1) The wiring of the current transformer should comply with the principle of series connection: that is, the primary winding resistance should be connected in series with the tested circuit, while the secondary winding resistance should be connected in series with all instrument loads
2) According to the size of the measured current, select the appropriate transformation ratio, otherwise the error will increase. At the same time, one end of the secondary side must be grounded to prevent the high voltage of the primary side from entering the secondary low voltage side once the insulation is damaged, resulting in personal and equipment accidents
3) The secondary side is absolutely not allowed to open the circuit, because once the open circuit is opened, the current I1 on the primary side becomes the magnetizing current, which causes a sudden increase in φm and E2, resulting in oversaturation and magnetization of the core, serious heating and even burning of the coil; At the same time, the error increases after the magnetic circuit is oversaturated and magnetized. When the current transformer is working normally, the secondary side is used in series with the current coils such as measuring instruments and relays, and the impedance of the current coils such as measuring instruments and relays is very small, and the secondary side is approximately short circuit. The magnitude of the secondary current of CT is determined by the primary current, and the magnetic potential generated by the secondary current is balanced by the magnetic potential of the primary current. If it is suddenly opened, the excitation electromotive force suddenly changes from a very small value to a very large value, and the magnetic flux in the iron core presents a seriously saturated flat-top wave, so the secondary side winding will induce a very high spire wave when the magnetic pass through zero, and its value can reach thousands or even tens of thousands of volts, endangering the safety of the staff and the insulation performance of the instrument.
In addition, the secondary side open circuit makes the secondary side voltage reach several hundred volts, and once touched, it will cause an electric shock accident. Therefore, the secondary side of the current transformer is equipped with a short-circuit switch to prevent the secondary side from being opened. In the process of use, once the secondary side is opened, the circuit load should be removed immediately, and then the power should be cut off. Everything can be reused after it has been processed.
4) In order to meet the needs of measuring instruments, relay protection, circuit breaker failure judgment and fault filtering devices, 2-8 secondary winding current transformers are set up in generators, transformers, outgoing wires, bus segmented circuit breakers, bus circuit breakers, bypass circuit breakers and other circuits.
5) For the installation site of the current transformer for protection, it should be set up according to the non-protection zone that eliminates the main protection device as much as possible. For example, if there are two sets of current transformers, and the position allows, they should be located on both sides of the circuit breaker so that the circuit breaker is in the cross protection range
6) In order to prevent bus failure caused by flashover of the bushing of the pillar type current transformer, the current transformer is usually arranged on the outgoing line or transformer side of the circuit breaker
7) In order to reduce the damage in the event of an internal fault of the generator, the current transformer used to automatically adjust the excitation device should be arranged on the outlet side of the generator stator winding. In order to facilitate the analysis and detection of internal faults before the generator is integrated into the system, the current transformer used for the measuring instrument should be installed on the neutral side of the generator.
|
More on that
|
Siemens APT Relays – What should I pay attention to when selecting relays?
1. When selecting a relay, it is necessary to understand the load and type of its contact, because the contact method of the relay of the same model is different, with multiple groups of contacts and single group contacts. When selecting a relay, you can choose the type of contact.
2. And in the peach ...
|
|
Siemens APT Relays - Maintenance Methods for Solid State Relays
1. The influence of the ambient temperature
The load capacity of the solid state relay is greatly affected by the ambient temperature and its own temperature rise, during the use of the device, it should be ensured that it has good heat dissipation conditions, the rated working current of more than 10A products should be equipped with radiators, and the products above 100A should be dissipated.
|
|
Siemens APT – PB1 Series FAQs
1. What are the installation methods of PB1 button?
PB1S and PB1L are fastened with metal screws, and PB1J and PL1 are fastened with plastic nuts.
2. PB1 series pushbuttons can be assembled with up to several sets of contact modules as standard
2*3=6
3. PB1S shell ...
|
|
Siemens APT current transformer – the basis for whether the current transformer is damaged or the measurement is inaccurate
1. The inspection basis for whether the current transformer is damaged:
1. The basis for checking whether the polarity is damaged:
The primary winding of the current transformer is marked P1 and P2, and the secondary winding is marked as S1 and S2. If P1 and S1 are the same name, then this sign is called reduced polarity. Primary current from P1 ...
|
|
Siemens APT - x.R series relays frequently asked questions
1. Does the AC control relay have surge suppression?
SR/NR/PR can produce AC with surge suppression circuits
2. How many types of thermal current specifications are there for our company's relays?
3A, 5A, 8A, 10A, 12A five current specifications
3. Surge suppression back ...
|
|
Siemens APT new x. The new product of R series relay was released
On May 8, 2019, APT held a grand online conference in Shanghai, Beijing, Guangzhou, Nanjing, Changsha and Tiantai...... and more than 20 cities across the country witnessed the new Siemens APT x. The new product of R series relay was released.
