Fault 1: The thermostat does not turn on (the screen does not display)
Analyze the causes
1. Wrong wiring;
2. The voltage of the input terminal is not enough or the input terminal is damaged by the empty leakage guarantee;
3. Whether the cable between the panel and the power board is broken or plugged incorrectly;
4. Load short circuit or open circuit, probe line leakage;
5. For other reasons, return to the factory for analysis and solution.
Resolution
1. Check whether the thermostat wiring is correct when the power is off (the middle AC220V corresponds to the input neutral line of fire);
2. Check whether there is a 220V voltage between the input terminals L and N of the thermostat (note that it is not enough to use a pen to measure the power of the live wire, but also to ensure that the neutral line is powered);
3. Open the thermostat panel, check whether the cable is disconnected, and check whether the cable is plugged in reverse or obliquely;
4. Remove the output load line and remove the outer probe line;
5. After completing the above steps 1-4, power on again and observe whether the thermostat is on, if not, the thermostat needs to be returned to the factory for analysis.
Fault 2: Thermostat flashes (normal boot, reboot repeatedly)
Analyze the causes
1. Wrong wiring;
2. The input terminal is not enough to open and leak and protect the belt load;
3. Load short circuit or open circuit, probe line leakage;
4. For other reasons, return to the factory for analysis and solution.
Resolution
1. Check whether the thermostat wiring is correct when the power is off (the middle AC220V corresponds to the input neutral line of fire);
2. Replace the input line;
3. Remove the output load line and remove the outer probe line;
4. After completing the above 1-3 steps, power on again and observe whether the thermostat is on.
Fault 3: The thermostat is missing, the keys are not easy to use, and the backlight is bright and not displayed
Analyze the causes
1. The single-chip microcomputer crashes;
2. Other problems, return to the factory for analysis and solution.
Resolution
1. Enter the background to restore the factory settings in the shutdown state, if there is a password, you need to crack the password first and then restore the factory settings;
2. Other problems, return to the factory for analysis and solution.
Fault 4: The display is normal and not heated
Resolution
1. Remove the load line, restore the factory settings, turn on and off the relay in the background of the thermostat, pay attention to whether there is a relay action, if there is no action, return to the factory for analysis, if there is an action, enter the next step;
2. After setting the temperature greater than (measurement temperature + tolerance temperature), whether the thermostat has a heating mark (if there is a next step, if there is no return to the factory for analysis), measure whether there is a voltage between the zero live wire at the output end of the thermostat, if there is a voltage, it is judged that the front end of the thermostat is empty open and load or the rear end load problem; If there is no voltage, it needs to be returned to the factory for analysis.
Fault 5: The thermostat is locked
Resolution
1. No password, press and hold the power button to unlock;
2. If you have a password, enter the password to unlock, if you forget the password, you need to press the setting key on the password page, and provide the 6-digit prompt password to the manufacturer, and the manufacturer will feedback the password.
|
More on that
|
RLC Thermostat – Precautions for Thermostat Operation
1) Measure the function
Its temperature measurement scale is mainly between -20 °C and 80 °C, and the humidity measurement scale is mainly between 20% RH and 99% RH. In addition, it has a temperature resolution of 1°C and a humidity of 1%RH.
2) Parameters and data display functions
Temperature and humidity control ...
|
|
RK Thermostat - Part of the LCD shows the status quo of floor heating thermostats
1) The LCD interface is too large or the display symbols are not proportional or standard.
2) The terminal blocks or circuits (components) that control the output cannot withstand large currents.
3) The cable of the external sensor (ground probe) is a thin and flexible wire, which cannot be inserted into the embedded pipe, and it is also a hidden danger for future maintenance.
...
|
|
RHK thermostat – a rapid detection method for common air conditioner thermostats
1. Bellows or diaphragm air conditioner thermostat
Fault Symptom:
Poor contact or burning, resulting in the circuit cannot be connected; The frequent action of the contact arc and sticking causes the circuit to be unbreakable; The leakage of the thermostat in the temperature sensing chamber causes the contact to fail to operate and lose control ...
|
|
How to set the parameters of the RCRS400 thermostat
1. Set temperature: Press the SET button to set or view the temperature set point. Press the SET key digital tube characters to start flashing, indicating that the instrument has entered the setting state, press the △ key to increase the set value, press the ▽ key to decrease the set value, press and hold the △ key or ▽ key The data will change rapidly, press the SET key again ...
|
|
RKC Level Gauge – the correct way to use the float level gauge
(1) Before use, first check whether the level gauge is within the verification cycle, otherwise, it should be calibrated, and replaced in time if it is unqualified.
(2) The sensor should be installed horizontally, and the length of the lower entry should meet the technical requirements.
