After the inverter is installed, disconnect the output of the inverter, use the diode file of the digital meter to measure the input and output of the inverter before powering on to ensure that there is no short circuit, and then turn on the working power supply of the inverter, (pay attention to whether the working power supply voltage calibrated by the inverter is consistent with the external input voltage), and confirm whether the factory settings and working conditions of the parameters are in accordance with the conditions, such as the rated frequency of the motor, the input voltage, the type of analog input/output signal, etc., if these signals are consistent with the working conditions, These parameters can be left unset and left at the factory.
There are some parameters that need to be preset before commissioning, such as: external terminal operation, analog operation, substrate frequency, *high frequency, upper frequency, lower limit frequency, start-up time, braking time (and mode), thermal electronic protection, over-current protection, carrier frequency, stall protection and over-voltage protection, etc.
There are also some parameters that are adjusted according to the operation during the debugging process, such as working frequency, acceleration time, deceleration time, 1-stage speed, 2-stage speed, 3-stage speed, analog output ratio adjustment, etc.
After the inverter is set, connect the motor, start the motor, given the speed, it should operate normally, pay attention to whether the DC bus voltage, the output current of the inverter, torque, power and other data are normal.
|
More on that
|
Delta's Amplon N series UPS ensures the safety of electricity consumption in pharmaceutical production lines
In recent years, in response to the development trend of automation, informatization and intelligence, pharmaceutical companies have continuously innovated, transformed and upgraded, selected fully automated intelligent production lines, accelerated the upgrading of equipment in the pharmaceutical industry, and completed the use of smart pharmaceutical technology for green, safe, high-quality and low-consumption development in the pharmaceutical industry.
|
|
The function in the process of using the inverter cabinet - Delta
Inverter cabinet is an industrial control equipment that can be widely used in fire fighting, daily constant pressure water supply and drainage, agricultural sprinkler irrigation pipe network pressurization, urban music fountain active water supply control, HVAC cold and hot water circulation control and other occasions. In addition, it also has a variety of maintenance functions such as: short circuit, overload, phase loss, etc.
|
|
Delta-B series inverter inverter output module is damaged and the drive circuit is damaged
Delta-B series inverter inverter output module is damaged and the drive circuit is seriously damaged: the drive integrated circuit T250V or burst, or the output terminal and the power supply ground are short-circuited, the filter capacitor is sprayed, the regulator tube is broken down or open, the resistance is open or the resistance value increases, and the circuit board carbonization is damaged.
|
|
Delta's inverter process setting
1. Restore the inverter to factory settings, press the "ENTER" button to enter the parameter setting interface, and press it continuously until it is 00-00 and then stop. Press the number up button to change to 00-02. Press the "ENTER" key again, the panel value will show 0, press the number up key to change it to 9. Press the "ENTER" key, break ...
|
|
Delta servo system composition
The servo system is mainly composed of a servo controller, a drive circuit, a servo motor and the corresponding reaction testing equipment.
(1) Servo motor
Servo motor refers to the motor that controls the mechanical components in the servo system, and the servo motor has an encoder inside, which can respond to the movement in real time.
|
|
Far EasTone telecommunications, delta and Microsoft jointly work together to build a 5g intelligent factory
Far EasTone Telecommunications, Delta Electronics, and Microsoft Corporation in Taiwan, China, announced today 8 that the three parties will work together to build a 5G smart workshop. With the characteristics of "big things" (network big data, artificial intelligence technology, Internet of Things technology), combined with 5G80MHz continuous network bandwidth, the integration of servo independent innovation and intelligence ...
|
|
Introduction to the inverter selection strategy - Delta inverter
1. Ability to adapt to the environment
1.1 Ability to adapt to grid voltage fluctuations
When the motor on the bus starts in a group, when the largest motor unit on the bus starts, the influence on the operation of the inverter, which is related to the input voltage fluctuation range parameters promised by the inverter.
|
|
Precautions for inverter selection - Delta
The selection of the inverter is mainly determined by the load characteristics of the drive and the actual working current of the motor, in addition to the following precautions:
1. The environment is suitable for some high temperature (higher than 50 degrees) and high altitude (higher than 1000 meters).
|
|
Detection methods for Delta circuit breakers, AC contactors and frequency converters
1. Circuit breaker
A circuit breaker is a device that can be manually or automatically controlled, and is used to control the on/off of the system power supply in the equipment circuit system. When there is a suspicion that there is a defect in the electrical system of the equipment, the primary functional part of the power supply should be checked.
