Inverter: The right inverter to use - Reynolds

Create Date: 2024-8-30 12:03:23|Source: RENLE/RENOLDS

Low pressure issues

The VFD reports a low voltage issue when the drive's DC link voltage drops below 62% of the nominal level at the high setting (480 Vac) and 50% of the nominal value at the low setting (400 Vac).

The +10% and -15% voltage tolerances in most manuals are advocated for the scale of operation to allow the drive at hand to adhere to quality efficiency and proper motor current. Drives can fall below these tolerances, but the voltage drop can have unpredictable effects on motor current, motor temperature, and overall performance.

More specifically, if the drive's line voltage parameter is set high and 480 VAC is being applied, the driver will experience a low voltage problem when the DC link voltage drops to 62% of the nominal - such as 480 VAC ·0.62·√2= 421 VDC. The nominal DC link voltage is 480 Vac·√2= 679 Vdc.

                              Inverter: The right inverter to use - Reynolds

Precautions when switching

While it is accepted practice in many applications to switch VFDs from line power to standby generators, there are some constraints. On top of that, many portable standby generators have a phase-to-phase voltage input voltage swing that is greater than the phase-to-phase voltage tolerance of the driver referral, typically less than 2%. To avoid voltage flapping, VFDs are equipped with surge maintainers in the input rectifier circuitry – but significant input disturbances may require external maintenance (e.g. surge arresters). Large variances cause large ripple across the DC bus capacitors, which can cause capacitors and other power components to deteriorate over time.

Another potential problem presents when switching from line power to a standby generator. Most drives take at least two minutes to power up from scratch; Failure to follow this guide may damage the charging relay circuit, or at least damage the input fuse or trip the circuit breaker.

In the case of current surges caused by moderate voltage in the input power, a 3% line reactor may improve the situation.

Another solution is to add a voltage monitor with the right moment delay. They have a maintenance trip level that encloses the driver in the event of undervoltage, overvoltage, out-of-phase, and phase-to-phase voltage imbalance. These devices ensure that the VFD is not exposed to unbalanced input power or power-up until the voltage is within tolerance and the appropriate delay moment is met.

Barrier transformer

Finally, the most expensive solution is the use of barrier transformers. This ensures complete blocking of grounding and noise-related input power issues that may affect the driver. Do barrier transformers provide better maintenance than line reactors. When to use a demand barrier transformer? When the installation location is close to the substation, the use of this type of transformer is advocated.

Inserting a driver barrier transformer between the VFD and its power supply offers several advantages. Blocking guarantees that there is no direct electrical connection between the source and the load – but this is true for any transformer other than an autotransformer. What drive barrier transformers have in common is the placement of a ground electrostatic (Faraday) shield between and around the primary and secondary windings. This shielding reduces the capacitive coupling touched by transmission common-mode voltage disturbances by a factor of one million. Without this shielding, the capacitor allows high-frequency noise and transient voltage spikes to pass through the transformer.

Common-mode transients are transients that are presented between the ground and the neutral point of the communication system. Although these two parts of a circuit are generally combined at one point, they cannot be assumed to have the same potential in the entire power system. Common mode transient disturbances arise from the normal operation of equipment such as switching power supplies, drive operations, arc welders, lightning, and even stepper motors. Some barrier transformers can also prevent the "normal form" transients that occur between the line and the neutral.

Consider an application in which a substation capacitor bank in an industrial park causes transient voltage spikes caused by the daily utility power supply – amplified by reflections from field capacitors in a neighboring plant. Let's say a facility in the park has several small drives rated at 7.5 horsepower. Normal form transients may cause these drives to self-enclose, which can then lead to high-value process downtime. Barrier transformers can avoid this abort.

More on that
Introduction to soft starters and their relationship with frequency converters - Reynolds Introduction to soft starters and their relationship with frequency converters - Reynolds

When the high-power motor starts, the current is large, which will cause the grid voltage to be seriously shaken, in order to deal with this problem, the general requirements for speed regulation are not high, and the soft engine can be used to reduce the voltage and start. However, the drop in the starting current when the step-down is started will also make the starting torque drop significantly.

Operating procedures for Reynolds frequency converters Operating procedures for Reynolds frequency converters

Bypass cabinet: The cabinet is equipped with high-voltage inlet and outlet isolation switches QS1 and QS2. Among them, QS1 is a single-pole single-throw variable frequency incoming knife switch, and QS2 is a single-pole double-throw power frequency and variable frequency outgoing knife switch. The bypass cabinet is a high-voltage environment, please investigate the status of the live display and electromagnetic lock to ensure safety before ...

Frequency characteristics of Reynolds frequency converters Frequency characteristics of Reynolds frequency converters

a. Output frequency scale. The output frequency scale that can be controlled by the general inverter, the lowest starting frequency is generally 0.1Hz, and the highest frequency is different according to the functional indicators of the inverter, generally 400Hz, and some models are 650Hz. No matter how high the output frequency is, it depends on the scale of the high-frequency inverter. ...

Reynolds permanent magnet synchronous motor solutions Reynolds permanent magnet synchronous motor solutions

The permanent magnet synchronous motor has high-efficiency motor drive performance, which can complete high-speed, high-precision, high-stability, fast-responding, high-efficiency and energy-saving motion control. Reynolds drives provide a vector control technology solution for permanent magnet synchronous motors. ...