(3) The connection between the sensor and the explosion-proof junction box should be tightened and tightened.
|
|
Specifications and models of RKC thermostats
CH102 (48×48×100mm)
CH402 (48×96×100mm)
CH902 (96×96×100mm)
1. RH400 size: 48*96, depth 60, about 250g
1. Thermocouples: K, J, R, S, B, E, N, T, W5RE/W6RE, PL‖, U, L
...
|
|
RLC thermostats – the classification of thermostats and their detailed introduction
1. Sudden jump thermostat
The type of various sudden thermostats is collectively called KSD, such as KSD301, KSD302, etc., the thermostat is a new type of bimetal thermostat, mainly as a variety of electric heating products with overheat protection, generally connected with the thermal fuse in series, sudden temperature ...
|
|
Introduction to the types of alarms for RRKC thermostats
* Alarm table {ALM1} (standard built-in)
A: Upper limit deviation alarm G: Standby upper and lower limit deviation alarm attached
B: Lower limit deviation alarm H: Upper limit input value alarm
C: Upper and lower limit deviation alarm J: Lower limit input value alarm
D: Alarm in the range K: Attached standby ...
|
|
Introduction and wiring method of Japan physical and chemical RKC thermostat
The core control algorithm of the temperature regulator is PID control, P (Proportional) ratio + I (Integral) point + D (Differential) differential control. In addition to the traditional PID control algorithm, RKC also has ON-OFF control, custom parameter control, adaptive parameter control and other algorithms, ...
|
|
RKC Level Gauges – Precautions for Level Gauges
The correct selection of the level gauge can ensure the better use of the level gauge. What kind of level gauge should be selected according to the physical and chemical properties of the fluid medium to be measured? What is the diameter of the level gauge, the flow range, the lining material, the electrode material, and the output current? can adapt to the ...
|
|
RRC thermostat - the principle of sudden jump thermostat, how to judge the good or bad?
1. What is the principle of the sudden jump thermostat?
The sudden jump thermostat is a kind of thermostat, which is a series of automatic control elements that are physically deformed inside the switch according to the temperature change of the working environment, resulting in some special effects and on-off action. Sudden jump ...
|
|
RKC Level Gauge – Buoy Level Gauge Use and Precautions
1. Support welding under the guidewire:
According to the direction of the movement of the buoy of the level gauge, determine the position at the bottom of the container, and fix the guide bracket (piece 1) under the welded or riveted steel wire
2. Install the guide rail joint.
(1) Straighten the wire forcefully and fix it at the lower support, taking care not to ...
|
|
RK Level Gauge - Introduction to the characteristics of float level gauge
It is suitable for measuring the level and interface of the liquid medium in the container. In addition to on-site instructions, it can also be equipped with remote transmitters, alarm switches, and detection functions.
The indication is novel, the reading is intuitive, eye-catching, and the direction of the observation indicator can be changed according to the user's needs.
Large measuring range ...
|
|
RRKC thermostat – the correct way to set up the thermostat
Press the SET button to set or view the temperature set point, press the SET key digital tube characters to start flashing, indicating that the instrument has entered the setting state, press the △ key to increase the set value, press the ▽ key to decrease the set value, press and hold the △ key or ▽ key The data will change rapidly, press the SET key again The instrument returns to normal working condition ...
|
|
The main technical indicators of RKC thermostat
The main technical indicators of RKC thermostat
· Input: various thermocouple (TC), RTD standard current and voltage signals (see input type table);
· basic error: 0.5% of the input full-scale ±±1 word;
· Resolution: 1°C, 0.1°C;
...
|
|
RKC Level Gauge – How to properly use a plug-in float level gauge for level measurement
1. Select the appropriate level gauge
First of all, it is necessary to choose the appropriate level gauge. The following factors should be taken into account in the selection of a level gauge:
Measure the properties of the medium: e.g., temperature, pressure, viscosity, corrosiveness, etc.
Measuring range: i.e. the height range of the liquid ...
|
|
What are the solutions to the failure of the RRKC thermostat - the sudden thermostat?
1. The cleanliness and finish of the contact surface have a great impact on the working condition of the contact. When the surface of the contact is rough or there is excess material on the contact, it is easy to cause arcing and reduce the life of the contact. Therefore, the parts cleaning process should be improved to eliminate excess materials; Increasing the process of screening excess materials, ...
|
|
How to set the parameters of the RKC rs400 thermostat?
1. Set temperature: Press the SET button to set or check the temperature set point. Press the SET key digital tube character start flashing, indicating that the appearance has entered the setting state, press the △ key to increase the set value, press the ▽ key to decrease the set value, press and hold the △ key or ▽ key data will change rapidly, press the SET key again ...
|
|
How to set the parameters of the RKG thermostat - intelligent digital display controller?
1. First of all, the digital display should be installed on the cabinet, so the overall coordination should be considered, too large may not fit, too small to see the display numbers.
2. In addition, the large size of the instrument is generally more expandable, the same function price may be expensive, the small size of the instrument may be ...
|
|
Common faults and solutions of RKC temperature controllers
1. The power indication is normal, but the temperature controller has no screen display. Most of this fault is caused by the heating of the voltage regulator element (7805 or 7812) on the thermostat during long-term use, which leads to the breakpoint of the solder joint, and sometimes it is caused by the phenomenon of virtual soldering at the factory, and the main re-soldering can be done.