1. The circuit breaker is equipped with an arc extinguishing device, so the circuit breaker can be operated with load, but it cannot operate the current of the load. The disconnector does not have an arc extinguishing device, and it can operate places where the load current is less than 5A, but it is generally not suitable for operation with load.
2. And the packaging form of the circuit breaker is very good, when we directly observe the circuit breaker, it is impossible to determine whether it is in the state of open or closed. The structure of the disconnector is particularly simple, and you can see at a glance what its operating state is. At the time of overhaul, it is more convenient.
3. The circuit breaker can isolate the devices in the circuit, and can also automatically trip in case of failure. Generally, it is used for control in long-distance electric operation. The isolation switch is a switch with isolator performance, which can only cut off the no-load current in the line, and can not break or control the fault current and load current above the relative capacity, etc., which is generally operated manually in the local area.
|
More on that
|
Tianyi switch - introduction to the type of disconnector switch
According to the different ways in which it is installed
It can be divided into outdoor disconnector and indoor high-voltage disconnector. Outdoor disconnector refers to the disconnector that can withstand wind, rain, snow, filth, condensation, ice and heavy frost, etc., and is suitable for installation on terraces.
According to the different structures of its insulating pillars ...
|
|
Q&A on Cam Switches and Load Disconnectors (11-21)
Q11: What is the maximum number of connecting rods for the rear mounting of P1 and P3?
A: Up to 4 sections can be added, each section is 25mm.
Q12: Does the P switch with SVB in the model come with PE grounding and N-wire terminals?
A: P switch models with SVB are equipped with PE grounding and ...
|
|
Tianyi button indicator - button indicator induction circuit fault and solution
First, the reason for the fault of the induction circuit of the switch button indicator
1. Aging of circuit board: The circuit board of the switch button indicator induction circuit board may be aged if it has been used for too long, resulting in leakage in the circuit, and then the induction failure of the indicator light.
2. Sense ...
|
|
Tianyi switch - dual power supply automatic transfer switch normal working conditions
1) Ambient air temperature: The upper limit of ambient air temperature is +40°C, the lower limit of ambient air temperature is -5°C, and the average value of ambient air temperature for 24h does not exceed +35°C
2) Altitude: The altitude of the installation site does not exceed 2000m.
3) Atmospheric conditions: Atmospheric relative humidity in the surrounding air ...
|
|
Tianyi switch - the selection of disconnector switches
Rated voltage:
The rated voltage of the disconnector (KV) = the nominal voltage of the circuit * 1.2/1.1 times.
Rated current:
The standard value of rated current should be greater than 150% of the maximum load current.
Rated Thermal Stability Current:
Select a rated ...
|
|
Tianyi switch - the difference between high-voltage load switch and circuit breaker
1. The high-voltage load switch can be broken with load and has the function of self-extinguishing arc, but its breaking capacity is very small and limited.
2. The high-voltage isolation switch is generally not able to break with load, there is no arc extinguishing cover in the structure, and there is also an isolation switch that can break the load.
|
|
Tianyi switch - the principle of electromagnetic interference generation and three control technologies of switching power supply
Generation and transmission of electromagnetic interference
There are two ways of electromagnetic interference transmission: one is conducted transmission and the other is radiated transmission. Conducted transmission is a complete circuit connection between the interference source and the sensitive equipment, and the interference signal is transmitted to the receiver along the connected circuit.
|
|
Tianyi switch - introduction to the types and characteristics of limit switches
Conventional domestic travel switch
LX19-001/111 in the LX19 series, LXK3-20S/T in the LXK3 series, JLXK1 series JLXK1-111/411/511 in the conventional travel switch are the most representative.
|
|
Tianyi switch - the characteristics of low-voltage isolation switch
1. When overhauling electrical equipment, provide an electrical interval and a visible disconnection point to ensure the personal safety of maintenance personnel.
