Common Rosemount pressure transmitter measurement incorrect situations:
1. The input impedance of the Rosemount transmitter load should be in line with RL≤ (transmitter power supply voltage -12V)/(0.02A), if necessary Ω, if not, corresponding measures can be adopted according to its differences: such as increasing the power supply voltage (but must be lower than 36VDC), reducing the load, etc.
2. Whether the power supply of the Rosemount transmitter is normal
If it is less than 12VDC, it should be checked whether there is a large load in the circuit, and the input impedance of the transmitter load should be in line with the Ω of RL≤ (transmitter supply voltage -12V)/(0.02A).
3. Whether the input of the pressure indication surface and the corresponding wiring are correct
If the input of the pressure indication surface is 4-20mA, the output signal of the pressure transmitter can be directly connected; If the input of the pressure indication surface is 1-5V, a resistor with an accuracy of 1/1000 or more and a resistance value of 250 Ω must be connected to the input of the pressure indication surface, and then connected to the input of the transmitter.
4. Whether the temperature of the pipeline is too high.
The operating temperature of the pressure sensor is -25-85°C, but it is best to use it within -20-70°C. Add a buffer tube to dissipate heat, and it is best to add some cold water to the buffer tube before use, so as to prevent overheated steam from directly impacting the sensor, thereby damaging the sensor or reducing the service life.
5. Whether the corresponding equipment shell is grounded, and whether the equipment shell is grounded.
6. Whether it is routed separately from AC power supply and other power sources, and whether it is routed separately from AC power supply and other power sources.
7. Whether the pressure sensor is damaged, severe overload sometimes damages the isolation diaphragm. It needs to be sent back to the manufacturer for repair.
The countermeasures for incorrect measurement of Rosemount pressure transmitter are as follows:
1. Correct grounding method for Rosemount transmitter.
2. Correctly bury the wire, and bury the signal line and the power line separately to reduce signal disturbance.
3. Whether the Rosemount transmitter is damaged, if damaged, please return it to the factory for repair.
4. Wiring the pressure transmitter correctly.
5. Organize the pipeline for measuring pressure.
6. The appearance of the pressure measurement, such as the pressure digital display table, the pressure paperless recorder and other settings are correct.
|
More on that
|
Features and performance of Rosemount pressure sensors
Features and performance of Rosemount pressure sensors
1. Diffusion silicon pressure sensor
The working principle of the diffusion silicon pressure sensor is that the pressure of the measured medium acts directly on the diaphragm of the sensor (stainless steel or ceramic), so that the diaphragm produces a micro-displacement proportional to the pressure of the medium, ...
|
|
How to troubleshoot the Rosemount 3051 differential pressure transmitter if it encounters problems
1. Line failure
When the computer in the Rosemount transmitter monitoring system shows abnormal values, it is necessary to immediately check the line status of the junction box of the differential pressure transmitter to see if there is a short circuit, etc., and the way to check is to measure the resistance.
...
|
|
Factors to consider when installing a Rosemount 644 temperature transmitter
Rosemount 644 temperature transmitter must be considered when installing the factors, only we solve these unfavorable factors, in the installation of the Rosemount temperature transmitter will not encounter some unnecessary things
routine
Electrical temperatures such as RTDs and thermocouples ...
|
|
What are the features of the Rosemount 644 temperature transmitter?
1. It can greatly reduce the cost of wire and labor.
2. The advanced diagnosis function can reduce the number of on-site repairs.
3. Order a complete temperature transmitter and temperature sensing assembly to simplify setup, specifications, and ordering, and then reduce costs.
4. Adopt HART communication protocol. ...
|
|
How to solve the problem that the Rosemount transmitter cannot be powered on
Analysis and countermeasures when the Rosemount transmitter cannot be powered on.
1. There is something wrong with the leakage circuit breaker itself
When the jump bar indicator and power indicator are not on, it is necessary to check whether the fuse is blown; Whether transformers, voltage regulator manifolds, and power switches ...
|
|
Rosemount Models 2088, 2090F, and 2090P Pressure Transmitters Quick Installation Guide
1.Rosemount 2088
Install it directly to the impulse pipe without the need for an additional mounting bracket, or use the optional mounting bracket to mount it directly to a wall, panel, or 2" pipe.
