Inverter selection and capacity matching method - Schneider

Create Date: 2024-8-30 12:03:23|Source: Schneider/Schneider

How to carry out the selection of inverter normally, is the difficulty faced by many enterprise technical personnel and business personnel, in addition, the selection of the inverter body alone, without considering whether the inverter selection and capacity matching is appropriate, is also unscientific.

                              Inverter selection and capacity matching method - Schneider

So what exactly to do?

1. Select the inverter according to the load characteristics.

Second, when selecting the inverter, the current value of the practical motor should be used as the basis for the selection of the inverter, and the additional power of the motor can only be used as a reference. Secondly, it should be fully considered that the output of the inverter contains higher harmonics, which will form the power factor and power of the motor will deteriorate.

3. When the inverter wants to run with a long cable, the inverter should be enlarged by one gear or the output reactor should be installed at the output end of the inverter.

4. When the inverter is used to control several motors connected in parallel, it must be considered that the sum of the length of the cable from the inverter to the motor is within the allowable range of the inverter.

5. For some special applications, such as high ambient temperature, high switching frequency, high altitude, etc., it will cause the capacity reduction of the inverter, and the inverter needs to be expanded by one gear.

6. When selecting the inverter for high-speed motors, it should be slightly larger than the inverter of general motors.

7. When the inverter is used in the pole changing motor, the capacity of the inverter should be selected so that the maximum additional current is below the additional output current of the inverter.

8. When driving the explosion-proof motor, the inverter does not have an explosion-proof structure, and the inverter should be set outside the dangerous place.

9. When the inverter is used to drive the gear reducer motor, the scope of use is restricted by the lubrication mode of the rotating part of the gear. Do not exceed the maximum speed tolerance.

10. When the inverter drives the wound rotor asynchronous motor, most of the existing motors are used. It is easy to overcurrent tripping due to ripple current, so it is necessary to select an inverter with a slightly larger capacity than usual.

11. When the inverter drives the synchronous motor, the output capacity is reduced by 10%-20% compared with the power frequency power supply.

12. For compressors, vibrators and other loads with large torque fluctuations and hydraulic pumps and other peak loads, the power frequency operation status should be understood, and the inverter with additional output current greater than its maximum current should be selected.

13. When the inverter controls the roots fan, because its starting current is very large, we must pay attention to whether the capacity of the inverter is large enough when selecting the inverter.

14. When selecting the inverter, we must pay attention to whether its protection level matches the situation on site.

15. Single-phase motors are not suitable for inverter drive.

If there is only the high reliability of the inverter body, and the inverter selection and capacity matching are not appropriate, the frequency conversion speed regulation system composed of it cannot achieve high reliability, or even unable to operate, so how to ensure the normal and efficient operation of the frequency conversion adjustment system?

We want to make sure that the capacity of the inverter is matched. First of all, according to the nature of the load, the correct type of inverter is selected. The general criterion is what the nature of the load characteristics with what characteristics of the inverter.

(1) Constant torque production equipment - within the speed regulation range, the load torque is basically constant. A frequency converter with constant torque function should be selected. It can only be overloaded to maintain 150% additional current for 1 minute.

(2) Square torque production equipment - within the speed regulation range, the load torque is proportional to the square of the speed, that is, M∝n2, centrifugal fan, water pump is its typical representative. The inverter with M∝n2 characteristics can have a small overload, and the additional current of 110%-120% is overloaded for 1 minute.

(3) Constant power load production equipment - within the speed regulation range, the speed is low and the torque is large; The rotational speed is high and the torque is small. Typical equipment such as machine tools and winding weaves.

More on that
Schneider Electric has announced a partnership with RMSI Schneider Electric has announced a partnership with RMSI

Schneider Electric has named RMSI North America, an IT services company that provides geospatial and software solutions, as an ArcFM Specialty Partner. RMSI is well positioned to provide GIS solutions for utilities and telecommunications companies across the entire geospatial value chain...

Schneider electrical circuit control fault range Schneider electrical circuit control fault range

In general, depending on the phenomenon of equipment problems, the scope of the problem can be roughly confirmed as follows: 1) All button functions fail, and there is a high possibility of power supply or fuse problems. 2) Some buttons are invalid, and some of the buttons are functioning normally ...

Schneider selection of different types of circuit breakers Schneider selection of different types of circuit breakers

Miniature circuit breakers are: A9 (iC65, iDPN, etc.), M9 (C65, DPN, C120, NG125, etc.), E9, OSMC32N/OSMC65H, etc. Molded case circuit breakers are: NSX, NSE, EZD, NSC, large molded case NS. Structural circuit breakers include: MT, MTE, etc. ...

Schneider's new Modicon programmable controller PLC series Schneider's new Modicon programmable controller PLC series

Schneider Electric, the global energy efficiency management specialist, has launched the new Modicon Programmable Manipulator (PLC) M221 series, M241 series and M251 series under the MachineStruxure machine automation channel. This series of new products is tailored for industrial OEM shopping malls, relying on Schneider Electric global ...

