What causes inaccurate measurements in Rosemount pressure transmitters

Create Date: 2024-8-30 12:03:23|Source: Rosemount/Rosemount

Rosemount Pressure Transmitter Inaccurate Measurement Causes:
What causes inaccurate measurements in Rosemount pressure transmitters
  1. Whether the power supply of the Rosemount pressure transmitter is normal, if it is less than 12VDC, then check whether there is a large load in the circuit, and the input impedance of the transmitter load should meet the Ω of RL≤ (transmitter supply voltage -12V)/(0.02A).

2. Whether the pressure sensor of the Rosemount pressure transmitter is damaged, and severe overload can sometimes damage the barrier diaphragm. It needs to be sent back to the manufacturer for repair.

3. Whether the reference pressure value must be correct, if the accuracy of the reference pressure gauge is low, it is necessary to replace the pressure gauge with higher accuracy.

4. Whether the temperature of the Rosemount pressure transmitter pipeline is too high, the operating temperature of the pressure sensor is -25-85 °C, but it is best to be within -20-70 °C in actual use. Add a buffer tube to dissipate heat, and it is best to add some cold water to the buffer tube before use, so as to prevent the overheated steam from directly impacting the sensor, thereby damaging the sensor or reducing the service life.

5. The input impedance of the load of the Rosemount pressure transmitter should be in line with RL≤ (transmitter supply voltage -12V)/(0.02A Ω), if necessary, if not, corresponding measures can be taken according to its differences: such as increasing the power supply voltage (but it is necessary to be lower than 36VDC), reducing the load, etc.

6. Whether the input terminal is open when the color screen paperless recorder does not record; If the circuit is open, 1) switch to other recorders with input impedance ≤250Ω when not recorded; 2) Can not carry other loads.

7. If there are impurities, sand, etc. blocking the pipeline in the pipeline, it is necessary to sort out the impurities, and add a filter screen before the pressure interface, which will affect the measurement accuracy when there are impurities.

8. Whether the input of the pressure indication surface of the Rosemount pressure transmitter and the corresponding wiring are correct, and the input of the pressure indication surface is 4-20mA, the output signal of the pressure transmitter can be directly connected; If the input of the pressure indication surface is 1-5V, it is necessary to connect a resistor with an accuracy of 1/1000 or more and a resistance value of 250Ω at the input end of the pressure indication surface, and then connect to the input of the transmitter.

9. Whether the range of the pressure indication surface is consistent with the range of the pressure indication surface and the range of the Rosemount pressure transmitter.

10. Whether it is routed separately from AC power supply and other power sources, and whether it is routed separately from AC power supply and other power sources.

11. Whether the corresponding equipment shell is grounded and the equipment shell is grounded.

More on that
A summary of methods for on-site inspection of Rosemount transmitter failures A summary of methods for on-site inspection of Rosemount transmitter failures

When something goes wrong with the Rosemount transmitter, you can first use the common methods of on-site inspection to check it, such as: query method: recall the ignition, smoke, odor, power supply change, lightning strike, wetting, misoperation, and mismaintenance before the fault occurs; Intuitive method: investigate external damage to the circuit, leakage of the impulse pipe, ...

Rosemount Models 2088, 2090F, and 2090P Pressure Transmitters Quick Installation Guide Rosemount Models 2088, 2090F, and 2090P Pressure Transmitters Quick Installation Guide

1.Rosemount 2088   Install it directly to the impulse pipe without the need for an additional mounting bracket, or use the optional mounting bracket to mount it directly to a wall, panel, or 2" pipe. 2. Rosemount 2090P Use of existing welded short casings ...

Features of Rosemount pressure transmitters: Features of Rosemount pressure transmitters:

The main features of Rosemount pressure transmitters are as follows:   1. It has the function of converting high and low pressure side: The conversion function of the high and low voltage side of this sensor is mainly through the adjustment of the internal parameters of the handheld communicator, and the useful data on the high and low voltage side is realized.

Features that Rosemount Instrument Thermowells have Features that Rosemount Instrument Thermowells have

Rosemount Instrument Heat Jacket has the following features:   1. Similar tags – when presenting some similar applications that only need to be changed slightly, it should be possible to imitate the application value of a specific tag, and then there is no need to re-enter the repetitive information, only change the variables that need to be changed in the new use.

Three types of Rosemount 3051 transmitters Three types of Rosemount 3051 transmitters

There are many types of Rosemount 3051 transmitters, and there are many types, today we will tell you about the most basic 3 types of transmitters of Rosemount 3051 transmitters, absolute pressure, gauge pressure, and differential pressure. 3051CA Absolute Pressure Transmitter Rosemount Reference Pressure When the Pressure is Vacuum, the ...

What are the main advantages of Rosemount temperature transmitters? What are the main advantages of Rosemount temperature transmitters?

What are the main advantages of Rosemount temperature transmitters? 1. Only by adapting to harsh environments can it be strong Rosemount temperature transmitters generally work in a wide range of environments, from extremely cold to extremely hot areas, many of which work in the open air.

