The reason for the slow response after the frequency converter potentiometer adjusts the frequency - Delta

Create Date: 2024-8-30 12:03:23|Source: Delta/Delta

The external use resistor is an external operation form of the inverter, which controls the inverter through the external operation signal generated by the external starting switch and frequency setting potentiometer. The regular external voltage signal of different inverters is different.

                               The reason for the slow response after the frequency converter potentiometer adjusts the frequency - Delta

We commonly have the following external given voltage standards: one is 0vS+10v, the second is 0vs±10v, the third is 0Vs±5V, and the fourth is 0vs+5v. In addition, there is a kind of current given signal, which is generally 4mAs20mA. The advantage of this method is that it is highly resistant to interference, and it is best to use this method when the control interval is far away.

It is a given signal with an external voltage. The phenomena in the presented questions are generally formed by the following conditions. In line with the analysis of the idea of eliminating faults according to maintenance, we will take the principle of easy first and then difficult. The first point is to look at the parameters set by the inverter, for example, in the combined form, if the external potentiometer is used to adjust the operating frequency, the acceleration time parameter Pr7 should be set according to the control requirements, and the time should not be too long. Taking the inverter FR-A540 as an example, its acceleration time scale can be set up to 05999s.

The second point, the first choice to suspect the problem of the potentiometer, first look at the potentiometer is not matched, because we know that the selection of external potentiometer is very critical, generally in the purchase of the inverter its clarification book on the external electrical cathometer Yin value and power wattage have clear rules, here I want to say more, in the selection of potentiometers to do the following aspects, one is the best potentiometer resistance value to choose the large resistance value, not to the small resistance value; Second, because the potentiometer needs to be frequently adjusted in ordinary work, the wear resistance of the internal contacts should be considered, and the wattage of the potentiometer is not small.

Generally, it is selected according to the practical power consumption of more than 10 times. For example, if the power supply voltage is 10V and the negative value of the potentiometer is 2,000 ohms, then the nominal power of the potentiometer should be more than 1/2W. If the potentiometer used does not match the one on the clarification, the above situation will occur; If the potentiometer standard is consistent, if this situation is presented, the potential should be checked whether there is a problem, first power off with a multimeter to check whether the resistance between the 3 terminals and 2 terminals of the potentiometer is smooth, and then measure the resistance between the 2 terminals and 1 terminal, the positive value is normal, then power on the inverter, and then use the DC 50V gear to measure the voltage to see whether the terminal voltage of the potentiometer is normal.

The third point, if the above is not a problem, it is necessary to consider the problem of the internal circuit of the inverter, at this time, it is necessary to check whether there is a problem with the input and output circuit of the inverter, because there is a problem with the working board, this phenomenon will also be formed!

More on that
Delta NT series UPS industrial power supply Delta NT series UPS industrial power supply

Delta's NT series UPS is a high-power UPS carefully discussed by experts for large-scale users, and a number of advanced skills have been selected, which can be used for various data processing systems, telecommunications systems, satellite systems, network systems, medical equipment, safety and emergency escape equipment, monitoring and security systems, and various industrial systems.

Precautions for long-term idle use of Delta inverter Precautions for long-term idle use of Delta inverter

If the inverter is to run the equipment again after being shelved for more than half a year, the probability of damage may be greatly increased due to many factors such as the placement environment, the service life of the inverter, and the load rate, and the failure usually presents the following problems: 1. After the equipment is powered on, it becomes ...

The output of the inverter is not short-connected to the power frequency The output of the inverter is not short-connected to the power frequency

1. To switch the motor of the power frequency, the parking method is set to free parking, and it is important not to park softly 2. Intercept the contactor of the motor from the output end of the inverter, and the control stop button and the inverter parking button are the same composite button, that is, when the inverter is pressed, the inverter parking will be followed by the contactor line.

Description of Delta inverter problems and solutions Description of Delta inverter problems and solutions

Problem Description: What is stall avoidance? Solution(s): If the given acceleration and deceleration time is too short, the output frequency of the inverter changes faster than the motor speed, and the inverter will stop working due to overcurrent, which is called stalling. In order to make the motor ...

Rated current design of inverter leakage circuit breaker - Delta Rated current design of inverter leakage circuit breaker - Delta

1. Install AC reactor and DC reactor. When the capacity of the inverter is greater than 500kva in the distribution transformer, and the transformer capacity is more than 10 times the capacity of the inverter, an AC reactor is installed on the input side of the inverter. And when the output voltage of the distribution transformer is unbalanced and uneven in three phases ...

The principle structure of low-voltage circuit breaker - Delta The principle structure of low-voltage circuit breaker - Delta

Low-voltage circuit breakers, commonly known as active air switches, are one of the primary electrical switches in low-voltage distribution networks. It can not only turn on and off normal load current, motor operation current and overload current, but also turn on and off short circuit current. It is mainly used as a low-voltage distribution line or a switch cabinet that is not often operated ( ...

