Siemens APT Relays - Maintenance Methods for Solid State Relays

Create Date: 2024-8-30 12:03:23|Source: APT/Siemens Shanghai Ergong

1. The influence of the ambient temperature

The load capacity of the solid state relay is greatly affected by the ambient temperature and its own temperature rise, during the use of the device, it should be ensured that it has good heat dissipation conditions, the rated working current of more than 10A products should be equipped with radiators, and the products above 100A should be equipped with radiators and fans when the strong cooling device should pay attention to the good contact between the bottom of the relay and the radiator and consider coating an appropriate amount of thermal grease to achieve the best heat dissipation effect.

If the relay temporarily works at a high temperature of 40°C-80°C), the user can consider derating to ensure normal operation according to the maximum output current and ambient temperature curve data provided by the manufacturer.

2. Over-current and over-voltage protection measures

When the relay is used, the internal output of the solid state relay will be permanently damaged due to overcurrent and load short circuit, so the fast fuse and air switch can be considered in the control loop for maintenance; It is also possible to connect the RC absorption loop and varistor at the output end of the relay to achieve output maintenance. The selection principle is 500V-600V varistor for 220V, and 800V-900V varistor for 380V.

3. Relay input loop signal

When the input voltage is too high or the input current is too large to exceed the rated parameters specified, it can be considered to connect the voltage divider resistor in series at the input terminal or connect the shunt resistor at the input port in parallel, so that the input signal does not exceed its rated parameter value.

4. When used specifically, the control signal and load power supply should be stable, and the fluctuation should not be greater than 10%, otherwise voltage stabilization measures should be taken.

5. When the device is used, it should be kept away from electromagnetic interference and radio frequency interference sources to prevent the relay from malfunctioning out of control.

6. When the solid state relay is open and there is voltage at the load end, there will be a certain leakage current at the output end, which should be paid attention to when using or designing.

7. When the solid-state relay fails to be replaced, the original model or the product with the same technical parameters should be selected as far as possible to match the original application line and ensure the reliable operation of the system.
Siemens APT Relays - Maintenance Methods for Solid State Relays

More on that
Siemens APT Relays – Principles and characteristics of photorelays Siemens APT Relays – Principles and characteristics of photorelays

When the input quantity (such as voltage, current, temperature, etc.) reaches the specified value, the controlled output circuit is turned on or off an electrical appliance. It can be divided into two categories: electrical (such as current, voltage, frequency, power, etc.) relays and non-electrical (such as temperature, pressure, speed, etc.) relays. With action ...

Siemens APT Relays – Classified by relay form factor Siemens APT Relays – Classified by relay form factor

(1) Miniature relay: the longest side of the relay is not more than 10 mm. (2) Ultra-miniature relay: the longest side size is greater than 10 mm, but not more than 25 mm. (3) Small miniature relay: the longest side size is greater than 25 mm, but not large...

Siemens APT Relays – The difference between solid state relays and intermediate relays Siemens APT Relays – The difference between solid state relays and intermediate relays

First, the solid-state relay has no contacts and coils in the structure, which can be opened and closed at a high frequency and will not produce sparks, and has a long service life; Second, the intermediate relay is generally only used for the control loop, and cannot work with load, and will make a "pop" sound when it is sucked in; ...

Siemens APT current transformer – precautions for current transformers Siemens APT current transformer – precautions for current transformers

1. Before the installation of the open current transformer, it must be connected to the meter (or other measuring devices) for the second time to ensure that the transformer is not open for the second time; 2. Place all the open current transformers connected to the secondary line on the site and wait for installation; 3. If the on-site bus is electrical...

Siemens APT Relays – What are the forms of protection relays? Siemens APT Relays – What are the forms of protection relays?

Rail protection relays A protective relay that works mainly as a result of accidents that occur in transmission lines. When this method works, the circuit breakers at both ends of the faulty line will be disconnected. Busbar protection relays A protective relay, mainly due to the power plant or transformer...

Siemens APT Relays – Protection Measures for AC Solid State Relays Siemens APT Relays – Protection Measures for AC Solid State Relays

1. Selection of voltage level and overvoltage protection of solid-state relay When the voltage peak value applied to the AC terminal of the solid state relay exceeds the maximum voltage peak that the AC solid state relay can bear, the components in the solid state relay will be broken down by the voltage and cause damage to the AC solid state relay, ...

Siemens APT Relays – a commonly used detection method for high and low voltage relays Siemens APT Relays – a commonly used detection method for high and low voltage relays

1. Visual inspection method: observe the appearance of the relay by the naked eye, check whether it is damaged or deformed, observe whether the contacts are tightly contacted, and whether there are copper slag and other substances attached to the contacts. 2. Parameter detection method: use test instruments to detect the parameters of the relay, such as: ...

