Inverter frequency regulation fault solution - Reynolds

Create Date: 2024-8-30 12:03:23|Source: RENLE/RENOLDS

Most of the applications of frequency converters (hereinafter referred to as -VFDs) are primarily due to the fact that VFDs can change the output frequency and thus change the speed of the motor. If the frequency of the VFD cannot be adjusted and no damage is found on the hardware, it can basically be considered that the maximum output torque of the VFD is less than the load progress torque caused by the failure, which is simply the VFD load can be poor.

                              Inverter frequency regulation fault solution - Reynolds

1. The V/F ratio is too large:

Some of these VFDs are also called torque advancements. If this parameter is set too large, it may not be able to start properly. If the cuts are appropriate, the problem is solved.

Second, the acceleration time is too short:

Theoretically, the longer the acceleration time, the stronger the ability to progress the load. If the acceleration time is set too short, sometimes VFD overcurrent, overload, and overtemperature alarms will appear, but some will not appear, but will only be stuck in a certain frequency band.

3. Set the maximum frequency and the maximum frequency is too low:

Generally, these two parameters are set to the maximum value, but there are some careless electricians who change these two parameters, so it will also cause the frequency to be unable to upcycle.

Fourth, the vector control parameters do not match.

In the vector control mode, it is necessary to accurately measure the internal resistance, inductance and other parameters of the motor, and to match the vector parameters of the VFD. After a period of operation, the motor parameters will overheat and form deviations. At this time, the current will be too large to start the motor normally, and the frequency may be stuck at a certain point. Re-optimizing the parameters solves the problem.

5. In some special occasions, the VFD parameters are set incorrectly.

In some cases, the minimum frequency cannot be set too low. For example, in a constant pressure water supply system, after the minimum frequency is set to 0Hz, when the pump pressure is low, when the starting frequency of VFD and VFD is exceeded, the start is accelerated, and the pressure cannot be added. The frequency of the VFD cannot progress to 50Hz, which is about 38Hz. After adjusting the PID repeatedly, the frequency cannot be improved. Only by setting the minimum frequency of VFD at about 15-20HZ can we be satisfied with the acceleration of VFD and keep the pump at a certain pressure. Although the pressure satisfies the constant pressure requirements, the VFD cannot be completely stopped without water and always maintains the lowest frequency speed.

For example, the minimum frequency of VFD in the constant pressure water supply system cannot be set to 0HZ, generally at least about 20HZ, which is determined by the flow rate and head of the pump.

The workaround is to set the sleep frequency. When the frequency of the pump (e.g. 28HZ) is running for a few minutes, the pump will go to sleep. When the pressure drops to 0.2-0.4MP lower than the set pressure, the pump will start. Another way is to set up a punctual water supply, which is supplied in several time slots. In general, the constant pressure water supply manipulator has the above functions.

6. Hardware failure of VFD

A similar situation can occur when the transformer (Hall) of the VFD is unable to properly measure the correct current. This can also be the case when a measuring element on another motherboard is aging. These are also common encounters when modifying VFDs

More on that
Inverter selection conditions and precautions - Reynolds Inverter selection conditions and precautions - Reynolds

1. When selecting the inverter, select the inverter with the appropriate control method according to the load characteristics In addition to the inverter manufacturing process, it is also important to choose which control method of the inverter. The control method of the inverter is mainly divided into two types: open-loop control and closed-loop control. In the meantime, the open-loop control method ...

The heat dissipation method of Reynolds switching power supply The heat dissipation method of Reynolds switching power supply

1. Transfer heat pipes for heat dissipation. In many applications, the heat generated from the base steel plate of the power module is transferred through the heat transfer components to the distant heat pipe surface. In this way, the temperature of the base steel plate of the power module will be equal to the temperature of the heat pipe heat dissipation surface, the temperature of the heat transfer parts, and the temperature of the two contact ...

Inverter power and box structure selection - Reynolds Inverter power and box structure selection - Reynolds

First, the selection of inverter power The system power is equal to the product of the inverter power and the motor power, and the system power is higher only when both are operating at a higher power. From the perspective of power, when selecting the power of the inverter, we should pay attention to the following points: 1) ...

Inverter replacement component requirements - Reynolds Inverter replacement component requirements - Reynolds

1) Find out the basic parameters and appearance of the equipment that needs to be replaced. The basic parameters include the rated operating current, the capacitance of the capacitor, the resistance value of the resistor, the value of the GTR Darlington device (current amplification factor), the switching characteristics and saturation voltage of the IGBT (including IPM) device, etc.

Inverter maintenance and undervoltage fault handling - Reynolds Inverter maintenance and undervoltage fault handling - Reynolds

In the repair of the inverter, we often hear about overpressure problems, but underpressure problems are also common problems encountered in the use of inverters. The reason is that the main circuit voltage is lower than the lower limit caused by the maintenance action or the damage of a rectifier bridge or the instantaneous power failure of the power grid, and the input is flat. Inverter after-sales ...

Reynolds inverter power selection Reynolds inverter power selection

The system power is equal to the product of the power of a general-purpose inverter and the power of the motor. As long as both work efficiently, the system power will be higher. From the perspective of power, when choosing VFD power, you should pay attention to the following points: VFD ...