2. Rosemount 2090P
Use of existing welded short casings ...
|
|
The Rosemount 3051 transmitter meter shows what the cause of the FAIL fault is
1. Look at whether the diaphragm is damaged, if not, after removing it, press it with chopsticks after imitating the power on in the room to see if there is a pressure display, if there is a display change, you can only disassemble another one, see if the transmitter module is broken, because the transmitter modules are integrated ...
|
|
What are the features of the Rosemount 644 temperature transmitter
The Rosemount 644 temperature transmitter is widely used in industrial temperature measurement, and the quality is also very stable, the following is to tell you about the characteristics of the 644 temperature transmitter:
1. It can greatly reduce the cost of wire and labor.
2. Advanced diagnostic function can reduce the need for on-site repairs.
|
|
Features of the Rosemount 8732E Electromagnetic Flowmeter:
Features of the Rosemount 8732E Electromagnetic Flowmeter
1. The measurement is not affected by the changes in fluid density, viscosity, temperature, pressure and conductivity.
2. There are no blocking moving parts in the measuring pipe, no pressure loss, and the requirements for the straight pipe section are low. It has unique adaptability to slurry measurement.
...
|
|
Installation of Rosemount transmitter attachments
The Rosemount transmitter is an important accessory in the use of time and time and time components, which will also affect the accuracy of the transmitter measurement results. Therefore, in order to prevent the occurrence of measurement errors, we need to pay attention to the following points in the equipment process of additional equipment.
1. Rosemont ...
|
|
How to choose the Rosemount 3051DP differential pressure transmitter
1.3051D transmitter is a coplanar pressure transmitter, which can measure the pressure or the side differential pressure, and there are two options P is the differential pressure measurement and G is the gauge pressure.
2. To understand the range used in the field, select the corresponding code according to the range, a total of 5 options: the lowest - 6.216KPA and the maximum 13789.54KPA.
...
|
|
An indispensable accessory for Rosemount transmitters
Before selecting a Rosemount transmitter, it is necessary to consider whether it is a threaded device or a flanged device, and the flanged device is divided into a single flange device and a double flange device. In order to let you better choose the flange, we have summarized some knowledge about the flange type:
Threading ...
|
|
How to choose a Rosemount transmitter for standard accuracy
Not every Rosemount product is the same, for example, the 3051 pressure transmitter and the 3051S high-precision pressure transmitter are not in the same range. But there is also a big relationship between the two. For example, the 3051CD transmitter is now used in ...
|
|
Factors to consider for Rosemount 5300 Series Radar Level Gauge Interface Measurements
For applications where the waveguide is completely submerged in liquids, the Rosemount 5301 measurement interface can be used, but the following guidelines should be followed
1. The dielectric constant of the above product must be known and cannot be changed. The Radar Master software has built-in dielectric constant calculations ...
|
|
How to care for your Rosemount pressure transmitter after use
Eight ways to use Rosemount pressure transmitters:
1. When measuring steam or other high-temperature media, it is necessary to connect a condenser such as a buffer tube (coil), and the working temperature of the Rosemount transmitter should not exceed the limit.
2. When wiring, pass the cable through the waterproof joint or wrap it around.
|
|
Three types of Rosemount 3051 transmitters
There are many types of Rosemount 3051 transmitters, and there are many types, today we will tell you about the most basic 3 types of transmitters of Rosemount 3051 transmitters, absolute pressure, gauge pressure, and differential pressure.
3051CA Absolute Pressure Transmitter Rosemount Reference Pressure When the Pressure is Vacuum, the ...
|
|
How the Rosemount transmitter is wired
During the use of the Rosemount transmitter, wire the Rosemount transmitter according to the following steps:
1. Take out the Rosemount 3051 and remove the electronic enclosure marked "FIELD TERMINALS".
2. Will be positive ...
|
|
A method for verifying a current loop signal for a Rosemount pressure transmitter
The Rosemount pressure transmitter uses a 4-20mA signal, which is the conversion value of the output generated by the pressure transmitter. The output of the transmitter is detected according to the HART protocol, however, it is converted to a proportional current so that it can be visualized as a reading. Normally, at zero level output, the transmitter displays 4mA ...
|
|
Features of Rosemount pressure transmitters:
The main features of Rosemount pressure transmitters are as follows:
1. It has the function of converting high and low pressure side:
The conversion function of the high and low voltage side of this sensor is mainly through the adjustment of the internal parameters of the handheld communicator, and the useful data on the high and low voltage side is realized.
|
|
The Rosemount 3051 transmitter resets the range
There are three ways to reset the range of the 3051 transmitter:
1. Use only the communicator to reset the range
HART communicator shortcut keys 4 or 5. The simplest and most common way to reset the range using only the communicator is to change the values that mimic points 4 and 20 mA independently, without the need for pressure inputs.
|
|