2. The disconnector can not be operated with load: it cannot be operated with rated load or large load, and it cannot be divided or combined with load current and short circuit current.
|
|
Tianyi switch - the role of low-voltage isolation switch
1. Through the isolation switch, it plays a good insulating role, so that the whole circuit can be safe and secure, and the maintenance personnel or staff also have enough ability to repair the circuit.
2. At the same time, the low-voltage isolation switch can also change the operation mode of the circuit, which is used in the power plant or gas plant.
|
|
Tianyi switch - the environmental conditions of the high-voltage load switch
1. Altitude: 2000m and below;
2. Ambient temperature: -25°C-+40°C;
3. Relative humidity: the daily average value is not more than 95%, and the monthly average value is not more than 90%;
4. Places without conductive dust, corrosive gases and water vapors;
5. No fire ...
|
|
Tianyi switch - the term introduction of limit switches
Pre-stroke - indicates the distance or angle at which the actuator on the limit switch must move before tripping the switch contact
Operating Point - Indicates the position of the actuator when the switch contact is moved to the working position
Release Point - Indicates the position of the actuator when the contact returns to its original state
Differential - ...
|
|
Tianyi switch - the role of the travel switch (limit switch) and its working principle
The scope of use of the travel switch (limit switch).
The range of use of travel switches (limit switches) is very wide, so what is the effect of travel switches (limit switches)? The position switch (limit switch) refers to the maintenance of the micro switch from external forces, oil, water, gas, ...
|
|
Tianyi switch - the high and low voltage division of low voltage switch
36V is a safe voltage, but it cannot be used as a standard for dividing high and low voltages. There are two ways to divide high and low pressure:
1. According to the rated voltage: the rated voltage is 1000V and below is called low voltage; The rated voltage of 1000V or more is called high voltage.
2. According to the voltage of the equipment to the ground...
|
|
Tianyi switch - classification and application of dual power transfer switch
The dual-power automatic transfer switch is mainly used in the emergency power supply system, which automatically switches the load circuit from one power supply to another (standby) power supply switching appliance to ensure the continuous and reliable operation of important loads. Therefore, the dual-power automatic transfer switch is often used in important places of electricity consumption.
|
|
Tianyi switch - the method of adjusting the current of Tianyi switch
1. Change the reference current of the feedback module
Regulating the reference current is the most basic way to regulate the output current of a switching power supply, and it can usually be achieved by rotating a potentiometer or toggling a switch. Changing the reference current allows the magnitude of the feedback current to be compared with it, so as to control the switch ...
|
|
Tianyi switch - common faults and treatment methods of switching power supply
First, the repair method
The maintenance of a switching power supply can be carried out in two stages
(1) When the power is cut off, it is "Look, Listen, Listen, Measure"
Look: Open the power box, check whether the wire is disconnected, look inside the power supply, and find that the PCB substrate of the power supply is scorched or the components are cracked.
|
|
Tianyi switch - common faults and troubleshooting methods of low-voltage switches
1 The contact is overheated
Contact heat is mainly caused by the current flowing through the contact, and there is power loss between the contacts (such as contact resistance loss, arc energy loss). It is normal for the contacts to heat up, but severe heat (overheating) is a malfunction.
The main ...
|
|
Tianyi switch - how to use the dual power transfer switch correctly
1. When the power is cut off for some reason and the power supply cannot be restored in a short period of time, the backup power supply must be enabled:
(1) Cut off the circuit breakers of the mains power supply (including the circuit breakers of the control cabinet of the power distribution room, and the mains power cut-off of the dual-power switching box), and pull the double-cast anti-backing switch to the side of the self-provided power supply, ...
|
|
The main features of VTeam X42 series limit switches
Uses: X42 series limit switches can be widely used in various types of mechanical equipment, automatic assembly lines and other light and medium load occasions, can detect the object action state, such as presence and absence, movement position, end of stroke, etc.
Overview: The switch is mainly composed of switch operating parts, ...
|
|