Tianyi switch - common faults and troubleshooting methods of low-voltage switches

Create Date: 2024-8-30 12:03:23|Source: TIANYI/TAYEE

1 The contact is overheated

Contact heat is mainly caused by the current flowing through the contact, and there is power loss between the contacts (such as contact resistance loss, arc energy loss). It is normal for the contacts to heat up, but severe heat (overheating) is a malfunction.

The main reasons for contact overheating failure should be found from the following aspects.

1. 1 Contact pressure is reduced

During use, the spring of the contact is deformed due to mechanical damage; or under the action of the arc, the spring is annealed at high temperatures; Reduced moving contact pressure; Or the contact itself is deformed, for example, the two flaps of the static contact in the knife switch are opened outward, so that the contact pressure of the contact is reduced.

1. 2 The contact surface is oxidized or there are impurities

Many metal oxides are undesirable conductors that can increase the contact resistance of the contact, causing the contact to overheat. The higher the contact temperature during operation, the more serious the oxidation; The greater the contact resistance, the faster the temperature rises. For contacts with severe oxidation, it can be gently sanded with 00 diamond sandpaper. Many contacts are inlaid with silver nuggets on their contact surfaces, and the oxide of silver is a good conductor and can be left untreated. Once the dust and dirt on the surface of the contact form an insulating film, the contact resistance will be greatly increased, and it should be removed regularly.

1. 3 Excessive contact wear

If the switch is used for a long time, the pressure will be reduced after the contact wear exceeds a certain amount, and the contact will also overheat, so the contact stroke should be adjusted appropriately.

2 Arc extinguishing system failure

The arc extinguishing device is an important part of the switch, especially for the circuit breaker and fuse.

If the switch does not extinguish the arc properly, it will cause the switch to be damaged, which in turn will cause a greater failure of the electrical installation. The main causes of arc extinguishing system failures are described below.

2. 1 The arc extinguishing hood is damp

The arc extinguishing cover is usually made of asbestos cement board or fiberboard, which is susceptible to moisture. After moisture, the insulation is reduced and the arc cannot be elongated. At the same time, when the arc is burned, the water in the arc extinguishing hood vaporizes under the action of high arc temperature, which causes the spatial pressure of the upper part of the arc extinguishing hood to increase, which prevents the arc from entering the arc extinguishing hood and prolongs the arc extinguishing time. This kind of fault is relatively easy to judge. Normally, the arc ejects a small range out of the arc extinguishing hood, and a crisp sound can be heard. If the arc spray range is very large, and you hear a weak "Bubu" sound, as well as the contact is seriously singeed, and there is a phenomenon such as burnt arc extinguishing cover, it means that the arc extinguishing cover has been damp. At this time, just dry the arc extinguishing hood.

2. 2 Arc extinguishing hood carbonization

Under the condition of high temperature, the surface of the arc extinguishing cover is scorched, forming a carbonaceous conductive bridge, which is very unfavorable to arc extinguishing and should be treated in time. The treatment method can be to file it gently with a fine file, but not to increase the roughness, because the rough surface will increase the resistance of the arc.

2. 3 Short circuit of magnetic blowing coil

In order to introduce arc into the arc extinguishing hood, some switches commonly use a magnetic blowing coil. This kind of coil is generally insulated with air, and no additional insulating material is added. If the coil is deformed by collision and conductive dust accumulates too much, there will be a short circuit between the coil lines or turns, which makes the coil unable to work and reduces the arc extinguishing performance of the switch.

2. 4 Arc extinguishing grid is damaged

The metal arc extinguishing grid is damaged, falling off and corroding, so that the arc can not be pulled into the grid smoothly, which affects the arc extinguishing effect, so it should be repaired in time. The arc extinguishing grid looks like copper on the outside, but in fact, most of it is made of steel, and only a layer of copper is plated on the surface. Damaged grids can be replaced with ordinary white iron sheets.

2. 5 Failure of arc extinguishing contacts

The arc extinguishing contact plays the role of attracting arc and protects the main contact.

Its basic working procedure is: close before the working contact, then open before the working contact. If the wear is severe or the assembly is not reasonable, it will lose its function, therefore, it should be checked and adjusted regularly.

