The preparation of the braking resistor of the inverter is mainly to consume part of the energy on the DC bus capacitor through the braking resistor to avoid the capacitor voltage being too high. Theoretically, if the capacitor stores a large amount of energy, it can be used to release it to drive the motor and avoid energy waste. However, the capacitance of a capacitor is limited, and the withstand voltage of a capacitor is also limited. When the voltage of the bus capacitor reaches a certain level, the capacitor may be damaged, and some even damage the IGBT. Therefore, it is necessary to brake the resistor in time to release the power. This release is wasted, and there is no way to do it.
Busbar capacitors are buffers with limited energy.
After all the three-phase alternating current is rectified, the capacitor is connected. When running at full load, the normal voltage of the bus is about 1.35 times, 380*1.35=513 volts. Of course, this voltage will fluctuate in real time, but the minimum should not be lower than 480 volts, otherwise it will give undervoltage alarm protection. The bus is generally composed of two sets of 450V electrolytic capacitors connected in series, and the theoretical withstand voltage is 900V. If the bus voltage exceeds this value, the capacitor will explode directly, so the bus voltage will not reach 900V anyway.
In fact, the withstand voltage of a 380 volt input three-phase IGBT is 1200 volts, and it is often required to operate within 800 volts. Considering that if the voltage rises, there will be an inertia problem, that is, if you immediately let the braking resistor work, the bus voltage will not drop quickly, so many VFDs go through the braking unit to let the braking resistor start to operate at about 700 volts, so as to reduce the bus voltage and avoid rising.
Therefore, the core of braking resistor planning is to consider the withstand voltage of the capacitor and IGBT module to prevent these two important devices from being damaged by the high voltage of the bus. If these two components are broken, the VFD will not work properly.
Fast parking requires braking resistance, and also needs instant acceleration.
The reason why the voltage of the VFD bus can become higher is that VFD is often the reason for it. Let the motor work in the electronic braking state, and let the IGBT go through a certain conduction sequence. By using the large inductance of the motor, the current does not change suddenly, and a high voltage is generated to charge the bus capacitor instantaneously. At this time, let the motor slow down quickly. At this moment, if there is no braking resistor to consume the energy of the bus in time, the bus voltage will continue to rise, threatening the safety of the VFD.
If the load is not heavy and there is no emergency stop required, there is no need to use a braking resistor in this case. Even if a braking resistor is installed, the operating threshold voltage of the braking unit is not triggered, and the braking resistor is not put into operation.
In addition to the need to add a braking resistor and a braking unit for fast braking in the case of heavy load deceleration, in fact, if the requirements of the heavy-load starting time and the starting time are very fast, the braking unit and the braking resistor are also required to start together. I once tried to drive a special punch machine with a VFD, and I asked the VFD to speed up to 0.1 seconds. At this point it starts at full capacity, although the load is not very heavy. However, due to the shortness of the acceleration time, the bus voltage fluctuates greatly at this moment, and overvoltage or overcurrent will also occur. Later, an external braking unit and braking resistor were added, and the VFD was able to operate normally. The analysis is because the starting time is too short, the bus capacitor voltage is instantly hollowed out, and the rectifier is instantly charged with a large current, resulting in a sudden increase in the bus voltage, which makes the bus voltage fluctuate too much, and it may exceed 700V in an instant. The participation of braking resistors can eliminate this wavering high voltage in time, and the VFD can operate normally.
There is also a special case where the torque and speed of the motor are in the opposite direction in the case of vector control, or the motor is operating at zero speed and outputs 100% torque. For example, the crane is stopped in mid-air, and torque control is required in the case of pay-off and pay-off, so that the motor needs to operate in the generator state, and the continuous current will be reversed into the bus capacitor. After the braking resistance, it can consume energy in time and adhere to the bus voltage balance and stability.
Many low-power VFDs, such as 3.7 kW, generally have a built-in braking unit and braking resistors. Considering the reason for the decline in bus capacitance, the small power resistor and braking unit are not so expensive.
|
More on that
|
Inverter frequency regulation fault solution - Reynolds
Most of the applications of frequency converters (hereinafter referred to as -VFDs) are primarily due to the fact that VFDs can change the output frequency and thus change the speed of the motor. If the frequency of the VFD cannot be adjusted and no damage is found on the hardware, it can be considered that the maximum output torque of the VFD is less than the load progress torque ...
|
|
"RNB6000 frequency conversion governor" was included in the National Torch Program
Recently, in the "2012 National Torch Program Project" issued by the Ministry of Science and Technology of the People's Republic of China, the "RNB6000 Frequency Conversion Governor" independently developed by Reynolds was included in the "2012 National Torch Program Project" with its domestic leading skills and efficient energy-saving conversion power.
|
|
Introducing the Reynolds JJR8000 series of intelligent soft starters
JJR8000 series of intelligent motor soft starter is the use of power electronics skills, microprocessor skills and modern control theory skills to produce today's international first-class starting equipment, the product can constrain the starting voltage of the asynchronous motor when starting, can be used in fans, water...
|
|
Reynolds inverter code function description
F09 second acceleration time 0.10 - 999.9sec; 5.0sec; △** The acceleration and deceleration parameters and the second acceleration and deceleration parameters are switched by terminal X3 (see F55);
F10 second deceleration time 0.10 - 999.9sec; 5.0sec; △**Acceleration and deceleration parameters and the second acceleration and deceleration parameters are switched ...
|
|
Inverter: The right inverter to use - Reynolds
Low pressure issues
The VFD reports a low voltage issue when the drive's DC link voltage drops below 62% of the nominal level at the high setting (480 Vac) and 50% of the nominal value at the low setting (400 Vac).