Siemens APT Relays – Maintenance of high-voltage relays Siemens APT Relays – Maintenance of high-voltage relays

1. Regular cleaning: The relay needs to be cleaned regularly with dust and dirt to keep its surface clean and smooth. It can be cleaned with a clean cloth or brush, and detergents containing acids and bases should be avoided. 2. Check the wiring: The wiring of the relay needs to be fastened firmly, and the contact ...

Siemens APT Current Transformer - The difference between voltage transformer and current transformer Siemens APT Current Transformer - The difference between voltage transformer and current transformer

The difference between the voltage transformer and the current transformer in terms of effect principle The primary difference is that the operating conditions are very different during normal operation, and the main performance is as follows: 1) The current transformer can be short-circuited twice, but it cannot be opened; The voltage transformer can be opened twice, but it must not be short-circuited 2) ...

Siemens APT Relays – The action of high and low voltage relays and how to adjust the low voltage side Siemens APT Relays – The action of high and low voltage relays and how to adjust the low voltage side

1. Disconnect the control power supply: Before making the low-voltage terminal contact adjustment, the control power supply should be disconnected first to avoid the current directly or indirectly passing through the relay contact, and avoid electric shock or damage to the relay. 2. Open the relay cover: Open the relay cover, you can see the inside of the relay.

Siemens APT Relays - What are the common faults of relays? Siemens APT Relays - What are the common faults of relays?

1. Contact failure (1) The phenomenon that cannot be disconnected due to mechanical occlusion of the contact (the needle-like protrusion and pit formed on the contact bite each other), fusion welding, or cold welding. (2) The contact wear of the relay is caused by the absence of arc extinguishing devices or measures, or improper parameter selection, ...

Siemens APT limit switches – what are the limits used for? Siemens APT limit switches – what are the limits used for?

daily life There are many applications of travel switches, and it is found in many electrical appliances. So what does such a simple switch do? It mainly plays the role of chain protection. The most common example is its use in washing machines and tape recorders (VCRs). ...

Siemens APT LA39 series button FAQ Siemens APT LA39 series button FAQ

1. What are the installation methods of LA39-A/B/C button? There are five types in total: the Z1 diagonal screw unit, the Z2 straight screw unit, the Z3 nut device with fastening screws, the Z4 nut device without fastening screws, and the Z5 quick and convenient one-handed device 2. LA39 series products can be used ...

Siemens APT Relays – The difference between signal relays and power relays Siemens APT Relays – The difference between signal relays and power relays

Signal relays are used more in secondary maintenance circuit circuits. It tells the right people exactly what is wrong with the maintenance. The power relay is a bit like a discriminant sentence in mathematics. When a constant is entered, the satisfactory and unsatisfactory conditions will output different results. Merit...

Siemens APT current transformer - precautions for the use of current transformer Siemens APT current transformer - precautions for the use of current transformer

1. The wiring of the current transformer should not present problems, otherwise it will lead to failure to operate normally, and there may be damage to the transformer. In this case, the primary winding needs to be connected in series with the measurement circuit, and the secondary winding needs to be connected in series with all the loads. 2. Estimation ...

Siemens APT Relays - Maintenance Methods for Solid State Relays Siemens APT Relays - Maintenance Methods for Solid State Relays

1. The influence of the ambient temperature The load capacity of the solid state relay is greatly affected by the ambient temperature and its own temperature rise, during the use of the device, it should be ensured that it has good heat dissipation conditions, the rated working current of more than 10A products should be equipped with radiators, and the products above 100A should be dissipated.

Siemens APT - LW39 series 10,000 revolutions FAQ Siemens APT - LW39 series 10,000 revolutions FAQ

1. What are the current specifications of universal transfer switches? At present, there are four forms: 10A, 16A, 25A, and 63A 2. What are the positioning angles of the universal transfer switch? At present, it is divided into four angles: 30°, 45°, 60° and 90° 3. There is no customer's ...

Siemens APT - x.R series relays frequently asked questions Siemens APT - x.R series relays frequently asked questions

1. Does the AC control relay have surge suppression? SR/NR/PR can produce AC with surge suppression circuits 2. How many types of thermal current specifications are there for our company's relays? 3A, 5A, 8A, 10A, 12A five current specifications 3. Surge suppression back ...

Siemens APT new x. The new product of R series relay was released Siemens APT new x. The new product of R series relay was released

On May 8, 2019, APT held a grand online conference in Shanghai, Beijing, Guangzhou, Nanjing, Changsha and Tiantai...... and more than 20 cities across the country witnessed the new Siemens APT x. The new product of R series relay was released. ...

Siemens APT Relays – Classified by relay load Siemens APT Relays – Classified by relay load

(1) Micro-power relay: when the contact open circuit voltage is DC 28V, the (resistivity) is 0.1A, 0.2A relay. (2) Weak power relay: when the contact open circuit voltage is DC 28V, (resistivity) is 0.5A, 1A relay. (3) Medium power relay ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top