2. 6 The quality of the insulating oil decreases

The insulating oil in the switch often has the functions of arc extinguishing, cooling and insulation. The quality of the insulating oil decreases (mainly due to the increase of moisture and impurities), and the insulation performance decreases, which is extremely unfavorable for arc extinguishing, and may even cause serious accidents such as explosion and oil injection. Therefore, it should be inspected regularly, filtered or replaced.

3 Suction solenoid failure

Suction solenoids are one of the main components of many automatic switches (such as contactors, circuit breakers) operating devices, which play the role of making the switch automatically turn on or off. In an AC circuit, the magnetic flux in the core is alternating and the suction force is alternating, which will cause the armature to vibrate and the switch to work unreliably. In order to overcome this shortcoming, a short-circuit ring is installed on the end face of the core, and the phase of the induced magnet generated by the induced current in the short-circuit ring is different from that of the main magnet in the core. In this way, the resultant flux is not equal to zero at any time, and the armature does not vibrate.

The common faults and causes of electromagnets are as follows.

3. 1 Loud noise

The normal operation of the solenoid only emits a uniform, harmonized, slight working sound, if the noise is very large, it means that there is a fault, and the reasons are as follows:

The iron core is in poor contact with the armature end face. Due to the wear and rust of the end face, or the presence of dust, oil scale and other impurities, the air gap between the end faces increases, the excitation current of the electromagnet increases, and the vibration is violent, which increases the noise.

The iron core and armature end face are finished, and generally cannot be smoothed with tools such as files and abrasive cloths, as long as they are cleaned with gasoline and kerosene.

If you use a file or abrasive cloth to repair, you can do it according to the following methods: firstly, line a layer of carbon paper on the end face, after the armature is engaged, the protruding part of the end face is printed with spots on the carbon paper, and then gently file the spots, and after repeating several times, the end face can be flattened.

Damaged short-circuit rings. The short-circuit ring is specially designed to prevent vibration, and the short-circuit ring breaks or falls off. It will make the core noise due to vibration.

Once found, just use copper material to process one and replace it.

The voltage is too low. If the voltage applied to the coil is too low, generally less than 85% of the rated voltage, the suction power will be insufficient, the excitation current will increase, and the noise will also increase.

The movement part is jammed. When the moving part of the armature driving switch is jammed, the reaction force increases, and the armature cannot be engaged normally, resulting in vibration and noise. Therefore, a few drops of light oil, such as engine oil, transformer oil, etc., should be added to the moving friction parts frequently.

3. 2 The coil is overheated or even burned

The reason for the overheating of the coil is due to the current flowing in the coil, which exceeds the rated value for a long time, and the magnitude of the current in the coil is related to the voltage applied to both ends of the coil, related to the load driven by the armature, and mainly related to the coil excitation current required by the magnetic circuit. When the armature is opened, the air distance is large, the magnetic circuit reluctance is large, and the coil excitation current required to generate the same magnetic flux is large. When the armature is closed, the magnetic circuit is less reluctant, and the excitation current is much smaller. It has been calculated that the excitation current of the armature at start-up is dozens of times greater than when it is closed. Prolonged overheating of the coil is the main cause of coil burnout. The main reasons are as follows.

Switching operations are frequent, need to be started frequently, and the coil is frequently subjected to high currents.

The armature is not in close contact with the core end face, and the large air gap makes the current in the coil much larger than the rated value.

If the armature is not installed well, the end face of the core is not aligned with the end face of the armature, which increases the magnetic resistance of the magnetic circuit and increases the current in the coil.

The transmission part is overloaded with a jamming solenoid and cannot be well engaged.

If the coil voltage is too low, the current in the coil will inevitably increase if the same load is driven.

If the voltage at the end of the coil is too high and the magnetic flux of the core is saturated, it will also cause the core to overheat.

The coil insulation is damp and there is an inter-turn short circuit, which will also increase the current in the coil.

