Why can't the inverter be equipped with a leakage protector?

Create Date: 2024-8-30 12:03:23|Source: LS/Power Generation

When using an inverter, a leakage maintainer must not be used. This is a major criterion for the use of frequency converters.

                               Why can't the inverter be equipped with a leakage protector?

Some users choose the corresponding leakage maintainer for the inverter when using the inverter. * The result is that the inverter moves together, the leakage maintainer acts, and the system cannot operate at all. Why?

The principle of a leakage maintainer is that the zero sequence current is zero. When using an inverter, the zero sequence current cannot be zero.

The output side of the inverter is a PWM wave, and there is a capacitive effect of a long cable between the motor cable and the ground, which is more obvious when using a shielded cable. During the operation of the inverter, the capacitor is charging and discharging, and the current flows into the ground through the capacitor, and flows back to the inverter from the grounding wire on the incoming side to form a current loop. If a leakage maintainer is used on the inlet side, it will operate and the blocking system will operate. So, don't equip your drive with a leakage maintainer. If you want to ensure safety, just do a good job of grounding the equipment.

Example: Q: An 18.5KW boiler induced draft fan is installed with an 18.5KW inverter, as soon as the inverter is installed, the power distribution room will jump when it is opened, and the original power distribution room is equipped with a leakage maintainer (200mA action, 30mA pulse). The customer was asked to remove the leakage maintenance was refused, and then the carrier frequency was adjusted to 1KHz, and the inverter engine method was still not solved, * After the doubt that the power line of the motor has leakage, because its length is about 20 meters and buried in the ground, but it is also difficult to ask the customer to replace it (its original power frequency is used normally). Is there a brief and useful solution?

Answer: Since the leakage maintainer generally detects that the three-phase unbalance is more than %20, it will jump for maintenance, and when the three-phase unbalance is more than %50 after the device inverter, the leakage maintainer will definitely jump.

Here are a few ways to do it:

Method 1: There will generally be an adjuster on the leakage maintainer, and the regulator can be adjusted to a larger size.

Method 2: Replace the leakage maintainer with a special leakage maintainer for the inverter, and there are special leakage maintainers for the inverter sold on the market.

Method 3: Increase the load of the equipment, that is, the load of the motor, and the leakage current of the inverter will not be very large when it is started.

Method 4: Short the leakage maintainer.
More on that
Calculation method of filter capacitance value of inverter Calculation method of filter capacitance value of inverter

Alternating current can be converted into direct current using rectifier electricity, but in three-phase electricity, this DC voltage or current contains voltage or current ripple with a frequency of six times the frequency of the power supply. In addition, the inverter inverter will also generate ripple voltage or current due to output and carrier frequency, etc., and reverse ...

Introduction of plc inverter - LS power generation Introduction of plc inverter - LS power generation

Because the imported products of the inverter brand have their own PLC function, they mainly play an important role in the control effect of mechanical equipment, and play an important role in the equipment, which can regulate the operation and control of the machine and meet the requirements of users. It should be scale pLC ...

Selection principles and key points of AC contactors for power production Selection principles and key points of AC contactors for power production

1. The coil voltage of the contactor should generally be lower, so that the insulation requirements of the contactor can be reduced, and it is safer to use. However, in order to facilitate and reduce the equipment, it is often selected according to the actual grid voltage. 2. The operating frequency of the motor is not high, such as compressor, water pump, air ...

A common fatal form of failure of the terminal block - LS power generation A common fatal form of failure of the terminal block - LS power generation

1. Poor touch The metal conductor inside the terminal block is the core part of the terminal, which transmits the voltage, current or signal from the external wire or cable to the touch piece corresponding to the connector it matches. Therefore, it is necessary for the touch parts to have excellent structure, stable and reliable touch firmness.

An internal component of LS's power circuit breaker An internal component of LS's power circuit breaker

1. Auxiliary contact: the contact mechanically linked with the main circuit of the circuit breaker and the closing mechanism is mainly used for the display of the circuit breaker and the closing status, and is connected to the control circuit of the circuit breaker through the opening and closing of the circuit breaker to control or interlock its related electrical appliances. For example, output to signal lights, relays, etc.

LS produces common sense of electroplastic case circuit breaker LS produces common sense of electroplastic case circuit breaker

(1) Tripping LS electric molded case circuit breaker basically involves the tripping unit in the process of practical application, and the tripping is generally a thermomagnetic tripping or electronic tripping, and we must also understand this different tripping method in advance. In practice the application ...

The basic problem of LS electric molded case circuit breaker The basic problem of LS electric molded case circuit breaker

Rated current of LS molded case circuit breaker: Now in the process of using the molded case circuit breaker, it is necessary to understand the rated current of the molded case circuit breaker, and the rated current of the molded case circuit breaker is generally more than a dozen, mainly 16A...

