Low pressure issues
The VFD reports a low voltage glitch when the drive's DC link voltage drops below 62% of the nominal level at the high setting (480 Vac) and 50% of the nominal value at the low setting (400 Vac).
The +10% and -15% voltage tolerances in most manuals are claimed operating ranges to promise the drive at hand to maintain optimal efficiency and proper motor current. The drive can be lower than these services, but the reduced voltage will have an unpredictable effect on the motor current, motor temperature, and overall function.
More specifically, if the line voltage parameter of the drive is set high and 480 VAC is being applied, the drive will experience a low voltage failure when the DC link voltage drops to 62% of the nominal - such as 480 VAC ·0.62·√2= 421 VDC. The nominal DC link voltage is 480 Vac·√2= 679 Vdc.
Precautions when switching
While it is accepted practice to switch VFDs from line power to standby generators in many uses, there are some limitations. Importantly, many portable standby generators have a phase-to-phase voltage input voltage swing that is greater than the driver's recommended phase-to-phase voltage tolerance, typically less than 2%. To prevent voltage sloshing, the VFD is equipped with a surge maintainer in the input rectifier circuit – however significant input disturbances may require external maintenance (e.g. surge arresters). Large variances result in large ripple across the DC bus capacitors, which can lead to damage to capacitors and other power components over time.
Another potential problem presents when switching from line power to a standby generator. Most drives take at least two minutes to power up from scratch; Failure to follow this strategy may damage the charging relay circuit, or at least damage the input fuse or trip the circuit breaker.
In the case where the input power exhibits a moderate voltage to induce current surges, a 3% line reactor may improve the situation.
Another solution is to add a voltage monitor with the appropriate time delay. They have a maintenance trip level that shuts down the driver in case of undervoltage, overvoltage, out-of-phase, and phase-to-phase voltage imbalance. These devices ensure that the VFD is not exposed to unbalanced input power or power-up until the voltage is within tolerance and the appropriate delay time is satisfied.
Barrier transformer
After the proposition - *** expensive solution - is the use of barrier transformers. This ensures complete blocking of grounding and noise-related input power issues that may affect the driver. Do barrier transformers provide better maintenance than line reactors? Be. When to Use a Demand Barrier Transformer? When the installation is located close to the substation, the use of such a transformer is advocated.
Penetrating a driver barrier transformer between a VFD and its power supply offers a variety of advantages. Blocking guarantees that there is no direct electrical connection between the source and the load – but this is true for any transformer other than an autotransformer. What drive barrier transformers have in common is the placement of a ground electrostatic (Faraday) shield between and around the primary and secondary windings. This shielding reduces the capacitive coupling involved in transmitting common-mode voltage interference by a factor of one million. Without this shielding, the capacitor promises high-frequency noise and transient voltage spikes through the transformer.
Common-mode transients are transients that are presented between the ground and the neutral point of the communication system. Although these two parts of a circuit are generally combined at one point, they cannot be considered to have the same potential in the entire power system. Common mode transient disturbances arise from the normal operation of equipment such as switching power supplies, drive operation, arc welders, lightning, and even stepper motors. Some barrier transformers are also capable of blocking the "normal form" transients that occur between the line and the neutral.
Consider a use of a substation capacitor bank in an industrial park during the day-to-day utility power supply that causes transient voltage spikes – amplified by reflections from field capacitors in a nearby plant. Let's say a facility in the park has several small drives rated at 7.5 horsepower. Normal form transients can cause these drives to shut down on their own, which can then lead to costly process downtime. Barrier transformers prevent such abortions.
|
More on that
|
Reynolds drive safety rules and warnings
The high-voltage inverter has been designed with the safety of the user in mind. However, due to the energy storage capacitor installed inside the power unit of the inverter, it may still carry a high voltage after disconnecting the power supply, and some parts generate a lot of heat, so contact is prohibited. When working on or near the inverter, please ...
|
|
Inverter starts the overload adjustment parameter - Reynolds
Motor overload: There is no need to set overload maintenance parameters in frequency conversion.
The inverter generally acquiesces to the motor overload maintenance based on the motor power. Generally, it is 1.2 times and 60 seconds will report an overload failure. The overload factor is not the same for different frequency converters.
...
|
|
Inverter acceleration and deceleration mode selection
The selection of the acceleration form and deceleration form of the inverter is also called the selection of acceleration and deceleration curves. Generally, there are several forms of inverter, such as linear, S-shaped, semi-S-shaped, etc., and the characteristics and uses of each form are as follows.
1. Linear form
The form makes the inverter ...
|
|
Basic characteristics of inverter transmission - Reynolds
Compared with the motor driven by the inverter, the power factor and efficiency of the motor will deteriorate and the temperature rise will increase because the output waveform of the inverter contains the influence of higher harmonics. On the other hand, when the frequency conversion is driven, the same torque should be obtained as when the power frequency power supply is driven, ...
|
|
Reynolds soft starter troubleshooting methods
Common troubleshooting methods for Reynolds soft starters.
