Misunderstandings in the application of Delta inverters

Create Date: 2024-8-30 12:03:23|Source: Delta/Delta

The capacity selection of the inverter is based on the rated power of the motor

                                  Misunderstandings in the application of Delta inverters

Myth: The capacity selection of the inverter is based on the rated power of the motor

Compared with the motor, the price of the variable frequency governor is more expensive, so it is very meaningful to reasonably reduce the capacity of the variable frequency governor under the premise of ensuring safe and reliable operation.

The power of the inverter governor refers to the power of the 4-pole AC asynchronous motor to which it is applicable.

Due to the same capacity motor, its number of poles is different, and the rated current of the motor is different. With the increase of the number of poles of the motor, the rated current of the motor increases. The capacity selection of the inverter governor cannot be based on the rated power of the motor. At the same time, for the original transformation project that does not use the frequency converter, the capacity selection of the frequency converter cannot be based on the rated current of the motor. This is because the capacity selection of the motor should consider factors such as large load, affluence coefficient, motor specifications, etc., and the amount of affluence is often large, and the industrial motor often operates at 50%-60% of the rated load. If the capacity of the inverter governor is selected based on the rated current of the motor, the amount of wealth is too large, resulting in economic waste, and the reliability is not improved.

For the squirrel cage motor, the capacity selection of the frequency converter should be based on the principle that the rated current of the frequency converter is greater than or equal to 1.1 times of the maximum normal working current of the motor, so as to save money to the greatest extent. For heavy-duty starting, high-temperature environments, winding motors, synchronous motors, etc., the capacity of the frequency conversion governor should be appropriately increased.

For designs that use inverters from the start, it is understandable that the selection of inverter capacity is based on the rated current of the motor. This is because the inverter capacity cannot be selected based on actual operating conditions. Of course, in order to reduce investment, in some cases, you can also determine the capacity of the inverter first, and wait for the actual operation of the equipment for a period of time, and then choose according to the actual current.

More on that
The key point to pay attention to when choosing a UPS power supply - Delta The key point to pay attention to when choosing a UPS power supply - Delta

(1) About the synchronous switching function. Now, in addition to the off-line UPS power supply with an additional output power of less than 500VA, the off-line UPS power supply with square wave output is still selected for conversion control without mains synchronization function, and all UPS power supplies with an output power of 1KVA and above are performing the conversion operation of mains power supply to inverter power supply.

Solution to Delta inverter fault CE1 and CE2 Solution to Delta inverter fault CE1 and CE2

Product range: CP/CH/CT/C2000/C200/MS300/MH300/VE/ED/VJ Problem Code: CE1 Problem Description: Communication is abnormal Solution: 1. Communication error: RS-485 Modbus function code may be faulty ...

Precautions for cleaning dust in the inverter - Delta Precautions for cleaning dust in the inverter - Delta

1. Each VFD should be cleaned and protected once a quarter. Protecting and cleaning equipment must have specific records and the signature of the person in charge. As long as the management is in place, the task can be completed with quality and quantity; 2. Before cleaning, the power supply must be blocked, and the voltage must be reduced to a safe voltage before starting to work. ...

Precautions for long-term idle use of Delta inverter Precautions for long-term idle use of Delta inverter

If the inverter is to run the equipment again after being shelved for more than half a year, the probability of damage may be greatly increased due to many factors such as the placement environment, the service life of the inverter, and the load rate, and the failure usually presents the following problems: ...

Problems in the inverter application – Delta inverters Problems in the inverter application – Delta inverters

1. Harmonic problems The equipment that plays the role of switching in the main circuit of the inverter must generate harmonics in the process of turning on and off the circuit. The lower harmonics generally have a greater impact on the motor load and cause torque ripple; The higher harmonics increase the leakage current of the inverter's output cable, making ...

The difference between a general-purpose inverter and a vector inverter - Delta The difference between a general-purpose inverter and a vector inverter - Delta

There are two main differences between vector inverter and general inverter, the first is high control accuracy, and the other is high output torque at low speed. It can output 150%-200% of the rated torque. It should be vector frequency conversion is to decompose the motor current into D-axis current and Q-axis current, where D-axis current is excitation current ...

Delta's inverter external positive and reverse operation mode Delta's inverter external positive and reverse operation mode

1. The external control panel is rotated and operated After selecting the upper or lower button on the panel, the Frd inverter will rotate forward if you select the inverter, and the rEu inverter will rotate 2. The external control terminal is rotated Access via external terminals ...

