First, the disadvantages
Choosing too high a voltage level results in too high an investment and a long payback period. With the increase of the voltage level, the insulation of the motor must be improved, so that the price of the motor increases. The increase of voltage level increases the number of series connections of power semiconductor devices in the inverter, and the cost rises.
It can be seen that it is extremely uneconomical and unreasonable to use 6kV and 10kV voltage levels for 200-2000kW motor systems.
Second, the relationship between the number of phases
The inverter device put into the 6kV power grid must comply with the national regulations on harmonic suppression. This is related to the capacity of the grid and the power rating of the device.
The short-circuit capacity is within 1000MVA, and the 1000kW device can be 12 phases (transformer secondary side double winding), if the 24-phase power can reach 2000kW, the 12-phase basically eliminates the 5th and 7th harmonics with large amplitudes.
After the number of rectifier phases exceeds 36 phases, the harmonic current amplitude decreases insignificantly, and the manufacturing cost is too high. If the grid short-circuit capacity is 2000MVA, the allowable capacity of the installation is larger.
3. Save investment
Considering the necessity of voltage level from the characteristics and safety factor of power electronic devices, limited by the voltage of power electronic devices and the allowable dv/dt of the motor, the 6kV inverter must be connected in series with multiple levels or multiple devices, resulting in complex lines, expensive and poor reliability. For the 6kV inverter, if 1700VIGBT is used, take the PERFECTHARMONY series of 6kV high-voltage inverter of United States Robin Kang as an example, each phase is connected in series by 5 power units with a rated voltage of 690V, and a total of 60 devices in three phases. If 3300V devices are used, a total of 30 devices in 3 strings are also required, which is a huge number. On the other hand, the device current is small, the current capacity of the device is not fully utilized, taking 560kW as an example, the current of the 6kV motor is only about 60A, and the IGBT current of 1700V has reached 2400A, and the current of the 3300V device is 1600A. Even with a motor power of 2,000 kW, the current is only about 140 A, which is still very small.
Foreign medium voltage inverters have multiple voltage levels: 1.1kV, 2.3kV, 3kV, 4.2kV, 6kV, which are mainly determined by the voltage level of power electronic devices.
For an inverter with the same output, the cost of using a higher voltage or more units in series is greater than the cost of using a lower voltage, a smaller number of units with a larger current, that is to say, the lowest voltage level should be selected as much as possible under the allowable condition of the device current.
Fourth, the issue of isolation
In order to isolate, improve the input current and reduce harmonics, all medium-voltage "direct inverters" are not true direct inverters, and their input side is equipped with an input transformer, which will not change for a short time. Since there is a transformer on the input side, the voltage of the inverter and the motor is not necessary to be the same as the power grid, 10kV and 6kV must be used, and the voltage below the power of 2500kW can not exceed 3kV, so there is a reasonable voltage level of the inverter and the motor.
——380V or 660V voltage level should be selected for frequency conversion speed regulation below 800kW. It has simple lines, mature technology, high reliability, small DV/DT and low price. Taking 560kW motors as an example, there are about 350,000 low-voltage inverters with 630kW and 660V low-voltage inverters, and about 900,000 medium-voltage inverters with the same capacity of 6000V. There are several forms of low-low, low-high, high-low, and high-low-high. Because of the motor, the price of the transformer is much lower than that of the inverter, and even if the motor and transformer are replaced, it is reasonable.
Fifth, how to match
How to match the original 6kV high-voltage motor with the 3.5kV inverter voltage
Since the founding of the People's Republic of China, the traditional 6kV high-voltage motor is the main product that has been put into production, in order to promote the 3.5kV inverter can no longer spend money to replace the motor, the author proposes a simple scheme for reference.
The original 6kV motor in the manufacturer is generally star-wired, and the actual voltage of the phase winding is 3468V, so as long as the winding is reconnected to a triangle, the others remain unchanged. With a 3.5kV inverter, the inverter voltage is reduced from 6kV to 3.5kV, and it can be seen from Table 3 that the 4.5kV device can withstand 3kV withstand voltage without being connected in series. If you use a 1.7kV device for 3 strings, you can do it. Manufacturing costs will drop by 30%. At present, the maximum motor of 30MW unit in China is 2500kW, and the voltage of 3.5kV is completely reasonable.
6. Harmonic pollution
From a practical point of view, the rectifier bridge is composed of 12-phase rectification, which can eliminate the 5th and 7th harmonics, which basically meets the harmonic requirements of the power grid. Therefore, 400kW-800kW can be rectified with 12 phases, and 1000kW-2500kW with 24 phases can also meet the requirements.
|
More on that
|
Introduction to Yaskawa inverter fault codes
1. If the fault code on the Yaskawa inverter is UV1, then it means that the low voltage of the main circuit is lower than the low voltage standard of 200V, at this time, we need to check whether there is a problem with the wiring of the power supply;
2. If the fault code appears on the Yaskawa inverter ...
|
|
Yaskawa servo drive parameters
PN000 function selection N.0010 (setting value) 0th position: set the direction of rotation of the motor; Set "1" to change the rotation of the motor in reverse. 1st position: Set the control mode to: "1" position control mode.