...
|
|
Siemens APT helps Tianjin's advanced manufacturing industry
Tianjin is a typical industrial city. Due to the steady progress of "three districts and one base", the advanced manufacturing industry has developed rapidly in recent years. Siemens APT brought a variety of low-voltage control products to the 14th China (Tianjin) International Industry Fair held from March 15-18. Siemens APT has launched the PB1...
|
|
Siemens APT Relays – The action of high and low voltage relays and how to adjust the low voltage side
1. Disconnect the control power supply: Before making the low-voltage terminal contact adjustment, the control power supply should be disconnected first to avoid the current directly or indirectly passing through the relay contact, and avoid electric shock or damage to the relay.
2. Open the relay cover: Open the relay cover, you can see the inside of the relay.
|
|
Siemens APT current transformer - common faults and solutions of current transformers
1. There is an abnormal noise or over-temperature of the iron core
Cause of failure: When the current transformer is in operation, if there is an open circuit or overload in the secondary circuit, it will lead to abnormal sound and over-temperature of the core.
|
|
Siemens APT relay - the use of solid state relay pay attention to five major matters
1. The resistive load should not exceed 60% of the rated current;
2. Overcurrent and load short circuit may cause permanent failure of the internal thyristor in SSR, so it is necessary to install a fuse or air switch, and a fuse can be used if the capacity is small;
3、 ...
|
|
Siemens APT current transformer - precautions for the use of current transformer
1. The wiring of the current transformer should not present problems, otherwise it will lead to failure to operate normally, and there may be damage to the transformer. In this case, the primary winding needs to be connected in series with the measurement circuit, and the secondary winding needs to be connected in series with all the loads.
2. Estimation ...
|
|
Siemens APT Relays - Installation Precautions for High and Low Voltage Relays
1. Choose the right relay: When choosing a high and low voltage relay, you should choose the right product according to your needs, such as selecting according to the rated voltage, current and other information
2. Installation location: high and low voltage relays should be installed in dry, ventilated, non-corrosive gas, less dusty areas, ...
|
|
Siemens APT transformer – common faults and analysis of voltage transformers
(1) The insulation between the iron chips is damaged
Problem: The temperature rises during operation.
Possible causes of the problem:
(1) Poor insulation between iron chips
(2) The use of harsh environmental conditions or long-term operation at high temperature to promote the aging of insulation between iron chips.
( ...
|
|
Siemens APT current transformer - classification of current transformer and its function
1. Current transformers are classified according to the installation method
According to the installation method, the current transformer can be divided into through-type current transformer, pillar type current transformer, bushing type current transformer, and busbar type current transformer.
Through-type current transformer: used to pass through the screen or wall...
|
|
Siemens APT current transformer - how to choose a current transformer?
First, the principle of primary parameter selection of current transformer
The rated primary current of the current transformer is determined by the actual load of the tested circuit, and the rated primary current of the current transformer should not be less than the rated primary current of the circuit.
|
|
Siemens APT Relays – the solution to common faults in solid state relays
1. The simplest and most effective way is to use a new solid state relay.
2. The other is to determine the voltage of the coil to avoid the voltage provided by the coil being less than the operating voltage.
3. Check whether the polarity is reversed.
4. Reasonable power-on time for the solid state relay coil, if ...
|
|
Siemens apt - TL series police lights frequently asked questions
1. How many light sources are there for the TL-70 police light?
There are 3 types, namely LED, incandescent and xenon.
2. What are the colors of the TL-70 police light?
There are 5 types, which are red, yellow, green, blue, and white.
3. What are the types of TL-70 police lights?
3 ...
|
|
Siemens APT Relays – Principles and characteristics of photorelays
When the input quantity (such as voltage, current, temperature, etc.) reaches the specified value, the controlled output circuit is turned on or off an electrical appliance. It can be divided into two categories: electrical (such as current, voltage, frequency, power, etc.) relays and non-electrical (such as temperature, pressure, speed, etc.) relays. With action ...
|
|
Siemens APT Relays – Components of Solid State Relays
Solid state relays consist of three parts: the input circuit, the isolation (coupling), and the output circuit.
Input circuitry
According to the different categories of input voltage, the input circuit can be divided into three types: DC input circuit, AC input circuit and AC and DC input circuit. Some input control circuits are also ...
|
|
Siemens APT limit switch - wiring method of limit switch
1. First of all, there is a general understanding of the knowledge of the limit switch, which is usually composed of a shell, an interconnection system and an operating head.
2. First of all, the limit switch should be set to the desired location, and then connected, in addition, it is necessary to figure out the meaning of different letters, such as NC for the long ...
|
|