Reynolds frequency converters RNB1000 series E.ITE fault codes

Create Date: 2024-8-30 12:03:23|Source: RENLE/RENOLDS

Reynolds inverter problem code:

  E.ITE

Reynolds inverter problem phenomenon/type:

Problems with the current sensing circuit

Possible causes of Reynolds inverter problems:

1. Poor contact of the control board connector

2. The auxiliary power supply is damaged

3. Hall device is damaged

4. The amplification circuit is abnormal

                            Reynolds frequency converters RNB1000 series E.ITE fault codes

Reynolds drive solutions:

1. Check the connector and plug it in from the end

2. Seek service

Analysis of the causes of Reynolds inverter problems:

When the conversion is initialized, the zero drift of the current sensor will be detected, and if there is a large deviation, the problem will be reported. If there is no alarm for the current detection circuit after power-on, when the inverter is working normally, use a multimeter to detect the lu, lv or lw signal on the control board, and the voltage value should be between 2.2 and 2.7N.

More on that
Water pump inverter pressure adjustment method - Reynolds Water pump inverter pressure adjustment method - Reynolds

Water pump inverter pressure conditioning steps: 1. Open PID closed-loop control; 2. Close the pressure circuit; 3. Set the pressure feedback and set the given pressure; When the pump speed is changed, the outlet pressure can be changed. Adjust the operating frequency of the VFD. The higher the frequency, the higher the pump speed and the higher the pressure. About ...

Reynolds drives RNB1000 series fault code resolution Reynolds drives RNB1000 series fault code resolution

Reynolds inverter fault codes: E.bC Reynolds inverter fault phenomenon/type: Brake unit failure   ​   Reynolds inverter failure may be caused: 1. Brake line failure or brake ...

Wiring method and principle of PLC and inverter shielded wire - Reynolds Wiring method and principle of PLC and inverter shielded wire - Reynolds

In order to avoid the interference of the control signal line between the PLC and the inverter by the space electromagnetic field, the shielding wire can be connected to the outer layer of these control signal lines to improve the anti-interference ability of the system. This kind of wiring must be noted, and only one point can be selected for the grounding point of the shield. Whether it's on the PLC side, or ...

Small fan inverter choice - Reynolds Small fan inverter choice - Reynolds

Now many electrical appliances are advocating the use of small parts, because small parts will not occupy space, and small parts can be moved and overhauled at any time, and the inverter also has a small inverter, how to buy a small fan inverter? Power picking ...

Inverter control loop wiring taboo - Reynolds Inverter control loop wiring taboo - Reynolds

1. The wires laid out in the inverter control circuit should be separated from the main circuit cable (power line), so as to avoid the harmonic disturbance components on the side of the main circuit of the inverter from polluting the inverter control circuit; 2. Due to the faulty signal of the inverter and ...

The frequency of the frequency converter is given in a given way The frequency of the frequency converter is given in a given way

The first way to use the inverter is to change the output frequency to achieve the controllability of the motor speed, so do you know what steps to complete the output frequency controllability? One of the first and foremost key points is how to complete the change of the frequency signal supplied by the inverter equipment.

Precautions for installation of Reynolds low-voltage inverters Precautions for installation of Reynolds low-voltage inverters

1. Safety precautions 1. The primary requirement is to have certain electrical professional knowledge, and understand the job site, understand the equipment status, and have certain electrical operation technology. 2. Determine the electrical ...

Reynolds servo motor selection steps Reynolds servo motor selection steps

According to the requirements of the operating conditions, the appropriate load inertia accounting formula is selected to calculate the load inertia of the organization. According to the load inertia and servo motor inertia, the appropriate servo motor standard is selected. Combined with the inertia and load inertia of the primary servo motor, the acceleration torque and deceleration are calculated.

What inverter to choose what occasion - Reynolds What inverter to choose what occasion - Reynolds

We need to ensure that the capacity of the inverter is matched. First of all, according to the nature of the load, the correct selection of the type of inverter. When selecting the inverter, the current value of the actual motor should be used as the basis for the selection of the inverter, and the rated power of the motor can only be used as a ...