During the debugging process of the soft starter, the fault light is on, the motor is unresponsive, and the cause of the fault is analyzed:
When the starting mode adopts the live mode, the operation sequence is wrong (the correct operation sequence must first deliver the main power supply, and then the control ...
|
|
Introduction to the braking mode of Reynolds inverter
1. Energy consumption braking: The energy consumption braking method uses the braking resistance set in the DC circuit to absorb the regenerative electric energy of the motor through the chopper and braking resistor, so as to realize the rapid braking of the inverter.
2. Feedback braking: feedback system ...
|
|
The relationship between Reynolds motion control and frequency converters
Motion control has obvious period characteristics, it is a variety of high-tech generalization, used to push industrial automation, office automation and home automation to a higher stage. Nowadays, motion control is mainly composed of variable frequency drive (VFD), electric motor, control ...
|
|
Application misunderstandings and drawbacks of inverter and countermeasures - Reynolds
Misunderstanding: connect electromagnetic switches and electromagnetic contactors in the output circuit of the inverter
In actual use, some occasions require the use of contactors for frequency converter switching: such as when the frequency conversion is faulty, switch to the power frequency operation, or when the one-to-two method is adopted, a motor is faulty, and the variable frequency is used.
|
|
The internal structure of the inverter is the role of Reynolds
The inverter is mainly composed of rectifier (AC to DC), filtering, inverter (DC to communication), braking unit, drive unit, detection unit and microprocessor unit.
The inverter adjusts the voltage and frequency of the output power supply by the internal IGBT break, and ...
|
|
The reason for the preferred DC mode in the intermediate link of the inverter - Reynolds
The development of the inverter has experienced a slow and gradual process, and the inverter at the beginning of the first century did not choose this kind of AC-DC: communication to DC and then to communication, but direct AC, no central DC link. This kind of inverter is called alternating frequency converter, and now this kind of inverter is in the ultra-high power ...
|
|
Germany core control appeared at the China International Industry Fair
It is human beings who have always been committed to making human-computer interaction safer, easier to use, and more efficient, which has made collaborative robots gradually become the main stream of shopping malls.
It is precisely because of the vigorous development of the collaborative robot industry that Synapticon Gmb ...
|
|
Wiring method and principle of PLC and inverter shielded wire - Reynolds
In order to avoid the interference of the control signal line between the PLC and the inverter by the space electromagnetic field, the shielding wire can be connected to the outer layer of these control signal lines to improve the anti-interference ability of the system. This kind of wiring must be noted, and only one point can be selected for the grounding point of the shield. Whether it's on the PLC side, or ...
|
|
Motor soft start mode – Reynolds frequency inverter
Starting performance is a very important performance parameter of motor products. The large starting current of the motor is an unpreventable problem in the process of direct starting. The high current during the engine process has a great impact on both the power grid and the motor itself. Therefore, according to different working conditions and different series of motors, ...
|
|
Dust design considerations for frequency converters - Reynolds frequency converters
1) The air duct of the inverter cabinet should be planned reasonably, and the exhaust should be clear and smooth, so as to avoid the formation of vortex in the cabinet and the accumulation of dust in a fixed direction.
2) The top air outlet of the inverter cabinet should be equipped with a protective top cover to avoid debris from falling directly.
|
|
Reynolds inverter frequency
That is, the upper and lower amplitudes of the output frequency of the inverter. Frequency is a maintenance function to avoid misoperation or failure of the external frequency setting signal source, which causes the output frequency to be too high or too low, so as to prevent damage to the equipment. You can set it according to the actual situation in the app. This function can also be used as a speed limit, so that ...
|
|
Classification of Reynolds inverter types
1. Classified according to the input voltage level
According to the input voltage level, the inverter can be divided into low-voltage inverter and high-voltage inverter, and the low-voltage inverter is common in China with single-phase 220 V inverter, three-phase 220 V inverter, and i-phase 380 V inverter. High-voltage inverters are commonly used in 6 kV, 10 kV transformers.
|
|
Reynolds inverter parameter settings
The use of Reynolds inverters in industrial production is very important, in addition to speed regulation, soft start effect, the important thing is to be able to save energy. There are many functional parameters of Reynolds inverter, and there are generally dozens or even hundreds of parameters for users to choose. In practice, it is not necessary to ...
|
|
Lightning protection measures for Reynolds frequency converters
The lightning protection measures of the inverter equipment are another important peripheral measure to ensure the safe operation of the inverter, especially in the area where lightning is active or in the lively season, this problem is particularly important.
Today's inverter products are generally equipped with mines.
|
|
Safety precautions for low-voltage soft lift - Reynolds
Precautions for low-voltage soft starters
For cooling purposes, the soft starter must be installed in a straight direction.
In order to ensure excellent heat dissipation, there should be room for the soft starter device.
Main circuit selection ...
|
|
Reynolds soft starter fault code and fault handling
Reynolds soft starter fault code
Instantaneous stop -F 01 Instantaneous stop terminal 7 to terminal 10 open
TOO LONG STARTING TIME -F 02 STARTING TIME IS TOO LOW AND THE STARTING TIME IS TOO LONG (GREATER THAN 60S)
Overheating -F 03 Start too often, reduce the number of starts
Input out of phase -F 04 ...
|
|