Features of the Rosemount 8732E Electromagnetic Flowmeter: Features of the Rosemount 8732E Electromagnetic Flowmeter:

1. The measurement is not affected by the change of fluid density, viscosity, temperature, pressure and conductivity. 2. There are no obstruction moving parts in the measuring pipe, no pressure loss, and the requirements for the straight pipe section are low. There is a common adaptability to slurry measurement. 3. Reasonable selection of sensor lining and electrode materials, ...

What to do if the Rosemount pressure transmitter measurement is inaccurate What to do if the Rosemount pressure transmitter measurement is inaccurate

Common Rosemount pressure transmitter measurement incorrect situations: 1. The input impedance of the Rosemount transmitter load should be in line with RL≤ (transmitter supply voltage -12V)/(0.02A)Ω if necessary, if it does not match, corresponding measures can be adopted according to its differences: such as increasing the power supply ...

Rosemount 3051 transmitter mounting Rosemount 3051 transmitter mounting

What are the factors that affect the functionality of the Rosemount 3051 differential pressure transmitter? What are the factors that affect the functionality of the Rosemount 3051 differential pressure transmitter? Unique to Rosemount, the typical North and South American device method, the head-mounted 3051 transmitter with threaded sensors. 1. Heat ...

Factors to consider for Rosemount 5300 Series Radar Level Gauge Interface Measurements Factors to consider for Rosemount 5300 Series Radar Level Gauge Interface Measurements

For applications where the waveguide is completely submerged in liquids, the Rosemount 5301 measurement interface can be used, but the following guidelines should be followed 1. The dielectric constant of the above product must be known and cannot be changed. The Radar Master software has built-in dielectric constant calculations ...

Rosemount transmitter signal line grounding method Rosemount transmitter signal line grounding method

If the Rosemount transmitter does not have alarms and safety adjustment options installed, the transmitter will typically operate according to the default alarm settings, i.e., the alarm condition is set to "high" and the safety is set to "off". Then proceed as follows: 1. ...

How to choose the Rosemount 3051DP differential pressure transmitter How to choose the Rosemount 3051DP differential pressure transmitter

1.3051D transmitter is a coplanar pressure transmitter, which can measure the pressure or the side differential pressure, and there are two options P is the differential pressure measurement and G is the gauge pressure. 2. To understand the range used in the field, select the corresponding code according to the range, a total of 5 options: the lowest - 6.216KPA and the maximum 13789.54KPA. ...

The installation environment affects the use of Rosemount transmitters The installation environment affects the use of Rosemount transmitters

If you want to get better measurement results in practical applications, you need to pay attention to the following environmental issues when installing:   1. The Rosemount transmitter pressure impulse pipe should be arranged in a place where the temperature fluctuation is small, and the buffer tube (disk) should be connected when measuring steam or other low-temperature medium.

Problems to be noted when calibrating Rosemount transmitters Problems to be noted when calibrating Rosemount transmitters

1. After adjusting the zero point, use the standard pressure source to apply pressure slowly, and increase the pressure to the maximum scale, and the output value is about 20mA. 2. The verification regulations require that the two high and low pressure chambers of H and L are connected to the outside world, and observe that the zero position is not in the direction of 4mA.

How the Rosemount 3051TG pressure transmitter works How the Rosemount 3051TG pressure transmitter works

The Rosemount 3051TG pressure transmitter is one of the most commonly used products in the Rosemount 3051 pressure transmitter that has been tested in the power industry for 40 years. Planning with high reliability, transient stability, and easy protection. Rosemount pressure transmitters are designed from planning to installation, from protection to operation.

The Rosemount flow meter indicates the cause of the failure The Rosemount flow meter indicates the cause of the failure

During the long-term use of the Rosemount flowmeter, there may be some problems in the manual: 1. The manual is not accurate for a long time; 2. There are always no signs; 3. It means that the fluctuation range is large and there is no reading; 4. The indication does not return to zero; 5. There is no indication when the flow rate is small; 6. When the large flow indicates that the positive ...

How to solve the problem that the Rosemount transmitter cannot be powered on How to solve the problem that the Rosemount transmitter cannot be powered on

Analysis and countermeasures when the Rosemount transmitter cannot be powered on. 1. There is something wrong with the leakage circuit breaker itself When the jump bar indicator and power indicator are not on, it is necessary to check whether the fuse is blown; Whether transformers, voltage regulator manifolds, and power switches ...

That's how Rosemount transmitters should be selected That's how Rosemount transmitters should be selected

Rosemount transmitter selection requires a good transmitter before use, so its selection is very important 1. According to the pressure interface mode Generally, threaded connection is the standard interface method. 2. According to the required accuracy level Measurement error of the transmitter ...

How the Rosemount transmitter is wired How the Rosemount transmitter is wired

During the use of the Rosemount transmitter, wire the Rosemount transmitter according to the following steps: 1. Take out the Rosemount 3051 and remove the electronic enclosure marked "FIELD TERMINALS". 2. Will be positive ...

Types of Rosemount transmitters Types of Rosemount transmitters

The intelligent Rosemount transmitter is also equipped with a hand-held terminal (external data setter or grouper) for setting the transmitter parameters, such as setting the type of transmitter, range adjustment, zero point adjustment, input signal selection, output signal selection, engineering unit selection and damping time constant.

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top