Siemens APT current transformer - how to choose a current transformer?

Create Date: 2024-8-30 12:03:23|Source: APT/Siemens Shanghai Ergong

First, the principle of primary parameter selection of current transformer

The rated primary current of the current transformer is determined by the actual load of the tested circuit, and the rated primary current of the current transformer should not be less than the rated primary current of the circuit, and the rated current of the transformer is generally determined by multiplying the load current by the coefficient of 1.2-1.25. In addition, the rated continuous thermal current, rated short-time thermal current and rated dynamic and stable current of the current transformer should be able to meet the requirements of the maximum load current and short-circuit current of the primary circuit, and the development of the system should be considered.

Second, the principle of secondary parameter selection of current transformer

The rated secondary load of the transformer is the key parameter to determine the accuracy level, size and cost of the transformer, which should be reasonably selected according to the actual situation of the project. The rated secondary current of the current transformer is generally 1A, if it is conducive to the production or expansion of the transformer, and in some cases, in order to reduce the secondary open circuit voltage of the current transformer, the rated secondary current can also be 5A.

The rated output value should be selected in accordance with the following principles:

1. The rated output values of the measurement, P, and PR grades are expressed in volt-ampere. When the rated secondary current is 1A, the rated output standard value should be 0.5V · A, 1V · A, 1.5V · A, 2. 5v·a、5v·a、7. 5v·a、10v·a、15v·a。 When the rated secondary current is 5A, the rated output standard value should be 2. 5v·a、5v·a、10v·a、15v·a、20v·a、25v·a、30v·a、40v·a、50v·a;

2. What is the rated resistive load value of TPX, TPY and TPZ current transformers? Denote. The standard value of rated resistive load should be 0.5, 1, 2, 5, 7.5, 10;

The rated output value of the current transformer should be selected according to the rated secondary current value of the transformer and the actual load. In order to meet the requirements of transient characteristics, a larger rated output value can also be used.
Siemens APT current transformer - how to choose a current transformer?

More on that
Siemens APT Relays – Classified by relay form factor Siemens APT Relays – Classified by relay form factor

(1) Miniature relay: the longest side of the relay is not more than 10 mm. (2) Ultra-miniature relay: the longest side size is greater than 10 mm, but not more than 25 mm. (3) Small miniature relay: the longest side size is greater than 25 mm, but not large...

What are the main problems with Siemens APT Relays – Solid State Relays? What are the main problems with Siemens APT Relays – Solid State Relays?

When the solid state relay is open and there is voltage at the load end, there will be a certain leakage current at the output end, and care should be taken to prevent electric shock when using or designing. When the solid-state relay fails to be replaced, the original model or the product with the same technical parameters should be selected as far as possible, so as to match the original application line and ensure that the system ...

Siemens APT Relays – The Difference Between Solid State Relays and AC Contactors Siemens APT Relays – The Difference Between Solid State Relays and AC Contactors

1. First of all, solid-state relays have a long service life and strong reliability. The solid state relay corresponds to the CDG1 series delicacy. This solid-state relay has no mechanical parts and solid-state devices to complete the contact function. Since the parts do not move, they can work in high shock and vibration environments. Because...

Siemens APT Relays – Components of Solid State Relays Siemens APT Relays – Components of Solid State Relays

Solid state relays consist of three parts: the input circuit, the isolation (coupling), and the output circuit. Input circuitry According to the different categories of input voltage, the input circuit can be divided into three types: DC input circuit, AC input circuit and AC and DC input circuit. Some input control circuits are also ...

Siemens APT Relays – Analysis of Common Faults and Causes of Relays Siemens APT Relays – Analysis of Common Faults and Causes of Relays

1. Overhaul of the sensing mechanism For electromagnetic (voltage, current, intermediate) relays, the sensing mechanism is the electromagnetic system. The faults of the electromagnetic system are mainly concentrated in the coil and the moving and static iron cores. (1) Coil fault maintenance Coil failure usually has a coil absolute...

Siemens APT current transformer - working principle and characteristics of current transformer Siemens APT current transformer - working principle and characteristics of current transformer

How a current transformer works The principle of current transformer is based on the principle of electromagnetic induction. A current transformer is composed of a closed core and windings. It has a small number of turns on the primary side winding, stringed in the line where the current needs to be measured, so it often has the full current of the line ...

Siemens APT Relays – The difference between solid state relays and intermediate relays Siemens APT Relays – The difference between solid state relays and intermediate relays

First, the solid-state relay has no contacts and coils in the structure, which can be opened and closed at a high frequency and will not produce sparks, and has a long service life; Second, the intermediate relay is generally only used for the control loop, and cannot work with load, and will make a "pop" sound when it is sucked in; ...