Under normal circumstances, when in the ON state, the input input ...
|
|
Inverter power-on panel without display fault analysis - Delta
In the inverter problem, it is often encountered that the energized panel does not appear. Generally speaking, the problem of the inverter panel not showing up is usually caused by three parts, one is the poor contact of the contactor, the second is the control panel of the inverter, and the third is the damage of the power module that supplies power to the control panel.
|
|
Correct use of Delta inverter in operation
(1) When the speed of the motor is controlled by the Delta inverter, the noise and temperature rise of the motor are higher than that of the frequency of the motor. When the motor is running at low speed, because the speed of the motor blades is low, the temperature rise of the motor becomes high.
|
|
Misunderstandings in the application of Delta inverters
The capacity selection of the inverter is based on the rated power of the motor
Myth: The capacity selection of the inverter is based on the rated power of the motor
Compared with the electric motor, the price of the inverter governor is more expensive, so it is important to ensure that the ...
|
|
The reason for the slow response after the frequency converter potentiometer adjusts the frequency - Delta
The external use resistor is an external operation form of the inverter, which controls the inverter through the external operation signal generated by the external starting switch and frequency setting potentiometer. The regular external voltage signal of different inverters is different.
...
|
|
In 2020, Delta once again won the Outstanding Human Resource Optimization Award
Not long ago, Delta was awarded the "2020 Excellence Award for Optimal Allocation of Human Resources Resources" by the Human Resource Management Service Project Organization "Future", which stood out from more than 5,000 companies. This is also the second time since 2018 that Delta has won this honor. Delta ...
|
|
The difference between a general-purpose inverter and a vector inverter - Delta
There are two main differences between vector inverter and general inverter, the first is high control accuracy, and the other is high output torque at low speed. It can output 150%-200% of the rated torque. It should be vector frequency conversion is to decompose the motor current into D-axis current and Q-axis current, where D-axis current is excitation current ...
|
|
How to use Delta's inverter operation
(1) When the speed of the motor is controlled by the Delta inverter, the noise and temperature rise of the motor are higher than that of the frequency of the motor. When the motor is running at low speed, because the speed of the motor blades is low, the temperature rise of the motor becomes high.
|
|
Delta's PLC-Based motion controller AX3 series
With the development of electronic semiconductor information technology, technologies such as the Internet of Things, big data, and cloud platforms are showing a trend of hundreds of schools of thought, which also drives the rapid development of intelligent production. Intelligent production also puts forward new requirements for controllers: high speed, large capacity, miniaturization, networking...... In order to ...
|
|
Delta's PLC-Based motion controller AX3 series
With the development of electronic semiconductor information technology, technologies such as the Internet of Things, big data, and cloud channels are showing a trend of a hundred flowers blooming, which also drives the rapid development of intelligent production. Intelligent production also puts forward new requirements for controllers: high speed, large capacity, miniaturization, networking...... In order to ...
|
|
How to use a PC to control Delta's inverter
The communication interface of Delta's inverter is to use RS485 to cooperate with the ModBus communication format commonly used in the general industry for material handing, so as long as the general ModBus software is used, the PC can be used to read and write the materials of the drive.
Furthermore...
|
|
Basic parameter setting of special inverter for wind turbine - Delta
1. Control mode:
i.e. speed control, torque control, PID control or other methods. After the control method is adopted, static or dynamic identification should generally be carried out according to the control accuracy.
2. Minimum operating frequency:
That is, the minimum speed of the motor. When the motor is working at low speed, the ...
|
|