What inverter to choose what occasion - Reynolds What inverter to choose what occasion - Reynolds

We need to ensure that the capacity of the inverter is matched. First of all, according to the nature of the load, the correct selection of the type of inverter. When selecting the inverter, the current value of the actual motor should be used as the basis for the selection of the inverter, and the rated power of the motor can only be used as a ...

Reynolds soft starter manual Reynolds soft starter manual

Reynolds JJR5000 series all-digital intelligent AC motor soft starter adopts power electronics technology, microprocessor technology and modern control theory technology, and is a new type of starting equipment at the international advanced level. This product can effectively limit the starting current of asynchronous motor start-up, and is widely used in ...

Use the right power for the inverter – Reynolds Use the right power for the inverter – Reynolds

Low pressure issues The VFD reports a low voltage glitch when the drive's DC link voltage drops below 62% of the nominal level at the high setting (480 Vac) and 50% of the nominal value at the low setting (400 Vac). The +10% and -15% voltage tolerances in most manuals are the ones that claim to be ...

The way to set the parameters of the inverter - Reynolds The way to set the parameters of the inverter - Reynolds

There are many setting parameters of the inverter, and each parameter has a certain range of choice, and the inverter can not work normally due to the improper setting of a single parameter in use, therefore, the relevant parameters must be set correctly. ...

The inverter uses a power-saving method – Reynolds The inverter uses a power-saving method – Reynolds

As an electronic electric, the inverter itself also consumes electricity (about 3-5% of the rated power). A 1.5 hp air conditioner consumes 20-30W of electricity, which is equivalent to the length of a lamp. The inverter works under the power frequency and has the function of saving electricity, which is practical. However, the conditions are: First, high power and ...

Reynolds inverter code function description Reynolds inverter code function description

F09 second acceleration time 0.10 - 999.9sec; 5.0sec; △ The first acceleration and deceleration parameters and the second acceleration and deceleration parameters are switched by terminal X3 (see F55); F10 second deceleration time 0.10 - 999.9sec; 5.0sec; △ The first acceleration and deceleration parameters and the second acceleration and deceleration parameters ...

The difference between a soft starter and an inverter – Reynolds The difference between a soft starter and an inverter – Reynolds

The inverter changes the output frequency and voltage together, that is, changes the n0 on the motor running curve, so that the motor running curve moves parallel downward. Therefore, the inverter can make the motor reach its maximum torque with a small starting current, that is, the inverter can start the heavy-duty load.

The basic principle of vector control – Reynolds frequency converters The basic principle of vector control – Reynolds frequency converters

The fundamental principle of vector control is to control the excitation current and torque current of the asynchronous motor according to the principle of magnetic field orientation through the measurement and control of the stator current vector of the asynchronous motor, and then to achieve the purpose of controlling the torque of the asynchronous motor. Specifically, it is to ...

Precautions for low-temperature operation of VFD Precautions for low-temperature operation of VFD

1. VFD should be operated in an environment above minus 10°C as much as possible, and it is best to operate indoors. 2. When the VFD is started and stopped, try to start and stop with the VFD itself, do not close the power supply, and keep your VFD in a power-on state. 3. Give VFD l ...

Features of Reynolds high-voltage frequency converters Features of Reynolds high-voltage frequency converters

RNVH-A series high-voltage inverter adopts multi-unit series multi-level technology, which is attributed to high-high voltage source inverter, which can directly input 6KV/10KV and direct 6KV/10KV output. Taking the 6KV series as an example, each phase is connected in series by 5 power units, and each power unit is isolated by the input transformer.

Difference Between Soft Starter and Inverter – Reynolds Difference Between Soft Starter and Inverter – Reynolds

Soft starters and frequency converters are two completely different products. The inverter is used in the local area where speed regulation is required, and its output not only changes the voltage but also changes the frequency at the same time; A soft starter is actually a voltage regulator, which is used when starting a motor, and the output only changes the voltage and does not change the frequency. Change...

The cause of damage to the inverter brake unit - Reynolds The cause of damage to the inverter brake unit - Reynolds

The inverter motor is equipped with a mechanical brake, is the inverter motor in the power generation condition when parking? Is the brake unit of the inverter working at the moment? What are the causes of brake unit damage? Answer: 1. The inverter motor is equipped with a mechanical brake, and when parking...

Features of the unit tandem inverter - Reynolds Features of the unit tandem inverter - Reynolds

(1) The multi-pronged PWM control method is selected, and the output voltage waveform is close to the sine wave. (2) The rectifier circuit is multiplied, the number of pulses is as high as 36, the power factor is high, and the input harmonic is small. (3) Modular design, compact structure ...

AC servo motor with inverter control method - Reynolds AC servo motor with inverter control method - Reynolds

Because the inverter and servo are different in performance and function, and the use is not very different, it is not possible: 1) In the case of speed control and torque control, the general frequency converter is not very high, and there are also frequency converters that are used to react signals in the upper position to form a closed loop.

Motor soft start mode – Reynolds frequency inverter Motor soft start mode – Reynolds frequency inverter

Starting performance is a very important performance parameter of motor products. The large starting current of the motor is an unpreventable problem in the process of direct starting. The high current during the engine process has a great impact on both the power grid and the motor itself. Therefore, according to different working conditions and different series of motors, ...

Reynolds drives use the most energy-efficient method Reynolds drives use the most energy-efficient method

As an electronic electric, the inverter itself also consumes electricity (about 3-5% of the additional power). A 1.5 hp air conditioner consumes 20-30W of electricity, which is equivalent to the length of a lamp. The inverter works under the power frequency and has the function of saving electricity, which is practical. But the conditions are: At the top of the list, great success ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top