4 Failure of the fuse

The fuse is a simple protection appliance in the circuit, which is used in series in the circuit, and can be used to protect the electrical device from the damage of overload current and short-circuit current, and its structure is composed of melt, contact and shell connecting the melt. Some fuses also have a simple arc extinguishing device to improve the arc extinguishing capacity of the fuse. Due to the simple structure and maintenance of the fuse and its small size, it is widely used in low-voltage power distribution devices, and is also widely used to protect voltage transformers and small-capacity electrical equipment in high-voltage power grids from 3 to 35 kV.

The melt is generally made into three shapes, namely filamentous, sheet-like, and cage-like.

Lead-tin melts are generally made into filaments; The zinc-tin melt is generally made into sheets; Silver melt is made into filaments or flakes; Copper melt can be made into filaments, sheets, and cages.

When the current in the circuit, i.e., the current of the two fuse fuses, reaches a certain value, the fuse will blow. The fault of the fuse is mainly manifested in the fact that the fuse is often abnormally burned, the connecting screws of the fuse are burned, and the service life of the fuse is reduced. The following scenarios should be considered to find the fault of a fuse.

4. 1 Whether the selection of fuses is reasonable

The fuse of the fuse should be selected according to the size of the load and the nature of the load.

(1) For electric lighting loads, the rated current of the load is selected, that is, the rated current of the fuse is greater than or equal to the rated current of the load.

(2) When selecting the fuse for the load selection of the asynchronous motor, the rated current should be considered, which is larger than the rated current of the motor.

(3) The rated current of the total fuse of multiple motors should consider the sum of 2-3 times the rated current of one motor with the capacity and the rated current of other motors.

(4) The selection of the rated current of the drop fuse on the high voltage side of the transformer should consider the excitation current when the transformer is closed, which is generally 2-3 times of the rated current. The size of the fuse is too small, which will inevitably make the fuse blow abnormally. For example, a three-phase electric heater with a capacity of 3 kW and a three-phase electric motor may be suitable for the electric heater if the fuse specifications are consistent, but when the motor is started, the fuse will blow abnormally.

(5) The selection of the rated current of the melt on the high and low voltage side of the distribution transformerFor the distribution transformer with a capacity of 100 kVA and below, the rated current of the melt on the high voltage side should be selected according to 2-3 times of the rated current on the high voltage side of the transformer.

For distribution transformers with a capacity of 100 kVA and above, the rated melt current on the high side of the transformer should be 1 of the rated current on the high side of the transformer. 5 - 2 times the selection.

The rated current of the low-voltage fuse can be 1. 5x pick.

(6) The rated current of the fuse should be greater than or equal to the rated current of the fuse. This is often the case, the fuse is suitable, but the fuse box of the fuse is smaller. In this way, the heat dissipation condition of the fuse is poor, and it is easy to make the fuse abnormal blowing.

4. 2 The fuse installation is unreasonable

The fuse end should be wound correctly, if it overlaps or winds in the opposite direction, it will make the fuse and the fuse terminal poor contact or the joint heat, so that the fuse is abnormal fuse.

During installation, the fuse will be blown abnormally if the fuse is pulled too tightly to reduce the cross-sectional area of the fuse, or the fuse will be too bent to increase the heat generation of the fuse.

When one fuse is not enough and multiple fuses are needed, it is generally not possible to twist them into a strand for use, because this will reduce the total capacity of the fuse and may also cause abnormal blowing.

The screws fixing the fuse must be flattened with a gasket, and some also need to add a spring gasket, otherwise it is easy to cause the fuse to blow abnormally.

For fuses equipped with quartz sand, when replacing the fuse, it is necessary to replace all the quartz sand. The new quartz sand must be dry and the purity should not be less than 95%.

Otherwise, the fuse will also be blown abnormally due to the reduction of the arc extinguishing ability of the fuse.

4. 3 Precautions for the use of the fuse

The melt should be selected correctly to ensure the selectivity of its work.

The rated current of the melt installed in the fuse can only be less than or equal to the rated current of the fuse.

After the melt is fused, the melt of the same size and material should be replaced, and it should not be thickened or reduced at will, and other metal wires that are not easy to fuse should be used to replace it, so as not to cause accidents.

