re-ignition, and in severe cases, arc extinguishing will be formed.
|
|
Schneider Electric has announced the launch of its Pacific Foundation
Schneider Electric has announced the launch of its Pacific Foundation, which will provide financial and advisory support to charitable foundations in the Pacific region to address fundamental human rights issues of access to energy. Four foundations were selected as the Foundation's initial recipients.
|
|
Schneider selection of different types of circuit breakers
Miniature circuit breakers are: A9 (iC65, iDPN, etc.), M9 (C65, DPN, C120, NG125, etc.), E9, OSMC32N/OSMC65H, etc.
Molded case circuit breakers are: NSX, NSE, EZD, NSC, large molded case NS.
Structural circuit breakers include: MT, MTE, etc.
...
|
|
Schneider Intermediate Relay Model Letter Meaning
RXM: Schneider's miniature center relay
The first 2: indicates the number of contacts, and the normally open contact is 2
LB: Indicates that the product has LED light
The second 2: indicates the number of contacts, and the normally closed contacts are 2
BD: Indicates that the supply voltage used is DC 24V
...
|
|
Maintenance of multiple models of Schneider inverters
Schneider inverter our most common problem is that the power is not visible, the series of inverter switching power supply uses a UC2842 chip as a waveform generator, the damage of the chip will lead to the switching power supply can not operate, so that it can not be displayed normally, in addition, the operating power supply of the chip is not ...
|
|
Schneider UPS uninterruptible power supply debugging precautions
1. Check whether all switches are in the disconnected position;
2. Check whether there are foreign objects in the UPS uninterruptible power supply cabinet and transformer; Check whether the flat cable connection is correct and whether it is loose;
3. Check that the connected plug is ...
|
|
Features of Schneider's different PLC series
Schneider PLC series mainly includes:
Schneider NEZA PLC (Schneider TSX08 series);
Schneider Quantum PLC (Schneider 140 series);
Schneider Micro PLC (Schneider TSX37 series);
Schneider Premium PLC (Schneider TSX...
|
|
Analysis of the causes of frequent overcurrent alarms of inverters - Schneider
(1) Caused by incorrect parameter setting.
If the acceleration time of the inverter is set too short, the change of the output frequency of the inverter far exceeds the change of the motor frequency, and when the inverter is started, it will trip due to overcurrent. Adjusting the acceleration time accordingly to different load conditions can eliminate this problem.
|
|
The operation essentials of Schneider disconnectors
Schneider Barrier Features: First of all, Schneider Barrier Switch can be used to block the power supply, it is able to disconnect the live equipment from the high-voltage maintenance equipment, and it can also see a significant disconnection point on it. Secondly, the Schneider barrier switch can be used with the circuit breaker to change the operation of the system.
|
|
Schneider instrumentation maintenance precautions
1. When assembling and adjusting the appearance, the original position should be recorded for rehabilitation.
2. When repairing the appearance of precision instruments, if you accidentally bounce small parts away, you should first determine the position where you can fly down.
|
|
Deterioration site and the principle of higher harmonic generation - Schneider
1. Electrical equipment will produce higher harmonics when it produces abnormality and deterioration, and the abnormality and deterioration of motors, loads, and inverters are used to distinguish the higher harmonics from 2 to 40 times, and the data is changed by FFT, and the analysis is made on the basis of the analysis data of long-term savings.
|
|
Schneider inverter maintenance precautions
Schneider Electric intelligent special effect inverter maintenance, the daily maintenance of the inverter mainly depends on your use environment, such as moisture-proof, dust-proof, anti-foreign body ingress, pay attention to whether there is any abnormal sound when usually protecting.
Attention to the needs of inverter protection ...
|
|
Schneider molded case circuit breakers NSX, CVS, EZD differences
1. NSX series is Schneider's high-end molded case circuit breaker, with the best performance in all aspects, and of course, the price is also the most expensive.
2. CVS series, which is the main series of Schneider, has the second best performance compared with the NSX series, but can meet the vast majority of applications, and the price is more affordable.
3 ...
|
|