Misunderstanding: connect electromagnetic switches and electromagnetic contactors in the output circuit of the inverter
In actual use, some occasions require the use of contactors for inverter switching: such as when the frequency conversion is faulty, switch to the power frequency state operation, or when the one-to-two method is adopted, one motor is faulty, and the inverter turns to drag another motor. Therefore, many users will think that installing electromagnetic switches and electromagnetic contactors in the output circuit of the inverter is a standard equipment and a way to safely disconnect the power supply, but in fact, there is a greater danger in this practice.
Harm
When the inverter is still running, the contactor is disconnected first, and the load is suddenly stopped, and the inrush current will make the overcurrent maintenance action, which will have a certain impact on the main circuit of the rectifier inverter. Seriously, it can even damage the IGBT of the inverter output module. Together, when the inductive motor is loaded, the inductive magnetic field energy cannot be released quickly, and high voltages will occur, which will damage the insulation of the motor and the connecting cable.
Coping strategies
The output side of the inverter is directly connected to the motor cable, and the normal start-stop motor can be completed by triggering the inverter control terminal to achieve the role of soft start and soft stop. If the contactor must be used on the output side of the frequency conversion governor, the necessary control interlock must be made between the output of the frequency conversion governor and the action of the contactor, so as to ensure that the contactor can operate as long as there is no output of the frequency conversion governor.
|
More on that
|
Difference Between Soft Starter and Inverter – Reynolds
Soft starters and frequency converters are two completely different products. The inverter is used in the local area where speed regulation is required, and its output not only changes the voltage but also changes the frequency at the same time; A soft starter is actually a voltage regulator, which is used when starting a motor, and the output only changes the voltage and does not change the frequency. Change...
|
|
The way to set the parameters of the inverter - Reynolds
There are many setting parameters of the inverter, and each parameter has a certain range of choice, and the inverter can not work normally due to the improper setting of a single parameter in use, therefore, the relevant parameters must be set correctly.
...
|
|
Inverter composition and various functions - Reynolds
Rectifier circuit: rectify 50HZ communication power into direct current.
Frequency conversion circuit: The rectified direct current is inverted into a variable frequency communication current.
Control part: control the frequency of communication electricity output by the inverter circuit.
Maintenance circuit: maintenance and blockage of overcurrent and phase loss ...
|
|
Reynolds EPS emergency power supply routine maintenance
1. EPS the first use of the emergency power supply, the battery pack should be charged continuously for 48 hours after discharging protection;
2. EPS emergency power supply to keep the whole machine dry, clean, free of dust and foreign objects, wipe with a soft cloth after shutting down, and strictly ...
|
|
The item that needs to be maintained after the inverter is shut down – Reynolds
1. Use a vacuum cleaner with a plastic nozzle to thoroughly clean the inside and outside of the inverter cabinet to ensure that there is no excessive dust around the equipment.
2. Check the ventilation and lighting of the frequency conversion room, and the ventilation equipment can operate normally.
3. Check the inverter ...
|
|
The distance between the Reynolds frequency converter and the motor determines the cable and wiring method
1. The interval between the inverter and the motor should be as short as possible. This reduces the cable's capacitance to ground and reduces the source of disturbance.
2. The control cable is shielded cable, the power cable is shielded cable or from the inverter to the motor.
|
|
The inverter protects the motor - Reynolds inverter
1. The output of the inverter for overvoltage maintenance has the function of voltage detection, and the inverter can actively adjust the output voltage, so that the motor does not bear the overvoltage, and the motor runs within the set voltage range.