Safety precautions for LS inverters Safety precautions for LS inverters

1. When the power supply is now powered or the inverter is in operation, do not open the shell of the inverter. Otherwise, an electric shock may occur. 2. When the front cover of the inverter is opened, do not run the inverter. Otherwise, you may be subjected to ...

A brief description of the K120S series plc A brief description of the K120S series plc

K120S series PLC product is a unit PLC product introduced to the market by LS in 2004, which has laid a solid foundation in the low-end small machinery supporting industry with its high-performance price ratio. Relying on some special functions of the product, it has also won some industry praise. ...

Inverter load test run step - LS power generation Inverter load test run step - LS power generation

1. Manually operate the work stop button of the inverter panel, investigate the work stop process of the motor and the display window of the inverter to see if there is any abnormal phenomenon. 2. If the inverter presents an overcurrent maintenance action during the process of starting P to abort the motor, ...

Selection of the color of the conductor of the high and low voltage switchgear - LS power production Selection of the color of the conductor of the high and low voltage switchgear - LS power production

1 AC three-phase circuit a) Yellow for phase A, green for phase B, and red for phase C; b) Light and blue colors for the neutral line or neutral line; C) Yellow and green two-color wires are used for safety grounding wires. 2 AC circuits connected by twinax wires or stranded wires: red, black ...

The inverter reads the rated data method - LS power generation The inverter reads the rated data method - LS power generation

The technical parameters of the inverter (Variable-frequency Drive, VFD) are divided into the input side and the output side. The technical parameters of the input side of the VFD include input voltage, number of phases and frequency; Output-side technical parameters include additional output voltage, additional current, additional capacity, capacity, frequency accuracy, etc.

The size of the contactor is selected by the type of contactor - LS produces electricity The size of the contactor is selected by the type of contactor - LS produces electricity

1. Select the corresponding category of contactor according to the control object, operation times and application category of the contactor. 2. Select according to the rated voltage of the line at the application location. 3. Select the rated current of the main contact of the contactor according to the load capacity. 4. About the voltage level of the lead coil ...

What are the determinants of the performance of LS inverters? What are the determinants of the performance of LS inverters?

The quality of the control circuit determines the function of the LS inverter. The function of the DC central circuit is to smooth the output of the rectifier circuit to ensure that the inverter circuit and the control power supply can obtain a high-quality DC power supply. When the whole ...

Why can't the inverter be equipped with a leakage protector - power generation Why can't the inverter be equipped with a leakage protector - power generation

When using an inverter, a leakage maintainer must not be used. This is a major principle of the use of frequency converters. Some users choose the corresponding leakage maintainer for the inverter when using the inverter. *The result is: the inverter moves together ...

Fault solution for three-phase asynchronous motor - LS power generation Fault solution for three-phase asynchronous motor - LS power generation

1. The motor cannot roll after being energized, but there is no abnormal noise, no peculiar smell and smoke. 1. Cause of the problem: (1) The power supply is not connected (at least two phases are not connected); (2) Fuse blowing (at least two-phase blowing); (3) The overcurrent relay is adjusted too small; (4) The wiring of the control equipment is faulty. 2. Question ...

Analysis of common faults of LS AC contactors Analysis of common faults of LS AC contactors

AC contactor is generally used to turn on or off the power supply in the control circuit of electromechanical equipment, it can frequently turn on or off the AC circuit, and can realize long-distance control. The toucher is mainly composed of a contact system and an electromagnetic system, and the problem of AC contactor is generally generated in the coil.

Inverter applications and common loads – LS generates electricity Inverter applications and common loads – LS generates electricity

1. Air conditioning load Office buildings, shopping malls and some supermarkets and factories have central air conditioning, and the electricity consumption of air conditioning is very large during the peak electricity consumption in summer. In hot weather, the electricity consumption of air conditioners in Beijing, Shanghai and Shenzhen accounts for more than 40% of peak electricity. Therefore, with inverter equipment, drag the air conditioning system ...

PLC installation and wiring skills - LS power generation PLC installation and wiring skills - LS power generation

The PLC should be kept away from strong disturbance sources such as electric welding machines, high-power silicon rectifier equipment and large-scale power equipment, and cannot be installed in the same switch cabinet as high-voltage electrical appliances. Power cables, control cables, and PLC power cables and I/O cables should be separated from the wiring ...

LS power generation installs the switching power supply step LS power generation installs the switching power supply step

The basic method of switching the power supply of the device requires us to carry out the corresponding installation and debugging according to the specific model and the device environment. And in the process of installation, we need to pay more attention to safety and stability to ensure the normal operation of the switching power supply. ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top