When something goes wrong with the Rosemount transmitter, you can first use the common methods of on-site inspection to check it, such as: query method: recall the ignition, smoke, odor, power supply change, lightning strike, wetting, misoperation, and mismaintenance before the fault occurs; Intuitive method: investigate the external damage of the circuit, the leakage of the impulse pipe, the overheating of the circuit, the state of the power supply switch, etc.
The on-site inspection methods of Rosemount transmitters also include inspection methods, which are mainly the following:
1. Break circuit detection: separate the part that may have problems from other parts, such as the intelligent differential pressure transmitter can not communicate remotely normally, the power supply can be disconnected from the meter body, and the transmitter can be energized for communication by adding another power supply on the spot, so as to see if the cable is superimposed with an electromagnetic signal of about 2kHz and interferes with the communication.
2. Short circuit detection: under the condition of ensuring safety, the relevant part of the circuit is directly short-circuited, if the output value of the differential transmitter is small, the impulse pipe can be disconnected, and the differential pressure signal can be directly bowed to both sides of the differential pressure transmitter from outside the primary pressure valve to investigate the output of the transmitter to judge the connectivity of the plugging and leakage of the impulse pipeline.
3. Replacement detection: replace the part that may have a problem and judge the part of the problem. If there is a suspicion that something is wrong with the transmitter circuit board, you can temporarily replace one to confirm the cause.
4. Division detection: divide the measurement loop into several parts, such as: power supply, signal output, signal transmission, signal detection, view by parts, from simple to complex, from outside to inside, reduce the scale, and find out the location of the problem.
|
More on that
|
Rosemount transmitter installation requirements and how to install it
Rosemount transmitters must be installed in a constant temperature environment, which is also determined by the characteristics of the flange transmitter. Because the measured medium of ordinary transmitters generally enters the transmitter measurement chamber through the impulse tube. If the measurement is a viscous liquid medium, it will be easier to form a conductive ...
|
|
How to care for your Rosemount pressure transmitter after use
Eight ways to use Rosemount pressure transmitters:
1. When measuring steam or other high-temperature media, it is necessary to connect a condenser such as a buffer tube (coil), and the working temperature of the Rosemount transmitter should not exceed the limit.
2. When wiring, pass the cable through the waterproof joint or wrap it around.
|
|
The Rosemount 3051 transmitter meter shows what the cause of the FAIL fault is
1. Look at whether the diaphragm is damaged, if not, after removing it, press it with chopsticks after imitating the power on in the room to see if there is a pressure display, if there is a display change, you can only disassemble another one, see if the transmitter module is broken, because the transmitter modules are integrated ...
|
|
The difference between a Rosemount transmitter and a Siemens transmitter
The difference between Siemens' transmitter and Rosemount's transmitter: Siemens' transmitter is a piezoresistive pressure transmitter, and Rosemount's transmitter is a capacitive pressure transmitter.
The transmitter converts the output signal of the sensor into a signal that can be recognized by the controller.
|
|
Factors to consider when installing a Rosemount 644 temperature transmitter
Rosemount 644 temperature transmitter must be considered when installing the factors, only we solve these unfavorable factors, in the installation of the Rosemount temperature transmitter will not encounter some unnecessary things
routine
Electrical temperatures such as RTDs and thermocouples ...
|
|
The Rosemount flow meter indicates the cause of the failure
During the long-term use of the Rosemount flowmeter, there may be some problems in the manual: 1. The manual is not accurate for a long time; 2. There are always no signs; 3. It means that the fluctuation range is large and there is no reading; 4. The indication does not return to zero; 5. There is no indication when the flow rate is small; 6. When the large flow indicates that the positive ...
|
|
Features of the Rosemount 8732E Electromagnetic Flowmeter:
1. The measurement is not affected by the change of fluid density, viscosity, temperature, pressure and conductivity.
2. There are no obstruction moving parts in the measuring pipe, no pressure loss, and the requirements for the straight pipe section are low. There is a common adaptability to slurry measurement.