When installing the melt, the melt itself should not be damaged. Otherwise, it may be burned out when the normal working current passes, causing unnecessary power outages.

The melt ends of the fuse should be in good contact.

When replacing the melt, the power supply should be cut off, and the fuse should not be pulled out in the case of live electricity.
Tianyi switch - common faults and troubleshooting methods of low-voltage switches

More on that
Tianyi switch - the principle of electromagnetic interference generation and three control technologies of switching power supply Tianyi switch - the principle of electromagnetic interference generation and three control technologies of switching power supply

Generation and transmission of electromagnetic interference There are two ways of electromagnetic interference transmission: one is conducted transmission and the other is radiated transmission. Conducted transmission is a complete circuit connection between the interference source and the sensitive equipment, and the interference signal is transmitted to the receiver along the connected circuit.

Overview of limit switches and their functions - Tianyi limit switches Overview of limit switches and their functions - Tianyi limit switches

An overview of limit switches Limit switch is a kind of mechanical orientation and electronic control interface, the mechanical action into electrical signals, is suitable for industrial environment of a common electromechanical and electrical components, through the contact way to detect the object, the existence and so on. It is possible to control the device's ...

Tianyi switch - PCB design considerations for switching power supplies Tianyi switch - PCB design considerations for switching power supplies

In the design of switching power supply, the physical design of the PCB board must be proper, otherwise it may cause excessive electromagnetic interference and lead to unstable power supply. 1. The design process from the schematic diagram to the PCB should be rigorous and perfect: the establishment of component parameters ...

Tianyi switch - the difference between high-voltage load switch and high-voltage isolation switch Tianyi switch - the difference between high-voltage load switch and high-voltage isolation switch

1. The high-voltage load switch can be broken with load and has the function of self-extinguishing arc, but its breaking capacity is very small and limited. 2. The high-voltage isolation switch is generally not able to break with load, there is no arc extinguishing cover in the structure, and there is also an isolation switch that can break the load.

Tianyi switch - the selection of disconnector switches Tianyi switch - the selection of disconnector switches

Rated voltage: The rated voltage of the disconnector (KV) = the nominal voltage of the circuit * 1.2/1.1 times. Rated current: The standard value of rated current should be greater than 150% of the maximum load current. Rated Thermal Stability Current: Select a rated ...

Tianyi switch - routine detection of air switch Tianyi switch - routine detection of air switch

The socket, lamp head, kitchen, bathroom, refrigerator, air conditioner of each route should be put out separately, and each route should have a separate air switch, high-power rooms, such as kitchens and bathrooms, the line of more than 4 square millimeters should reach 20A, and the general lamp head line should only be 16A, and each line ...

Tianyi switch - the use conditions and applicable places of low-voltage isolation switch Tianyi switch - the use conditions and applicable places of low-voltage isolation switch

1. The basic conditions for the use of low-voltage isolation switches (1) The altitude does not exceed 1000 meters; (2) The ambient temperature is not higher than +40°C and not lower than -40°C; (3) The relative humidity is not more than 85% (relative to +20±5°C). 2. The low-voltage isolation switch is not suitable for the following ...

Tianyi switch - maintenance of disconnector switch Tianyi switch - maintenance of disconnector switch

1) Clean the dust on the surface of the porcelain, check whether the surface of the porcelain is glazed or damaged, whether there are cracks and flashover marks, and whether the iron and porcelain joints of the insulator are firm. If the damage is severe, it should be replaced; 2) Wipe the oil stains on the blades, contacts or fingers with gasoline and check the contact ...

Tianyi switch - the operation precautions of the disconnector switch Tianyi switch - the operation precautions of the disconnector switch

(1) Before operation, check that the circuit breaker (switch) is in the opening position accordingly to prevent the isolation switch from being pulled and closed with load. (2) There is a locking device to prevent misoperation between the knife switch, the grounding knife switch and the switch, and the reverse operation must be carried out in order. If it is locked and cannot be operated, ...

Tianyi switch - the difference between C type and D type of air switch Tianyi switch - the difference between C type and D type of air switch

The meaning is different, the scope of application is different, and the role is different. Air opening C represents the current, and the D model represents the power. The scope of use is different. If it is a household electricity, the air switch of the C model is generally chosen. The role is different. Type C it is used for home lighting use, Type D is suitable for ...

