We need to ensure that the capacity of the inverter is matched. First of all, according to the nature of the load, the correct selection of the type of inverter.
When selecting the inverter, the current value of the actual motor should be used as the basis for the selection of the inverter, and the rated power of the motor can only be used as a reference. Secondly, it should be fully considered that the output of the inverter contains higher harmonics, which will form the power factor and efficiency of the motor.
Current matching: For ordinary centrifugal pumps, the rated current of the inverter is consistent with the rated current of the motor. For special loads, such as deep-water pumps, it is necessary to refer to the motor performance parameters and confirm the inverter current and overload ability with the highest current. The current setting of the inverter should not be less than 1.1 times of the rated current of the motor, and the highest current is generally set to 1.5 times of the rated current of the motor.
Special applications
For example, high ambient temperature, high switching frequency, high altitude, etc., will cause the derating of the inverter at this moment, and the inverter needs to be enlarged by one gear.
When the inverter is used to drive the high-speed motor, the output current value increases due to the small reactance of the high-speed motor and the increase of higher harmonics. Therefore, the capacity of the inverter used for high-speed motor is slightly larger than that of ordinary motor.
When driving an explosion-proof motor, the inverter does not have an explosion-proof structure, and the inverter should be set up outside the risk area.
|
More on that
|
Progressive method of robustness of automatic control cabinets – Reynolds
1. Appropriate working environment
1. The ambient temperature is suitable
All manufacturers have certain rules for active temperature control cabinets. The PLC promises that the ambient temperature is usually about 0 to 55 ° C, so during the equipment process, this heating element is not placed in the PLC; The PLC should have adequate ventilation and ...
|
|
Fault signal of the frequency converter - Reynolds frequency converter
There are three types of fault signals for the inverter:
(1) Excessive mechanical load: The primary feature of excessive load is that the motor heats up, and the operating current can be read from the display screen to find. The primary reason is that the load of the inverter is too large, and the acceleration and deceleration time and operation cycle time are too short; V/F ...
|
|
Inverter speed regulation method - Reynolds
1. Pole change logarithmic speed regulation method
This speed regulation method is to change the number of stator poles of the cage motor by changing the connection method of the stator winding, so as to reach the intention of speed regulation; The wiring is simple, the control is convenient, and the price is low; It can be used in conjunction with pressure and speed regulation, electromagnetic slip clutch to obtain high efficiency ...
|
|
Analysis and repair of inverter failure cases - Reynolds
1. The inverter can not speed up the frequency increase when it starts with load
The 1366S-BR 040 inverter carries a load of 37 kW fan motors. During the trial operation, it was found that the inverter could not speed up the frequency increase normally, and the HIM display was speeding up. The inverter only swings at 1-4 Hz, and the motor emits a buzzing ...
|
|
The reason why the inverter burns the power supply inlet end - Reynolds
1. It is necessary to consider the touch and current size of the incoming terminal, if the terminal standard is small, perhaps the conductive function of the terminal is poor, which will directly cause the current carrying capacity of the terminal to be small and heated.
2. The inlet at the end of the inlet line must be pressed well and the like, if it is not pressed, it may cause ...
|
|
The lightning protection method of Reynolds inverter
The lightning protection measures of the inverter equipment are another important peripheral measure to ensure the safe operation of the inverter, especially in the area where lightning is active or in the lively season, this problem is particularly important.
Today's inverter products are generally equipped with lightning ...
|
|
Small fan inverter choice - Reynolds
Now many electrical appliances are advocating the use of small parts, because small parts will not occupy space, and small parts can be moved and overhauled at any time, and the inverter also has a small inverter, how to buy a small fan inverter?