3. Reasonable selection of sensor lining and electrode materials, ...
|
|
Rosemount transmitter pressure gauges are widely used
Rosemount transmitters are used in industrial process control and technical measurement processes, because the elastic and sensitive elements of mechanical pressure gauges have high mechanical strength and easy production, so that mechanical pressure gauges are more and more widely used.
Rosemont ...
|
|
An indispensable accessory for Rosemount transmitters
Before selecting a Rosemount transmitter, it is necessary to consider whether it is a threaded device or a flanged device, and the flanged device is divided into a single flange device and a double flange device. In order to let you better choose the flange, we have summarized some knowledge about the flange type:
Threading ...
|
|
How to maintain the Rosemount 3051 pressure transmitter
United States rosemount 3051 pressure transmitter maintenance is mainly divided into two points:
1. In the whole process of accurate measurement, some common faults often occur in the Rosemount pressure transmitter, and the immediate judgment and analysis and resolution of common faults are especially important for the production and manufacturing that has been carried out.
|
|
Installation of Rosemount transmitter attachments
The Rosemount transmitter is an important accessory in the use of time and time and time components, which will also affect the accuracy of the transmitter measurement results. Therefore, in order to prevent the occurrence of measurement errors, we need to pay attention to the following points in the equipment process of additional equipment.
1. Rosemont ...
|
|
What to look out for before using a Rosemount transmitter
Rosemount transmitters can be used in many different fields, and different people face different situations and problems when using transmitters. Then the editor will introduce these problems to us.
How to clear the Rosemount transmitter ...
|
|
What to do if the Rosemount pressure transmitter measurement is inaccurate
Common Rosemount pressure transmitter measurement incorrect situations:
1. The input impedance of the Rosemount transmitter load should be in line with RL≤ (transmitter supply voltage -12V)/(0.02A)Ω if necessary, if it does not match, corresponding measures can be adopted according to its differences: such as increasing the power supply ...
|
|
Rosemount Models 2088, 2090F, and 2090P Pressure Transmitters Quick Installation Guide
1.Rosemount 2088
Install it directly to the impulse pipe without the need for an additional mounting bracket, or use the optional mounting bracket to mount it directly to a wall, panel, or 2" pipe.
2. Rosemount 2090P
Use of existing welded short casings ...
|
|
How to solve the problem of Rosemount differential pressure transmitter migration failure
The migration of differential pressure transmitters is a form of application, which refers to the process of artificially moving the measuring point of a differential pressure transmitter from the zero point to the required value. The migration of differential pressure transmitters includes two major contents: positive migration and negative migration.
|
|
How to solve the problem that the Rosemount transmitter cannot be powered on
Analysis and countermeasures when the Rosemount transmitter cannot be powered on.
1. There is something wrong with the leakage circuit breaker itself
When the jump bar indicator and power indicator are not on, it is necessary to check whether the fuse is blown; Whether transformers, voltage regulator manifolds, and power switches ...
|
|
Rosemount 3051 transmitter mounting
What are the factors that affect the functionality of the Rosemount 3051 differential pressure transmitter? What are the factors that affect the functionality of the Rosemount 3051 differential pressure transmitter? Unique to Rosemount, the typical North and South American device method, the head-mounted 3051 transmitter with threaded sensors.
1. Heat ...
|
|
How to troubleshoot the Rosemount 3051 differential pressure transmitter if it encounters problems
1. Line failure
When the computer in the Rosemount transmitter monitoring system shows abnormal values, it is necessary to immediately check the line status of the junction box of the differential pressure transmitter to see if there is a short circuit, etc., and the way to check is to measure the resistance.
...
|
|
What are the features of the Rosemount 644 temperature transmitter
The Rosemount 644 temperature transmitter is widely used in industrial temperature measurement, and the quality is also very stable, the following is to tell you about the characteristics of the 644 temperature transmitter:
1. It can greatly reduce the cost of wire and labor.
2. Advanced diagnostic function can reduce the need for on-site repairs.
|
|
The meaning of the Rosemount transmitter fault code indication
Press Limit: The process variable read out by the transmitter is not within the transmitter range, which means that the range of the set volume exceeds the range of the transmitter cassette, and the solution is to replace the transmitter cassette.
Temp Limit: ...
|
|