2. Undervoltage maintenanceWhen the voltage of the motor is lower than 90% of the normal voltage (some are set to 85% ...
|
|
Frequency converters need to be replaced regularly – Reynolds
The inverter is composed of many electronic parts, such as semiconductor components, etc., in the application and protection involves the replacement of a related component, because of the composition or physical characteristics of the inverter, it will deteriorate in a certain period of time, which will reduce the characteristics of the inverter, and even ...
|
|
Reynolds JJR5000 introduction to soft starters
The cost performance of Reynolds JJR5000 soft starter is relatively high, which is mainly reflected in the following aspects:
1. The price is more reasonable: compared with other similar products, the price of Reynolds JJR5000 soft starter is more affordable, and the price is in a more advantageous position among the products of the same level.
|
|
Safety standards for AC drives – Reynolds
International electrical safety standards: The requirements are in line with international electrical safety standards, such as CE standards in Europe and UL specifications in United States. These specifications specify the requirements for electrical safety functions, mechanical safety functions, EMC functions, etc.
...
|
|
PLC and inverter communication mode
1. The switching signal of PLC controls the inverter
The PLC can control the start, stop and reset of the inverter through the program; It can also control different combinations of high-speed, medium-speed and low-speed terminals of the inverter to achieve multi-stage speed operation. However, because it is controlled by switching ...
|
|
Reynolds assisted Sinopec Weirong shale gas project
With the rapid development of China's national economy, the supply and demand situation of oil and gas resources is becoming increasingly severe, and the import of oil and gas is increasing year by year, so it is urgent to expand the field of domestic oil and gas exploration and development. Strengthening the exploration and development of shale gas resources can make up for the lack of conventional oil and gas resources and promote the sustainability of the oil and gas industry.
|
|
Inverter replacement component requirements - Reynolds
1) Find out the basic parameters and appearance of the equipment that needs to be replaced. The basic parameters include the rated operating current, the capacitance of the capacitor, the resistance value of the resistor, the value of the GTR Darlington device (current amplification factor), the switching characteristics and saturation voltage of the IGBT (including IPM) device, etc.
|
|
Reynolds-5G empowers the paper industry to improve quality and efficiency of the industrial IoT control system
From September 23rd to September 25th, 2020, the 2020 China International Paper Technology Exhibition was held in Hall D1 of Suzhou International Expo Center.
|
|
Characteristics and Discrimination of Resistance Damage - Reynolds
I often see many beginners tossing on the resistor when overhauling the circuit, and it is dismantling and welding, in fact, it is repaired a lot, as long as you understand the damage characteristics of the resistor, you don't have to bother.
Resistors are the most numerous in electrical equipment ...
|
|
Problems between the inverter and the motor – Reynolds
1. The power and temperature rise of the motor
Regardless of the method of the inverter, different degrees of harmonic voltage and current occur during operation, so that the motor runs under non-sinusoidal voltage and current. Rejection of material introduction, taking the sine wave PWM type inverter that is now widely used as an example, ...
|
|
Reynolds soft starter problem solving
1. The soft starter does not start and the fault-free code appears, perhaps because the control power supply is not connected, the solution is to check the power supply of the control power supply to see if the circuit connection is correct.
2. The motor starts when the motor announces a hum/no start signal, perhaps because of the thyristor/module ...
|
|
Selection of large fan inverter in the factory - Reynolds
First, select from the inverter "software".
The reason why the factory chooses the inverter to work together with the fan is that it is hoped that the automation and intelligent design of the inverter technology can improve the speed regulation mode of the fan, and reduce the wasted energy consumption, which not only improves the wind efficiency.
|
|
Elimination of inverter harmonics method – Reynolds
a. Add the internal impedance of the power supply of the inverterIn general, the internal impedance of the power supply equipment can play a role in buffering the reactive power of the DC filter capacitor of the inverter. This internal impedance is the short-circuit impedance of the transformer. When the power supply capacity is smaller than the inverter capacity, the internal impedance value is relatively large.
|
|
Tips for using reducers - Reynolds
1. After 200-300 hours of operation, the first oil change should be carried out, and the quality of the oil should be checked regularly in the subsequent use, and the oil mixed with impurities or deteriorated oil must be replaced in time. Under normal circumstances, the reducer for long-term continuous operation should be replaced after 5000 hours of operation or once a year.
|
|