The main technical indicators of RKC thermostat

Create Date: 2024-8-30 12:03:23|Source: RKC

The main technical indicators of RKC thermostat

· Input: various thermocouple (TC), RTD standard current and voltage signals (see input type table);

· basic error: 0.5% of the input full-scale ±±1 word;

· Resolution: 1°C, 0.1°C;

· Sampling period: 3 times/sec

· Alarm function: upper limit, lower limit, upper deviation, lower deviation, in the interval, outside the interval;

· Alarm output: relay contact AC250V 3A (resistive);

· Control output: relay contact AC250V 3A (resistive), logic level C 0/12V (with solid state relay SSR), zero-crossing trigger pulse: photocouple thyristor output 1A600V 0-10mA current output (load resistance below 600Ω), 0-20mA current output (load resistance below 600Ω), 4-20mA current transmission (load resistance below 600Ω);

· Control mode: fuzzy PID control, bit control;

· Power supply voltage: AC85-264V(50/60Hz)(rated 100-240V AC) 21.6-26.4V AC(rated 24V AC) 21.6-26.4V DC(rated 24V DC);

· working environment: non-corrosive occasions with temperature of 0-50°C and temperature <85%RH. Power consumption< 5VA;

· panel size: 80X160, 160X80, 96X96, 72X72, 96X48, 48X96, 48X48mm.
The main technical indicators of RKC thermostat

More on that
Classification of thermostats and their brief introduction Classification of thermostats and their brief introduction

Pop-up thermostat Bimetal Disc Jump Thermostat is a kind of bimetal sheet after constant temperature as a heat-sensitive reaction component, when the temperature of the main part of the product rises, the heat generated is transferred to the bimetal disc, and when the operating temperature is set, it acts quickly, and acts through the mechanism to act as a contact ...

RLC thermostat - a detailed explanation of dry-type transformer thermostats RLC thermostat - a detailed explanation of dry-type transformer thermostats

The working principle of dry-type transformer thermostats The dry-type transformer temperature controller is a new generation of controller designed for the safe operation of dry-type transformers. The controller adopts single-chip microcomputer technology, and uses three platinum thermal resistors embedded in the three-phase winding of the dry-type transformer to detect and display the transformer.

RKC thermostat - introduction of three wiring methods of thermal resistance RKC thermostat - introduction of three wiring methods of thermal resistance

1. The three wiring methods of Pt100 RTD are different in principle: The two-wire system and the three-wire system are measured by the bridge method, and the relationship between the temperature value and the analog output value is given after ***. There is no bridge on the four wires, it is completely just sent with a constant current source, measured by a voltmeter, and the test is given after *** ...

RHK thermostat – a rapid detection method for common air conditioner thermostats RHK thermostat – a rapid detection method for common air conditioner thermostats

1 Bellows or diaphragm air conditioner thermostat Fault Symptom: Poor contact or burning, resulting in the circuit cannot be connected; The frequent action of the contact arc and sticking causes the circuit to be unbreakable; Leakage of thermostat in the temperature sensing chamber, causing the contacts to fail to operate and lose control ...

RLC thermostats – the classification of thermostats and their detailed introduction RLC thermostats – the classification of thermostats and their detailed introduction

1. Sudden jump thermostat The type of various sudden thermostats is collectively called KSD, such as KSD301, KSD302, etc., the thermostat is a new type of bimetal thermostat, mainly as a variety of electric heating products with overheat protection, generally connected with the thermal fuse in series, sudden temperature ...

Common faults and analysis of thermostats Common faults and analysis of thermostats

Common faults of thermostats 1. There is no display when the power is on. This type of problem first determines whether the power supply is available and whether the power supply matches the power supply required by the thermostat, and then checks whether the wiring is secure. The problem is still there, then it is the problem of the thermostat itself. 2. There is a display, and the control is wrong. This...

RK Level Gauge - Typical Fault Problems and Solutions of Pontoon Level Gauges RK Level Gauge - Typical Fault Problems and Solutions of Pontoon Level Gauges

1. There is no liquid level display or lower liquid level display When the sewage is discharged, only a small amount of condensate flows out, and it is judged that the pontoon is blocked. Treatment: Dismantle the outer pontoon and find that the pontoon is almost filled with dirt and impurities. Clean, calibrate, and return to normal. 2. The liquid level display is ...

RKC Thermostat Usage Warning RKC Thermostat Usage Warning

· Wiring warning: - If the instrument fails or an error occurs, which can cause a system failure, install external protection circuits to prevent such accidents; - To prevent damage or failure of the instrument, use appropriate fuses to protect the power cord and input/output cord from strong power shocks. ...