Power picking
...
|
|
The difference between inverter motor and ordinary motor – Reynolds
Inverter motor - used for special occasions with inverter, it is different from the general motor in that a strong cooling fan is added. And the power of the fan comes from the independent power supply, can not be from the main motor out of the line, the effect of the strong cooling fan is to ensure that the motor at low speed...
|
|
Reynolds assisted Sinopec Weirong shale gas project
With the rapid development of China's national economy, the supply and demand situation of oil and gas resources is becoming increasingly severe, and the import of oil and gas is increasing year by year, so it is urgent to expand the field of domestic oil and gas exploration and development. Strengthening the exploration and development of shale gas resources can make up for the lack of conventional oil and gas resources and promote the sustainability of the oil and gas industry.
|
|
Structural characteristics of Reynolds RHY series inverter governor
1. Advanced technology: (PC or PLC) is used to make the equipment complete the intelligent constant pressure variable supply water supply according to the requirements of water supply and fire protection;
2. High efficiency and energy saving: the system can set the pressure according to the demand, and the system can actively adjust according to the set pressure.
|
|
Frequency conversion cabinet external conduit wiring method - Reynolds
When it is required to wiring outside the frequency conversion cabinet, it is generally necessary to use the conduit for wiring, which requires suitable mechanical pressure and unsuitable mechanical damage, moisture-proof and corrosion-resistant. Conduits include the following two wiring methods:
1. Kim ...
|
|
Precautions for installation of Reynolds low-voltage inverters
One. Safety Precautions
1. First of all, it is necessary to have certain electrical professional knowledge, and understand the job site, understand the equipment status, and have certain electrical operation technology.
2. Determine the voltage level of the equipment (such as low-voltage AC380V) and whether it is low-voltage ...
|
|
Rated current analysis of inverter leakage circuit breaker
The output of the inverter is controlled by PWM (pulse width modulation, similar to high-speed switching), so a high frequency leakage current will occur, if you want to install a general leakage disconnect switch on the primary side of the inverter, it is recommended to select a sensitivity current of more than 200mA for each inverter and the action time is 0.1 seconds ...
|
|
The breaking capacity of the industrial control appliance switch
Assuming Icu=60KA, then when a faulty current of 60KA is generated in the line, the circuit breaker can safely cut off the circuit without abnormal conditions such as contact welding and blasting. Pay attention to the extreme breaking ...
|
|
Precautions for Wiring Reynolds Inverters
1. The inverter itself has a strong electromagnetic disturbance, which will disturb the work of some equipment, so we can add a cable sleeve to the output cable of the inverter.
2. The control line in the inverter or control cabinet is at least 100mm away from the power cable, etc.
...
|
|
The difference between servo and inverter - Reynolds
Overload can be different
Servo drives generally have 3 times the overload ability, which can be used to overcome the inertial moment of the inertial load at the moment of start-up, while the frequency converter generally allows 1.5 times the overload.
Handling precision
Servo control ...
|
|
Inverter leakage solution - Reynolds
1. The cause of the leakage problem
Some sites use frequency converters to control the motor, which will present the problem of leakage, and the leakage voltage ranges from tens of volts to 200 volts. In view of this problem, the reasons for this shortcoming are theoretically expounded and stated as follows.
Depend on...
|
|
Classification and working principle of Reynolds inverter
Classification of Reynolds frequency converters:
There are many classification methods for Reynolds inverters, which can be divided into voltage-type inverters and current-type inverters according to the classification of the main circuit operation method; According to the classification of switching methods, it can be divided into PAM operation.
|
|
Wiring of Reynolds frequency converters
1 Main circuit wiring
(1) Reynolds inverter three-phase AC input terminal (R, S, T)
The power input terminal is connected to the three-phase AC power supply through the circuit breaker of the circuit breaker for line protection, regardless of the connection phase sequence. It should be noted here that the three-phase AC power supply is not ...
|
|
Reynolds inverter parameter settings
The use of Reynolds inverters in industrial production is very important, in addition to speed regulation, soft start effect, the important thing is to be able to save energy. There are many functional parameters of Reynolds inverter, and there are generally dozens or even hundreds of parameters for users to choose. In practice, it is not necessary to ...
|
|