PN200 Command Pulse Input Mode Function Selection N.0101 (Set Value) "1" Positive ...
|
|
Common faults and solutions of Yaskawa inverter
(1) Overcurrent, display character: OC. The reason for tripping is the short circuit of UVW at the output end, the load is too large, the acceleration/deceleration time is set incorrectly or the torque is unreasonable, resulting in overcurrent or overheating of the main circuit module. Check whether there is a short circuit in the motor junction box, whether the motor winding is to the ground, phase to phase ...
|
|
There are three control modes of Yaskawa servo motor
1. Torque control mode: The torque control mode is to set the output torque of the motor shaft through the input of the external analog quantity or the assignment of the direct address, which is manifested as 10V corresponding to 5Nm, when the external analog quantity is set to 5V, the output of the motor shaft is 2.5Nm: if the electric ...
|
|
Yaskawa invested in Europe to win local customers in Europe
Sina U.S. stock news on the 29th Beijing time Nikkei Chinese Network reported that Japan's Yaskawa Electric will launch an offensive in the European industrial manipulator sales market. In September 2018, Yaskawa Electric will open Europe's first intelligent robot processing plant in South America, with the intention of winning the "European company" as a "European company".
|
|
Yaskawa servo alarm C90 (AC9) troubleshooting method
1. Analysis of the causes of Yaskawa servo alarm C90 (AC9):
1. The encoder cable is broken or the encoder plug is made in poor process (there are also wiring errors in the alarm of the new machine);
2. The servo drive itself is faulty;
3. Environmental interference, caused by poor connection: ...
|
|
Yaskawa servo drive fault code
Yaskawa servo drives are used to control servo motors, which are similar to AC motors and are part of the servo system. The servo drive takes the digital signal processor as the control core, which can realize more complex control algorithms and realize digitalization, networking and intelligence. The present invention adopts the wisdom ...
|
|
Yaskawa Robot - the basic function of the robot control system
(1) Memory function: store operation sequence, motion path, motion mode, motion speed and information related to production process;
(2) Teaching function: offline programming, online teaching, indirect teaching. There are two types of online teaching: teaching box and guided teaching;
(3) With ...
|
|
Yaskawa servo drive failure causes and maintenance treatment
Yaskawa MOTOMAN servo drive fault repair:
1. The motor runs faster in one direction than in the other;
(1) Cause of failure: The phase of the brushless motor is wrong.
Solution: Detect or detect the correct phase.
(2) Cause of failure: In the absence of ...
|
|
Yaskawa inverter installation precautions
Precautions for installing Yaskawa inverter
Do not turn on the power supply during wiring operations, otherwise there will be a risk of electric shock.
In order to prevent electric shock, please do not operate in the state of removing the inverter cover, otherwise there will be a risk of electric shock.
Be sure to ground the ground terminal on the motor side ...
|
|
Yaskawa inverter - how to check the mechanical system failure of elevator failure
1. Failure of mechanical system
(1) The common fault phenomena and causes of mechanical systems are as follows
1. Due to poor lubrication or lubrication system failure, the rotating parts of the parts are seriously heated and worn or the shaft is held, resulting in the destruction of the parts of the rolling or sliding parts.
2 ...
|
|
Yaskawa Servo Drive FAQ (1-9)
[1] Yaskawa 5 series 1KW drive on telegram 030 what is the reason?
When you power on, it will display 030, check the manual to explain: the main circuit is abnormal in various detection data, and there is no problem with the main circuit module after checking.
Is there a motherboard that can be swapped to try, if not...
|
|
Yaskawa has actively fought the epidemic and gradually and steadily recovered its industry
On July 10 this year, Yaskawa Electric announced the announcement of the consolidated accounting liquidation report for the period of March ~ May this year (according to the international accounting standards for business enterprises). Of this amount, the total profit was $620,000, down 22% from the same period last year. Main electric ...
|
|
Detailed explanation of Yaskawa inverter fault codes
1. The manifestation of the fault code of Yaskawa inverter
When the Yaskawa inverter has a fault code, there are three manifestations:
1. Failure
When a fault is detected, the following conditions occur.
The LED operator has a text indicating the content of the fault, and the ALM refers to ...
|
|
YASKAWA The success of industrial automation starts here
Founded in 1989, Yaskawa Motoman is a leading industrial robotics company in the Americas. With more than 400,000 Motoman industrial robots, 15 million servos and 26 million inverter drives installed worldwide, Yaskawa provides automation products and ...
|
|
Analysis of fault codes of Yaskawa inverter
Analysis of the fault code of Yaskawa inverter, for reference only:
OC Overcurrent The output current of the inverter exceeds the overcurrent detection value ·
GF grornd Favlt Grounding The ground current on the output side of the inverter exceeds 50% of the rated output current of the inverter
...
|
|
Yaskawa MH24 handling robot maintenance routine inspection
Yaskawa Robot is a well-known robot manufacturer in the world, it is one of the four major robot families, and has launched Yaskawa MH24, it is a multi-functional robot, which is widely used in industrial production, and the following look at Yaskawa MH24 handling robot maintenance routine inspection. ...
|
|
What is the reason for Yaskawa servo alarm AF5?
1. When the control power supply is put in, it is caused by the failure of the servo unit circuit board, and the servo unit needs to be replaced.
2. When it occurs in servo ON, then it is caused by the failure of the servo unit circuit board or the short-term motor power line, and the servo unit or motor needs to be replaced.
|
|
What are the faults of Yaskawa inverter?
The following are the common faults of the inverter and how to deal with them
1) OC Over Current
This is the most frequent failure of the inverter, and it is divided into external and internal causes in the analysis of causes. External causes: mechanical structure and parameter setting, open-loop control ...
|
|
Yaskawa inverter - introduction to the basic principle of high-voltage inverter
High-voltage and high-power variable frequency speed control devices are widely used in various fans, pumps, compressors, rolling mills, etc. in large-scale mining production plants, petrochemical industry, municipal water supply, metallurgical steel, power and energy industries.
In metallurgy, chemical, electric power, municipal water supply and mining and other industries...
|
|