Use the right power for the inverter – Reynolds Use the right power for the inverter – Reynolds

Low pressure issues The VFD reports a low voltage glitch when the drive's DC link voltage drops below 62% of the nominal level at the high setting (480 Vac) and 50% of the nominal value at the low setting (400 Vac). The +10% and -15% voltage tolerances in most manuals are the ones that claim to be ...

Inverter breakdown factor – Reynolds Inverter breakdown factor – Reynolds

1. Overpressure leads to brake pipe breakdown. The so-called overvoltage of the inverter refers to the fact that the inverter voltage composed of various reasons exceeds the additional voltage, which is reflected in the DC voltage of the inverter DC bus. Overvoltage alarm generally appears when the machine is shut down, and its main ...

Inverter composition and various functions - Reynolds Inverter composition and various functions - Reynolds

Rectifier circuit: rectify 50HZ communication power into direct current. Frequency conversion circuit: The rectified direct current is inverted into a variable frequency communication current. Control part: control the frequency of communication electricity output by the inverter circuit. Maintenance circuit: maintenance and blockage of overcurrent and phase loss ...

Misunderstanding of inverter selection - Reynolds Misunderstanding of inverter selection - Reynolds

1. In order to save power, the inverter is selected Many manufacturers and salesmen praise how high the power-saving rate of the inverter is, and the user also believes that it is true, and the inverter is selected at a high cost simply in order to save electricity, but the results are greatly disappointed. Whether the inverter can save power after using it is determined by the load driven by it.

Reynolds product range models Reynolds product range models

JJR1000系列:   JJR1011;JJR1017;JJR1022;JJR1030;JJR1037;JJR1045;JJR1055;JJR1075;JJR1090;JJR1115;JJR1132;JJR1160;JJR1200;JJR1250;JJR1 ...

The working principle of the motor soft starter – Reynolds The working principle of the motor soft starter – Reynolds

Motor soft starter is the primary selection of power electronics skills and microprocessing skills and modern control theory and design and production of advanced level of new engine equipment, motor soft starter mainly has anti-interference function, high reliability, multiple protection functions and other characteristics, according to these characteristics of electric ...

Renault is available in a variety of product ranges Renault is available in a variety of product ranges

JJR1000系列:   JJR1011;JJR1017;JJR1022;JJR1030;JJR1037;JJR1045;JJR1055;JJR1075;JJR1090;JJR1115;JJR1132;JJR1160;JJR1200;JJR1250;JJR1320;JJR1400;JJR1500;JJR1600 ...

Misunderstanding of inverter control loop wiring - Reynolds Misunderstanding of inverter control loop wiring - Reynolds

1. The wires of the inverter control circuit should be strictly distinguished from the main circuit cable (power line) and placed separately. This effectively prevents the inverter's control circuit from being disturbed by harmonics in the inverter's main circuit. 2. To separate the connection of the inverter from the terminals or contacts of other control circuits, ...

Reynolds drive control panel description Reynolds drive control panel description

1. FUN button; Press the FUN button to enter the settings menu F00; 2. Press and hold the up button or down button to scroll to the code that needs to be set; 3. Press the FUN button to confirm at this moment, and adjust the entry parameters to the required value; 4、 ...

Application misunderstandings and drawbacks of inverter and countermeasures - Reynolds Application misunderstandings and drawbacks of inverter and countermeasures - Reynolds

Misunderstanding: connect electromagnetic switches and electromagnetic contactors in the output circuit of the inverter In actual use, some occasions require the use of contactors for frequency converter switching: such as when the frequency conversion is faulty, switch to the power frequency operation, or when the one-to-two method is adopted, a motor is faulty, and the variable frequency is used.

Frequency converter overcurrent problem treatment - Reynolds Frequency converter overcurrent problem treatment - Reynolds

General treatment methods for inverter overcurrent problems: The output side of the inverter is a PWM voltage waveform, and after passing through the motor winding, the output current is approximately a sine wave, and lags behind the voltage by a phase viewpoint, which is determined by the power factor of the motor. The output current of the inverter passes through ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top