Requirements for Pilz to fix safety switches

Create Date: 2024-8-30 12:03:23|Source: PILZ/PILZ

Safety doors are mainly used to prevent the operation of the machine under certain conditions (usually when the guard is not closed) in order to avoid the occurrence of danger as much as possible. If the installation of the safety door switch itself is not compliant, resulting in its interlocking function cannot be realized correctly, "inaction when it is time to act" is obviously what everyone does not want to see. Therefore, the first priority when applying a safety switch is to use it correctly.

Requirements for securing the safety switch

Compliant installation is the premise of ensuring the normal function of the safety switch, and the following will tell you some requirements for fixing the safety switch:

The fastener itself needs to be reliable and stable enough.

It can be removed with specialized tools, such as hexagon screws, star screws, etc. Phillips/slotted screws are not recommended, as in some cases they can be easily opened with fingernails or personal equipment.

Fasteners need to prevent themselves from loosening, and when appropriate, consider the necessity of elastic washers or screw glue.

It is necessary to prevent damage caused by foreseeable external shocks, and to judge the installation location according to the actual situation, such as the water level that is often walked away from people and forklifts often pass.

Mechanical switches need to be carried out within the specified operating range, especially for mechanical deadbolts, the length of which is fixed, if the installation distance is not calculated, it is easy to cause physical damage to the switch if it is often operated.

The safety door switch is not allowed to be used as a mechanical stop and mechanical stop for protection, and it is also to avoid damage to the switch body and operating head, reduce unnecessary physical impact as much as possible, and prevent safety failure and service life reduction

In practical applications, some operators, for the sake of temporary convenience, in the case of safety protection opening, artificially make the safety switch often have signals, such as taking an additional operating head to tie it to the switch body, so that it can not function normally. In order to eliminate potential safety hazards caused by non-standard operations at the operational level, the ISO14119 standard specifically describes "supplementary measures to minimize the possibility of discarding interlocks", which is the anti-shielding measures for safety switches that we often mention.
Requirements for Pilz to fix safety switches

More on that
The Pilz Safety PC PSS 4000 system provides customers with a better service The Pilz Safety PC PSS 4000 system provides customers with a better service

When building a safety system, it is particularly important to arrange the components of the safety system reasonably, which determines whether the reliability of the entire system can be guaranteed. Nowadays, with the gradual popularization of safety concepts, people's requirements for safety automation are getting higher and higher, and the scenarios of safety PLC applications are also increasing. ...

Peel magnetic relays – the difference between safety relays and general relays Peel magnetic relays – the difference between safety relays and general relays

1) Larger shape: The safety relay is different from the ordinary relay, and the safety relay is larger. 2) Modules instead of components: A safety relay is a module, not an electronic component like a normal relay. 3) Red and yellow: The safety relay has ...

The main anti-shielding measures of Pilz safety switches The main anti-shielding measures of Pilz safety switches

1. Physical location of the installation – "out of reach or out of sight" Consider installing the component in a place that is out of the reach of personnel, or directly outside the interlock switch as a protective cover to prevent disassembly or movement, as shown in the figure, whether it is a mechanical interlock on the left, or a non-...

Pilz will be exhibiting at SPS Smart Production Solutions 2022 Pilz will be exhibiting at SPS Smart Production Solutions 2022

From 8 to 10 November 2022, at the SPS trade fair for intelligent production solutions in Nuremberg, Pilz will focus on automation solutions for safety and industrial security in plants and machinery under the theme "Safe and reliable".   Safe and cost-effective control ...

How Pilz replaces the safety switch How Pilz replaces the safety switch

1. First, unscrew out the fixing screws of fixing the noodle frame and the water baffle plate according to the above steps; 2. Unscrew out the two screws that fix the safety switch, and pull out the two lead pins connecting the safety switch; 3. Replace the new safety switch and assemble it according to the original steps. Electrical safety switch ...

Pilz: Don't underestimate the authorization key, it can make a big difference! Pilz: Don't underestimate the authorization key, it can make a big difference!

With the increasing functional requirements of industrial production, the continuous optimization of process levels and the escalation of the complexity of production conditions, systems that effectively record and manage relevant data are particularly important for machine safety, especially for production safety. PITreader Authorization ...

PILZ presents the new base module PNOZmulti2 – PNOZ m B0.1 PILZ presents the new base module PNOZmulti2 – PNOZ m B0.1

In terms of functionality and cost-effectiveness, it is more suitable for customer needs of small and medium-sized security applications. "Similarities and differences" between PNOZ m B0 and PNOZ m B0.1 Similar to PNOZ m B0, the base module body of PNOZ m B0.1 offers 20 safe digital inputs that can be freely combined.

Pilz: Configurable safety relays with reliable delivery times Pilz: Configurable safety relays with reliable delivery times

Have you encountered any of the pain points of these safety relay applications? Since the invention of the first emergency stop safety relay by Pilz in 1987, after twenty or thirty years of development, the current safety relay market can be described as a hundred flowers blooming and a hundred schools of thought contending. Although, the currently selectable security relay ...