RK Thermostat - The working principle and device precautions of liquid expansion thermostat RK Thermostat - The working principle and device precautions of liquid expansion thermostat

How liquid expansion thermostats work Liquid expansion thermostat is a physical phenomenon (volume change) that causes the material (generally liquid) in the temperature sensing part of the thermostat to undergo corresponding thermal expansion and cold contraction when the temperature of the controlled object changes, and the diaphragm box connected with the temperature sensing part expands or ...

RHK thermostat - 5 common problems and solutions for stand-alone thermostats RHK thermostat - 5 common problems and solutions for stand-alone thermostats

Fault 1: The thermostat does not turn on (does not light up) Analyze the causes 1. Wrong wiring 2. The voltage of the input terminal is not enough or the input terminal is damaged by empty opening and leakage 3. Whether the cable between the panel and the power board is broken or plugged incorrectly 4. Load short circuit or open circuit, probe ...

RKC Thermostat – How can a thermostat be broken? RKC Thermostat – How can a thermostat be broken?

First, the temperature does not appear 1. Fault with the temperature sensor If the temperature probe of the temperature sensor breaks or the wire is broken, the sensor does not have a digital display when the temperature sensor is connected, but only shows the "----" and sounds an alarm.

RLC thermostat - classification and detailed explanation of floor heating thermostat RLC thermostat - classification and detailed explanation of floor heating thermostat

1. Mechanical The sensitive gas diaphragm box or thermal bimetal sheet is used as the temperature sensing element to form the temperature control switch of the mechanical contact. This kind of thermostat is more in the European and American markets, and only a few domestic manufacturers promote such products. Mechanical floor heating thermostats usually have contact currents of no more than 8A, which are suitable for ...

Precautions for the use of RKC thermostats Precautions for the use of RKC thermostats

fold When the RKC thermostat comes out, it is a single-loop regulator, that is, it only has a heating function, which is called the basic meter, which is generally sent to the agent, and the agent will expand the multi-channel adjustment and alarm output control function, which is called "changing the meter" in the industry, so as to ensure that there is very little hardware cost.

RLC Thermostat – Instructions for installation and use of pop-up thermostats RLC Thermostat – Instructions for installation and use of pop-up thermostats

1. Grounding method: It is connected to the grounding metal parts of the equipment through the metal cover of the thermostat. 2. The thermostat should work in the general indoor environment where the relative humidity of the air is not more than 90%, and there are no corrosive gases, flammable gases and conductive dust. 3. The thermostat adopts contact ...

RKG thermostat - an introduction to the relevant knowledge of temperature controllers RKG thermostat - an introduction to the relevant knowledge of temperature controllers

The temperature controller is an electrical switchgear that controls the temperature of an air-conditioned room. The temperature range in the air-conditioned room controlled by the temperature controller is generally 18°C--28°C. The temperature controller commonly used in window air conditioners uses the principle of pressure to push the contacts on and off. Its structure consists of bellows ...

RK thermostat - common problems and solutions of electric floor heating stand-alone thermostat RK thermostat - common problems and solutions of electric floor heating stand-alone thermostat

Fault 1: The thermostat does not turn on (the screen does not display) Analyze the causes 1. Wrong wiring; 2. The voltage of the input terminal is not enough or the input terminal is damaged by the empty leakage guarantee; 3. Whether the cable between the panel and the power board is broken or plugged incorrectly; 4. Load short circuit or broken ...

RKC converter - an introduction to the classification of converters RKC converter - an introduction to the classification of converters

  Analog-to-digital converters The analog-to-digital converter comprises a first transmission circuit, which receives an input voltage and an output clock signal, which is phase-shifted, depending on the input voltage, and a second transmission circuit receives a reference voltage and an input clock signal, and outputs a reference clock signal, which ...

RLC thermostat - temperature controller control method classification and working principle RLC thermostat - temperature controller control method classification and working principle

1. The temperature controller control method is generally divided into two types: One is controlled by the temperature change of the cooled object, and the vapor pressure temperature controller is mostly used, and the other is controlled by the temperature difference change of the cooled object, and the electronic temperature controller is mostly used. ...

Wiring method of the RKG thermostat Wiring method of the RKG thermostat

Take CD901 as an example, L(1) pin to 220 volt live wire, N(2) pin 220 volt neutral wire, 3,4 pins for *** output, 5,6 pins for the second output, 7, 8, 9 pins are alarm output, The rear three pins are connected to thermocouples or PT100 and so on.

Common faults in the use of RKC thermostat Pt100 RTD Common faults in the use of RKC thermostat Pt100 RTD

  PT100 RTD is a platinum RTD, which can be regarded as a more commonly used thermometer in the range of medium and low temperatures, and it has a wide range of uses, including medical, electric, industrial production, thermometers and other high-precision thermometers. But due to the range of use ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top