Siemens APT Relays - Selection Method for Solid State Relays Siemens APT Relays - Selection Method for Solid State Relays

1. When selecting the solid-state relay used in the printed circuit board with small current specifications, because the lead terminal is made of high thermal conductivity material, the soldering should be carried out under the condition that the temperature is less than 250 °C and the time is less than 10S.

Siemens APT helps Tianjin's advanced manufacturing industry Siemens APT helps Tianjin's advanced manufacturing industry

Tianjin is a typical industrial city. Due to the steady progress of "three districts and one base", the advanced manufacturing industry has developed rapidly in recent years. Siemens APT brought a variety of low-voltage control products to the 14th China (Tianjin) International Industry Fair held from March 15-18. Siemens APT has launched the PB1...

Siemens APT Relays – the solution to common faults in solid state relays Siemens APT Relays – the solution to common faults in solid state relays

1. The simplest and most effective way is to use a new solid state relay. 2. The other is to determine the voltage of the coil to avoid the voltage provided by the coil being less than the operating voltage. 3. Check whether the polarity is reversed. 4. Reasonable power-on time for the solid state relay coil, if ...

Siemens APT - ALS series limit switch FAQ Siemens APT - ALS series limit switch FAQ

1. What are the installation methods of ALS limit switches? Usually the limit switch is divided into front of the board installation or board back installation, all of which are installed by screws. 2. What are the different modes of limit switch action? According to the action mode of the limit switch head, it is divided into ...

Siemens APT transformer - the use, principle and selection of current transformer Siemens APT transformer - the use, principle and selection of current transformer

The principle of the current transformer is based on the principle of electromagnetic induction. A current transformer is composed of a closed core and windings. Its primary side winding turns are very small, string in the line of the current that needs to be measured, so it often has all the current of the line flowing through, the number of turns of the secondary side winding is relatively large, and the series ...

Siemens APT Relays - a detailed introduction to the classification of relays Siemens APT Relays - a detailed introduction to the classification of relays

Classified according to the working principle or structural characteristics of relays: 1) Electromagnetic relay: an electrical relay that works by using the suction force generated by the current in the input circuit between the electromagnet core and the armature. 2) Solid state relay: refers to the electronic components that perform their functions without mechanical ...

Siemens APT limit switch - wiring method of limit switch Siemens APT limit switch - wiring method of limit switch

1. First of all, there is a general understanding of the knowledge of the limit switch, which is usually composed of a shell, an interconnection system and an operating head. 2. First of all, the limit switch should be set to the desired location, and then connected, in addition, it is necessary to figure out the meaning of different letters, such as NC for the long ...

Siemens APT Limit Switches - Introduction to the types and characteristics of limit switches Siemens APT Limit Switches - Introduction to the types and characteristics of limit switches

Conventional domestic travel switch LX19-001/111 in the LX19 series, LXK3-20S/T in the LXK3 series, JLXK1 series JLXK1-111/411/511 in the conventional travel switch are the most representative.

Siemens APT Relays – a commonly used detection method for high and low voltage relays Siemens APT Relays – a commonly used detection method for high and low voltage relays

1. Visual inspection method: observe the appearance of the relay by the naked eye, check whether it is damaged or deformed, observe whether the contacts are tightly contacted, and whether there are copper slag and other substances attached to the contacts. 2. Parameter detection method: use test instruments to detect the parameters of the relay, such as: ...

Siemens APT current transformers – precautions for the use of current transformers Siemens APT current transformers – precautions for the use of current transformers

1) The wiring of the current transformer should comply with the principle of series connection: that is, the primary winding resistance should be connected in series with the tested circuit, while the secondary winding resistance should be connected in series with all instrument loads 2) According to the size of the measured current, select the appropriate transformation ratio, otherwise the error will increase. At the same time, one end of the secondary side must be grounded in case ...

Siemens APT limit switches – the difference between proximity switches and travel switches Siemens APT limit switches – the difference between proximity switches and travel switches

01 The role is different Proximity switches are contactless switches with a long life and are suitable for "pass-through signals". The travel switch is also known as the limit switch, the travel switch and the limit switch are both position switches, but the travel switch can detect the stroke, and can be used as an input signal to control the circuit at a certain distance ...

Siemens APT Relays – The working principle of zero-crossing AC solid state relays Siemens APT Relays – The working principle of zero-crossing AC solid state relays

1. Working process: AC zero-crossing solid state relays have the characteristic of turning on when the voltage crosses zero and turns off when the load current crosses zero. Circuit diagrams, dimensions and drawings of zero-crossing AC solid state relays When the optocoupler OPT is turned off (i.e. there is no input signal at the control end of the OPT ...

Siemens APT Relays - Precautions for the use of solid state relays Siemens APT Relays - Precautions for the use of solid state relays

1. When choosing the solid state used in the printed circuit board with small current specifications, because the lead terminal is made of high thermal conductivity material, the welding should be carried out under the condition that the temperature is less than 250 °C and the time is less than 10S.

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top