Peel magnetic relays - characteristics and principles of use of safety relays Peel magnetic relays - characteristics and principles of use of safety relays

The fundamental characteristics of safety relays: Feature 1, can be used in some automatic control occasions: safety relay - a kind of equipment that can control safety, this equipment is very easy to use in the automatic control field. Generally, there are emergency stops or safety doors, as well as safety gratings and other input devices.

Pilmagnetic switch – the role of a load switch Pilmagnetic switch – the role of a load switch

1. Breaking and closing. Because it has a certain arc extinguishing ability, it can be used to break and close the load current and the overload current of a certain multiple (usually 3-4 times) of the small stem; It can also be used to break and close a no-load transformer with a larger capacity than the disconnector allows, a longer no-load line ...

The working principle and characteristics of Pilz safety relays The working principle and characteristics of Pilz safety relays

Pilz safety relays generally consist of an iron core, a coil, an armature, a contact reed, etc. As long as a certain voltage is added to both ends of the coil, a certain current will flow through the coil, resulting in an electromagnetic effect. Under the action of electromagnetic attraction, the armature overcomes the pulling force of the return spring and sucks in the iron ...

Pilz: Buying VS Retrofit? Take a look at the selection of the Austrian company Pilz: Buying VS Retrofit? Take a look at the selection of the Austrian company

When part of the production line no longer meets the current production needs, do you choose to buy new equipment or modify old equipment? Scheucher, a hardwood flooring manufacturer based in Austria, was faced with such a choice not so long ago. In Scheuch ...

Pilz has launched the new PNOZmulti2 base module PNOZ m C0 Pilz has launched the new PNOZmulti2 base module PNOZ m C0

Pilz's new PNOZmulti2 base module, PNOZ m C0, is sure to be the next big thing...... The reason is simple, it has a compact design, a beautiful price, and the functionality is not "ambiguous" at all, after all, it belongs to the PNOZmulti family.   The basic module of PNOZ m C0 ...

Pilz is actively involved in the research and practice of Industrie 4.0 Pilz is actively involved in the research and practice of Industrie 4.0

With the advancement of history, people have experienced the transformation from light industry to heavy industry, and then entered the era of automation brought about by innovation in the field of electronic computer technology and other scientific and technological fields.   The wisdom and potential of human beings are limitless, and today in the 21st century, we are experiencing new ...

Pilz: Safety light curtains for hand protection Pilz: Safety light curtains for hand protection

The tightly meshing beam field of the safety light curtains PSENopt and PSENopt II is ideally suited for all applications where hand protection is required. By placing the safety light curtain close to the danger zone, the operator can be optimally protected and the workflow will not be interrupted, making it ideal for spaces with ...

Pilz: A new version is here! This time it's more powerful Pilz: A new version is here! This time it's more powerful

Since its launch, Pilz's flagship product, the configurable and safe small controller PNOZmulti, has been impressed by users for its robustness, flexibility and ease of operation. PNOZmulti Configurator as a configuration tool for the safe small controller PNOZmulti ...

Peel magnetic relays – testing of relays Peel magnetic relays – testing of relays

(1) Measure the resistance of the contact: use the resistance of the multimeter to measure the resistance of the normally closed contact and the moving point, and the resistance value should be 0; The resistance between the normally open contact and the moving point is infinite. From this, it is possible to distinguish which is a normally closed contact and which is normally open. (2) Coil resistance: multimeter R...

Pierre magnetic switch – the function of the disconnector Pierre magnetic switch – the function of the disconnector

1. After opening, establish a reliable insulation gap to separate the equipment or line that needs to be overhauled from the power supply with an obvious disconnection point to ensure the safety of maintenance personnel and equipment. 2. According to the operation needs, change the line. 3. It can be used to divide and combine small currents in the line, ...

Pilz was unveiled at the "Safety Standardization" theme exhibition of China Machinery Industry Safety and Health Association Pilz was unveiled at the "Safety Standardization" theme exhibition of China Machinery Industry Safety and Health Association

The "Safety Standardization" theme exhibition organized by the China Machinery Industry Safety and Health Association and the National Machinery Safety Standardization Technical Committee was unveiled at the China Yiwu International Commodities (Standards) Expo held from November 24 to 27, 2022. Automation specialist Pilz was invited to participate in the exhibition to demonstrate ...

Pilz safety switches – wiring methods for safety switches Pilz safety switches – wiring methods for safety switches

1. The switch binding post is generally marked with L, L1, L2. When the L end enters the line, L1 and L2 have one end and L on, and after pressing the switch, the other end of L1 and L2 is connected to L. 2. Peel the thread with diagonal pliers first, and be careful not to leave too long the thread to avoid touching. 3. To the left ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top