Delta inverter braking resistor selection Delta inverter braking resistor selection

1. The necessity of braking resistance If the regenerative energy that occurs during deceleration and descent in the application is too large, there is a possibility that the voltage of the main circuit inside the inverter will rise, causing damage. Due to the built-in overvoltage maintenance function in the inverter, the overvoltage of the main circuit (O ...

Problems in the use of Delta inverters and Delta motors Problems in the use of Delta inverters and Delta motors

Delta's motors are the most frequently used rotating things so far, and with the development and spread of Delta inverters, they need to be used in conjunction with inverters. However, in the process of combining inverters and motors, it is inevitable to encounter a lot of ...

Inverter application for heat dissipation to solve the precautions - Delta Inverter application for heat dissipation to solve the precautions - Delta

The transformer DC resistance tester uses the 32-bit ARM core as the core of processing, controls the whole machine, and automatically completes the functions of self-calibration, current stabilization judgment, data processing, resistance value display, etc., and can measure the DC resistance of various types of transformers and transformers. ...

Delta's inverter product recommendation Delta's inverter product recommendation

Delta was established in 1971 to provide power supply and heat dissipation treatment programs for the world. Over the past 20 years, Delta's development in Chinese mainland has become increasingly deep-rooted, and its business operations cover development, production, sales and service. With innovative skills, we will continue to strengthen engineering research and development equipment and sophisticated testing ...

Delta's servo drive ASDA-B2-F motion control alarm Delta's servo drive ASDA-B2-F motion control alarm

Abnormal alarm indication Abnormal alarm title Abnormal alarm action content Sweeping method Indicate DO servo status Switch AL111 DMCNET Packet Receive Overfill Rx Buffer Overfill (more than two DMCNET packets received within 1 millisecond) ALM ON AL185 DMCNET Bus Hardware ...

Delta UPS power supply RT5K extension configuration method for 2 hours Delta UPS power supply RT5K extension configuration method for 2 hours

Engined DC: 1K=36V, 2K=72V, 3K=96V, 5K, 6K, 10K=192V UPS power supply accounting formula: 1KVA (volt-ampere) =700W (watt) =1000VA (volt) UPS power supply x extended time + starting DC = how big the battery is Start DC + V number of battery = how much power is distributed ...

The robot reducer accessories are faulty The robot reducer accessories are faulty

Robot harmonic reducer is a kind of power transmission organization, which uses the speed converter of the gear to reduce the number of revolutions of the motor (motor) to the required number of revolutions, and obtains a larger torque organization. The scale of use of the reducer is quite extensive, if the noise of the reducer is too loud, it will hinder people ...

Touch screen controls the inverter step – Delta Touch screen controls the inverter step – Delta

1. The touch screen is controlled by PLC inverter 1. At present, the general control of the inverter needs to choose PLC to communicate with the inverter, read the information of the inverter, and then the touch screen communicates with the PLC to complete the control of the inverter to start, stop, and monitor the operation of the inverter.

Servo motor speed improvement method - Delta Servo motor speed improvement method - Delta

When many engineers debug servo motors, they often have such a problem: why is my servo motor so slow, how can I improve the speed, and how much can the maximum speed reach? The basis for the confirmation of the speed method of the servo motor: the speed of the servo motor. ...

Introduction to Delta's PLC maintenance knowledge Introduction to Delta's PLC maintenance knowledge

1. Delta's PLC power on running light does not light up, and the ERROR flashes, the reason may be: no program 2. Delta's PLC cannot communicate with the computer, which may be: RS23 port is broken 3. Delta's PLC power light does not light up: The power supply is bad ...

The impact of inverter cable design on the life of motor cables The impact of inverter cable design on the life of motor cables

Reflected waves that affect the impedance mismatch between the cable and the motor are pervasive in all AC VFD applications. The severity of the problem depends on the length of the cable, the rise time of the PWM (Pulse Width Modulation) carrier, the voltage of the VFD, and the magnitude of the impedance difference between the motor and the cable. ...

Delta's inverter is powered on and commissioned Delta's inverter is powered on and commissioned

After the installation of the Delta inverter is completed, disconnect the output of the inverter, use the diode file of the digital meter to measure the input and output of the inverter before the power is not turned on to ensure that there is no short circuit, and then turn on the operating power supply of the inverter.

Delta was awarded an "A" rating as a "Supply Chain Engagement Leader." Delta was awarded an "A" rating as a "Supply Chain Engagement Leader."

On February 10, CDP released its 2021 Supplier Engagement Rating; SER) As a result, Delta received the highest scores in key scoring items such as "Supply Chain Participation" (Note 1) and "Three Emissions in the Greenhouse Gas Field" (Note 2).

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top