Abnormal handling of inverter series reactor - Reynolds Abnormal handling of inverter series reactor - Reynolds

Capacitor series reactors generally adopt epoxy glass fiber multi-encapsulated parallel structure, according to the characteristics of the device site, three-phase vertical stacking, three-phase horizontal "△" and three-phase horizontal "-" type distribution. The substation in the southern area ...

Parameter setting of acceleration and deceleration time of Reynolds universal inverter Parameter setting of acceleration and deceleration time of Reynolds universal inverter

The acceleration time of the Reynolds inverter is the time required for the output frequency to rise from 0 to the high frequency, and the deceleration time is the time required to drop from the high frequency to 0. Usually, the inverter uses the frequency setting signal to rise and fall to confirm the acceleration and deceleration time. When the motor accelerates, the rise of the frequency setting must be constrained ...

Introducing the Reynolds JJR8000 series of intelligent soft starters Introducing the Reynolds JJR8000 series of intelligent soft starters

JJR8000 series of intelligent motor soft starter is the use of power electronics skills, microprocessor skills and modern control theory skills to produce today's international first-class starting equipment, the product can constrain the starting voltage of the asynchronous motor when starting, can be used in fans, water...

Inverter composition and various functions - Reynolds Inverter composition and various functions - Reynolds

Rectifier circuit: rectify 50HZ communication power into direct current. Frequency conversion circuit: The rectified direct current is inverted into a variable frequency communication current. Control part: control the frequency of communication electricity output by the inverter circuit. Maintenance circuit: maintenance and blockage of overcurrent and phase loss ...

How to control the torque of the inverter vector according to the system - Reynolds How to control the torque of the inverter vector according to the system - Reynolds

A brief introduction to the progress of the inverter in terms of torque: This function adds the output voltage of the inverter so that the output torque of the motor is proportional to the square of the voltage, so as to improve the output torque of the motor. Improve the skill of insufficient torque at low speed output of the motor, and use the "vector manipulation" ...

The solution to the low or high output of the differential pressure transmitter – ifm The solution to the low or high output of the differential pressure transmitter – ifm

When the differential pressure flowmeter (V-cone flowmeter) is used in the field, it often encounters such and such problems, but the reason for it is investigated, as long as it is installed correctly, the primary problem is on the secondary surface differential pressure transmitter, and the following is the first to introduce these problems to us ...

The difference between inverter motor and ordinary motor – Reynolds The difference between inverter motor and ordinary motor – Reynolds

Inverter motor - used for special occasions with inverter, it is different from the general motor in that a strong cooling fan is added. And the power of the fan comes from the independent power supply, can not be from the main motor out of the line, the effect of the strong cooling fan is to ensure that the motor at low speed...

General Purpose Inverter Repair Inspection – Reynolds General Purpose Inverter Repair Inspection – Reynolds

The first step is to check whether the appearance of the inverter is defective, including whether the indicator light is in normal operation, whether the mission control function of the operation panel is complete, and carefully observe the appearance of the inverter under the operating condition, and do the corresponding recording operation; When repairing the inverter, check whether the voltage value and current value exceed the ...

Inverter control method - Reynolds Inverter control method - Reynolds

The output voltage of low-voltage general frequency conversion is 380-650V, the output power is 0.75-400kW, and the operating frequency is 0-400Hz. Its control methods have gone through the following four generations. 1U/f=C Sinusoidal Pulse Width Modulation (SPWM) Manipulation MethodIts Characteristics ...

Inverter breakdown factor – Reynolds Inverter breakdown factor – Reynolds

1. Overpressure leads to brake pipe breakdown. The so-called overvoltage of the inverter refers to the fact that the inverter voltage composed of various reasons exceeds the additional voltage, which is reflected in the DC voltage of the inverter DC bus. Overvoltage alarm generally appears when the machine is shut down, and its main ...

The water pump is controlled by a frequency converter – Reynolds The water pump is controlled by a frequency converter – Reynolds

1. The constant pressure water supply of the inverter increases the comfort of water supply by 3 times 2. Constant water pressure, reducing pipe bursts and leakage by 80% 3. High efficiency and energy saving, power saving effect up to 20%-60% (depending on the actual situation) 4. The use of frequency converters can realize multi-point pressure in different time periods.

Analysis and repair of inverter failure cases - Reynolds Analysis and repair of inverter failure cases - Reynolds

1. The inverter can not speed up the frequency increase when it starts with load The 1366S-BR 040 inverter carries a load of 37 kW fan motors. During the trial operation, it was found that the inverter could not speed up the frequency increase normally, and the HIM display was speeding up. The inverter only swings at 1-4 Hz, and the motor emits a buzzing ...

Applicable mode of inverter maintenance - Reynolds inverter Applicable mode of inverter maintenance - Reynolds inverter

CNC cutting machine 1. Gradual reduction method The so-called gradual reduction method is to narrow the scope of shortcomings step by step by elaborating the shortcomings and judging the measurement parameters.

Features of electronic single-phase current transmitter – Reynolds Features of electronic single-phase current transmitter – Reynolds

Single-phase current transmitter is a kind of electric power test substation developed for the power measurement of single-phase communication in motor experiments on the basis of motor experiment and testing technology research, in accordance with IEC and relevant national specifications for motor experiments. The use of advanced filtering technology, reasonable software algorithms, ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top