The +10% and -15% voltage tolerances in most manuals are the ones that claim to be ...
|
|
Inverter maintenance power-on test instructions - Reynolds
First, the inverter is not repaired and the power test is tested
(1) Inverter repair test rectifier circuit
At the two ends of the inverter to detect the internal DC power supply, P and N ends, adjust the multimeter to the resistance RX10 gear, the red watch pen is connected to the P end, and the black watch pen is connected to R, S, T, and there are tens of ohms under normal conditions.
|
|
Classification and working principle of Reynolds inverter
Classification of Reynolds frequency converters:
There are many classification methods for Reynolds inverters, which can be divided into voltage-type inverters and current-type inverters according to the classification of the main circuit operation method; According to the classification of switching methods, it can be divided into PAM operation.
|
|
General Purpose Inverter Repair Inspection – Reynolds
The first step is to check whether the appearance of the inverter is defective, including whether the indicator light is in normal operation, whether the mission control function of the operation panel is complete, and carefully observe the appearance of the inverter under the operating condition, and do the corresponding recording operation; When repairing the inverter, check whether the voltage value and current value exceed the ...
|
|
The inverter cannot adjust the frequency solution - Reynolds
1. The acceleration moment is too short.
Theoretically, the longer the acceleration time, the stronger the load lifting capacity. If the acceleration time is set too short, some VFDs will show an overcurrent or overload, overtemperature alarm, while others will not, and will only be stuck in a certain frequency band.
2.The V/F ratio is too large
Some of this ...
|
|
What inverter to choose what occasion - Reynolds
We need to ensure that the capacity of the inverter is matched. First of all, according to the nature of the load, the correct selection of the type of inverter.
When selecting the inverter, the current value of the actual motor should be used as the basis for the selection of the inverter, and the rated power of the motor can only be used as a ...
|
|
Structural characteristics of Reynolds RHY series inverter governor
1. Advanced technology: (PC or PLC) is used to make the equipment complete the intelligent constant pressure variable supply water supply according to the requirements of water supply and fire protection;
2. High efficiency and energy saving: the system can set the pressure according to the demand, and the system can actively adjust according to the set pressure.
|
|
Reynolds inverter manual
Reynolds inverter brochure (partial)
Before installing
When unpacking, it is found that the machine has water or left water traces, indicating that the inverter has been flooded, so please do not install and use it.
When unpacking, it is found that the machine is damaged and deformed or the parts are missing, please do not install and use it, otherwise there will be fault expansion and personnel ...
|
|
Methods and steps of frequency conversion speed regulation - Reynolds
Frequency conversion speed regulation is to change the power supply frequency through the frequency converter, and then adjust the motor speed to improve the operation efficiency of the electric drive system. Depending on the current, VFDs can be divided into AC-DC-AC type and AC-AC type. At present, the most widely used in China is the AC-DC-AC type.
...
|
|
Safety precautions for low-voltage soft lift - Reynolds
Precautions for low-voltage soft starters
For cooling purposes, the soft starter must be installed in a straight direction.
In order to ensure excellent heat dissipation, there should be room for the soft starter device.
Main circuit selection ...
|
|
Frequency converter overcurrent problem treatment - Reynolds
General treatment methods for inverter overcurrent problems:
The output side of the inverter is a PWM voltage waveform, and after passing through the motor winding, the output current is approximately a sine wave, and lags behind the voltage by a phase viewpoint, which is determined by the power factor of the motor. The output current of the inverter passes through ...
|
|
Inverter composition and various functions - Reynolds
Rectifier circuit: rectify 50HZ communication power into direct current.
Frequency conversion circuit: The rectified direct current is inverted into a variable frequency communication current.
Control part: control the frequency of communication electricity output by the inverter circuit.
Maintenance circuit: maintenance and blockage of overcurrent and phase loss ...
|
|
Wiring of Reynolds frequency converters
1 Main circuit wiring
(1) Reynolds inverter three-phase AC input terminal (R, S, T)
The power input terminal is connected to the three-phase AC power supply through the circuit breaker of the circuit breaker for line protection, regardless of the connection phase sequence. It should be noted here that the three-phase AC power supply is not ...
|
|
Features of Reynolds high-voltage frequency converters
RNVH-A series high-voltage inverter adopts multi-unit series multi-level technology, which is attributed to high-high voltage source inverter, which can directly input 6KV/10KV and direct 6KV/10KV output. Taking the 6KV series as an example, each phase is connected in series by 5 power units, and each power unit is isolated by the input transformer.
|
|
Motor soft start mode – Reynolds frequency inverter
Starting performance is a very important performance parameter of motor products. The large starting current of the motor is an unpreventable problem in the process of direct starting. The high current during the engine process has a great impact on both the power grid and the motor itself. Therefore, according to different working conditions and different series of motors, ...
|
|
Reynolds drives RNB1000 series fault code resolution
Reynolds inverter fault codes:
E.bC
Reynolds inverter fault phenomenon/type:
Brake unit failure
Reynolds inverter failure may be caused:
1. Brake line failure or brake ...
|
|