Delta's soft starter component role Delta's soft starter component role

The soft starter is a device used to control the start and stop of the motor, which is composed of a number of components, including the soft starter controller, the soft starter conditioner, the soft starter power supply, the soft starter input and output module, the soft starter interface module, etc. ...

Delta's inverter is powered on and commissioned Delta's inverter is powered on and commissioned

After the installation of the Delta inverter is completed, disconnect the output of the inverter, use the diode file of the digital meter to measure the input and output of the inverter before the power is not turned on to ensure that there is no short circuit, and then turn on the operating power supply of the inverter.

Common problems of VFD control motors - Delta Common problems of VFD control motors - Delta

Question 1. Why use a VFD to control the motor? Speaking of this question, let's first take a brief look at these two devices. The motor is a rational load, which hinders the change of current, and a large change in current will occur when it is started. VFD, which is actually made up of a rectifier inverter circuit, ...

Cause of Servo Motor Failure – Delta Cause of Servo Motor Failure – Delta

1. The motor is broken shaft 1. The cause of the problem (1) Unreasonable mechanical design leads to excessive radial load force; (2) The load end is stuck or severely overloaded; (3) The motor and reducer are not centered when installed. 2. Eliminate problems (1) Check the ...

The energy-saving principle of inverter - Delta The energy-saving principle of inverter - Delta

In order to ensure the reliability of production, all kinds of production machinery are designed with power drive, and there is a certain surplus when designing and matching power drive. When the motor cannot operate at full load, in addition to reaching the power drive requirements, the residual torque increases ...

Introduction to Delta's DVPSCM52-SL communication module Introduction to Delta's DVPSCM52-SL communication module

Recently, Delta Group has made a big hit in the field of building automation with the launch of the DVPSCM52-SL, a slave communication module that supports BACnet MS/TP (Building Automation Control Network Communication Protocol). Building automation system is an indispensable part of intelligent building.

Delta's inverter is automatically changed to manual setting Delta's inverter is automatically changed to manual setting

The converter is capable of manual and active switching: 1. The switching between the manual operating system and the DCS operating system is done by the transfer switch SA installed on the field operation tower, which has active, manual and ...

Common knowledge points of Delta inverters Common knowledge points of Delta inverters

1. How to set the acceleration and deceleration time of Delta inverter? Solution(s): The acceleration time of Delta's inverter is the time it takes for the driver to accelerate from 0.0Hz to "high operating frequency". Deceleration time refers to the deceleration time required for the inverter to decelerate from "high operating frequency" to 0.00Hz.

Precautions for long-term idle use of Delta inverter Precautions for long-term idle use of Delta inverter

If the inverter is to run the equipment again after being shelved for more than half a year, the probability of damage may be greatly increased due to many factors such as the placement environment, the service life of the inverter, and the load rate, and the failure usually presents the following problems: ...

When the Delta inverter is powered on, the uptube drive voltage is established When the Delta inverter is powered on, the uptube drive voltage is established

One is hardware, similar to the CPU reset circuit, which gives the downtube a short high-level drive pulse during the initial power-up, and then the voltage drops to 0 to cut off the downtube. The second is the software, when the CPU is operating normally, it outputs a square wave pulse that only needs to be turned on by the lower three tubes, so that the upper tube ...

Precautions for transportation, installation and storage – Delta Precautions for transportation, installation and storage – Delta

1) When taking out or placing the servo motor, it is not possible to only pull the wire and drag the motor or only hold the rotating shaft core. 2) Do not hit the shaft directly, e.g. by tapping or hammering, as this may cause damage to the shaft and the encoder attached to the opposite side of the shaft. 3) Give the shaft core ...

The reason for the low voltage trip of the inverter - Delta The reason for the low voltage trip of the inverter - Delta

The low voltage of the inverter mainly refers to the low voltage of the central DC circuit, and the reasons for the low voltage of the central DC circuit generally come from two aspects: ​ (1) Low voltage from the input side of the power supply The power supply under normal conditions ...

DC motor speed regulation method - Delta DC motor speed regulation method - Delta

There are three speed regulation methods for DC motors: armature loop string resistance, armature voltage regulation and speed regulation, and weak magnetic field speed regulation. The three speed regulation methods can achieve stepless speed regulation. 1. Armature loop string resistance The applied resistor is connected to the armature circuit.

Delta launched the MZM, a high-power positional drive system Delta launched the MZM, a high-power positional drive system

Driven by consumption promotion and product diversification, the manufacturing industry's demand for automation and intelligent promotion in production and processing is also increasing. In the production process, the processing of "large and heavy" items is often difficult to control accurately, and the deviation of orientation is not as easy as that of "small" items. To this end ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top