Schneider circuit board maintenance work commonly used instrumentation Schneider circuit board maintenance work commonly used instrumentation

Before preparing to do circuit board repair work, you should prepare some things and appearances to help repairers better carry out circuit board repair operations, according to our circuit board repair training center for many years of experience has shown that prepare some necessary circuit board repair things and appearance, to be able to reach ...

Advantages and disadvantages of closed busbars compared with open busbars - Schneider Advantages and disadvantages of closed busbars compared with open busbars - Schneider

The advantages of closed busbars over open busbars are: 1) Closing the bus duct can reduce the grounding fault, avoid the short circuit between phases, basically eliminate the grounding defect caused by external moisture, dust and foreign objects, and improve the continuity of generator operation. 2) Eliminate ...

Schneider EZD series molded case circuit breaker is recommended Schneider EZD series molded case circuit breaker is recommended

Create a high-quality circuit breaker for secondary power distribution EZD molded case circuit breaker is a product series of molded case circuit breakers specially designed for secondary power distribution, especially suitable for secondary power distribution, civil construction market and mechanical and electrical market.

Schneider miniature circuit breaker code calling Schneider miniature circuit breaker code calling

Schneider miniature circuit breaker code marking method For example: 1-C65N-C20A/2P+VE+30mA+SD, the meaning of each item is: 1--------- identification number C65 ------ serial code N -------- breaking ability, N is 6000A, H is 10000A, L is 15kA ...

The cause of leakage in the motor using the inverter - Schneider The cause of leakage in the motor using the inverter - Schneider

1. The output of the inverter is controlled by PWM (pulse width modulation, similar to high-speed switching), so high-frequency leakage current will occur. The PE points of the three transmission equipment of the inverter, the pre-power supply transformer and the motor must be connected together and then grounded consistently. Frequency conversion...

Maintenance and overhaul of frequency converters and soft starters Maintenance and overhaul of frequency converters and soft starters

The protection and viewing of inverters and soft starters is a useful means to prevent occasional equipment problems. In order to be useful for protection and inspection, inspection orders should be created to record and save the inherent characteristics of the equipment and the stability of the constituent parts, so as to prevent problems and problems that occur.

Schneider improves plant performance with automated control Schneider improves plant performance with automated control

1. Engineering planning one by oneWith data at their fingertips and intelligent and sensitive functions, engineers can easily plan and test equipment, improve process availability, and easily complete system integration together – ultimately reducing the planning time by up to 25%. ...

Knowledge of Schneider Lexium32 servo motors Knowledge of Schneider Lexium32 servo motors

Schneider Lexium32 servo motor new generation servo release enriches Schneider Electric's high-end product line, its outstanding product functions, sensitive openness and user-friendly planning will better meet the high functional and safety requirements of industrial customers. In China's industrial production is increasingly moving towards energy-saving ...

Schneider disconnector operation inspection content and requirements Schneider disconnector operation inspection content and requirements

(1) Whether the closing of the barrier switch is defective, whether there is no failure or dislocation; (2) The porcelain insulation of the barrier switch should be free of cracks, discharge phenomena and flashover traces; (3), contact viewing: a, view ...

The energy-saving effect of using frequency converter for fan and pump loads The energy-saving effect of using frequency converter for fan and pump loads

Why is the use of inverter for fan and pump loads to save energy? According to the basic laws of fluid mechanics, it can be seen that the fan pump load is a typical square rotation load, and its main characteristics are: speed n and torque T and load ...

Schneider turbine flowmeter selection considerations Schneider turbine flowmeter selection considerations

1. According to the requirements of measurement intention: It is required to select the unit with instantaneous flow rate or cumulative flow rate (cumulative flow), the unit of flow display, measurement accuracy, repeatability, linearity, flow scale and scale, measurement temperature, pressure loss, temperature and pressure compensation, output signal characteristics and echoes.

Schneider intermediate relays Schneider intermediate relays

  Schneider 24VDC intermediate relays are the most common components in control systems. Generally, 2 normally open and 2 normally closed are the most commonly used, but sometimes 4 normally open and 4 normally closed contacts are not enough. Both have different coil and base models. ...

Advantages of the Schneider Magelis GXU touchscreen Advantages of the Schneider Magelis GXU touchscreen

1. Save capital contribution Focus on central function (true color LCD, serial communication interface, USB connection, Ethernet interface, etc.) 2. Save space Compact structure planning, only 38mm thick The fuselage is reserved for communication wiring ...

Schneider inverter maintenance inspection steps Schneider inverter maintenance inspection steps

1. Check whether the appearance of the inverter is in good condition, including whether the indicator light is in normal operation, whether the task control function of the operation panel is complete, and carefully observe the appearance of the inverter in operation, and do the corresponding recording operation; When repairing the inverter, check whether the voltage value and current value exceed the promised ...

Schneider XPS safety control module selection method Schneider XPS safety control module selection method

(1) Evaluate the safety control level that the machinery and equipment need to reach (2) Confirm the type of input signal to be monitored and (3) the number of input signals that need to be monitored (4) The number and type of channels that the module needs to output (5) Whether it is necessary to control the output device (such as ...

Schneider inverter Eplan file download Schneider inverter Eplan file download

Product line: Frequency converters and soft starters Solution(s): All Eplan software users can visit the Eplan website (directly from the Eplan software). The EPLAN database includes ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top