Tianyi switch - the high and low voltage division of low voltage switch Tianyi switch - the high and low voltage division of low voltage switch

36V is a safe voltage, but it cannot be used as a standard for dividing high and low voltages. There are two ways to divide high and low pressure: 1. According to the rated voltage: the rated voltage is 1000V and below is called low voltage; The rated voltage of 1000V or more is called high voltage. 2. According to the voltage of the equipment to the ground...

Tianyi switching power supply troubleshooting Tianyi switching power supply troubleshooting

1. Check the key points: 1) Whether the voltage at point B is 310V. 2) Whether the 15V voltage is normal. 3) Whether the voltage at point C is greater than 14V. 4) Whether the SS terminal of (8) pin IC6 is higher than 10V, whether the SD terminal of pin (10) is lower than 0.6V, and whether there is a square wave transmission at pin 13 and pin 14 ...

Tianyi switch - the method of adjusting the current of Tianyi switch Tianyi switch - the method of adjusting the current of Tianyi switch

1. Change the reference current of the feedback module Regulating the reference current is the most basic way to regulate the output current of a switching power supply, and it can usually be achieved by rotating a potentiometer or toggling a switch. Changing the reference current allows the magnitude of the feedback current to be compared with it, so as to control the switch ...

Tianyi switch - the use and function of air switch Tianyi switch - the use and function of air switch

What are the uses of air switches 1. The air switch is an important electrical appliance in the low-voltage distribution network and power drive system, which integrates control and a variety of protection functions. In addition to completing contact and breaking circuits, it can also generate short circuits to circuits or electrical equipment. Severe...

Tianyi switch - dual power supply automatic transfer switch normal working conditions Tianyi switch - dual power supply automatic transfer switch normal working conditions

1) Ambient air temperature: The upper limit of ambient air temperature is +40°C, the lower limit of ambient air temperature is -5°C, and the average value of ambient air temperature for 24h does not exceed +35°C 2) Altitude: The altitude of the installation site does not exceed 2000m. 3) Atmospheric conditions: Atmospheric relative humidity in the surrounding air ...

Tianyi Switch - Cam Switch and Load Disconnector Q&A (1-10) Tianyi Switch - Cam Switch and Load Disconnector Q&A (1-10)

Q1: What is the difference between P switch and T switch? A: P switch is a load isolation switch, mainly used for the opening and isolation of the main circuit load, only 3P and 3+N, can add auxiliary contacts; The T-switch is a multi-function switch with a wide variety of contact sequences, modular contact units, which can ...

Tianyi switch - classification and application of dual power transfer switch Tianyi switch - classification and application of dual power transfer switch

The dual-power automatic transfer switch is mainly used in the emergency power supply system, which automatically switches the load circuit from one power supply to another (standby) power supply switching appliance to ensure the continuous and reliable operation of important loads. Therefore, the dual-power automatic transfer switch is often used in important places of electricity consumption.

Tianyi switch - the term introduction of limit switches Tianyi switch - the term introduction of limit switches

Pre-stroke - indicates the distance or angle at which the actuator on the limit switch must move before tripping the switch contact Operating Point - Indicates the position of the actuator when the switch contact is moved to the working position Release Point - Indicates the position of the actuator when the contact returns to its original state Differential - ...

Where can Tianyi switch - limit switch be used? Where can Tianyi switch - limit switch be used?

daily life There are many aspects of the use of limit switches, and it is found in many electrical appliances. So what effect can such a simple switch have? It is first and foremost a chain maintenance effect. The most common example is its use in washing machines and tape recorders (video recorders). ...

Tianyi switch - precautions for switching power supply to regulate current Tianyi switch - precautions for switching power supply to regulate current

1. Pay attention to stability When adjusting the output current of the switching power supply, the stability of the circuit must be ensured, otherwise there will be current fluctuations, disturbances and other phenomena, which will affect the normal operation of electronic equipment. Therefore, it is necessary to perform a ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top