1. Heating for a period of time, the temperature does not change. The ambient temperature of the site (e.g. room temperature 25°C) is displayed at all times.
In case of such a fault, first check whether the SV value setting value is set, whether the 0UT indicator light of the meter is lit, and whether the No. 3 and No. 4 terminals of the meter are 12VDC output with the "multimeter". If the light is on, terminals 3 and 4 also have a 12VDC output. This indicates that the problem is with the control device of the heating element (e.g.; AC contactors, solid-state relays, relays, etc.), check whether the control device has an open circuit, whether the device specification is wrong (such as a 380V device connected to a 220 circuit), and whether the circuit is connected to the wrong one. Also, check the sensor for a short circuit (the meter always shows room temperature when the thermocouple is shorted).
2. After heating for a period of time, the temperature display is getting lower and lower.
In case of such faults, the positive and negative polarity of the sensor is generally reversed, and the input terminal wiring of the instrument sensor should be checked (thermocouple: 8 to the positive pole, 9 to the negative pole: PT100 thermal resistance: 8 to the monochrome wire, 9 and 10 to the two wires of the same color).
3. After heating for a period of time, the temperature value (PV value) measured by the instrument is very different from the actual temperature of the heating element (for example, the actual temperature of the heating element is 200°C, while the meter shows 230°C or 180°C).
In case of this type of fault, first check whether there is any loose contact between the contact point between the deep temperature head and the heating element, whether the temperature measurement point is selected correctly, and whether the specification selection of the temperature sensor is consistent with the input specification of the temperature controller (for example, the temperature control meter is a K-type thermocouple input, and the J-type thermocouple is installed on site to measure the temperature).
4. The PV window of the temperature control instrument displays HHH or LLL characters.
If this type of fault is encountered, it means that the signal measured by the meter is abnormal (LL is displayed when the measurement temperature of the meter is lower than -19°C, and HHH is displayed when the measurement temperature is higher than 849C). Solution: If the temperature sensor is a thermocouple, you can remove the sensor, directly use the wire to short the thermocouple input terminals (8 and 9 terminals) of the instrument, after powering on, if the instrument can display the room temperature normally (on-site ambient temperature such as: 30 °C), then the problem lies in the temperature sensor, use a multimeter tool to detect whether the temperature sensor (thermocouple or PT100 thermal resistance) has an open circuit (broken wire), whether the sensor wire is reversed, wrong, or the specifications of the sensor are inconsistent with the instrument.
If all of the above problems are ruled out, the internal temperature measurement circuit of the meter may be burned due to leakage of the sensor.
5. The control is out of control, the temperature exceeds the set value, and the temperature has been rising.
In case of such a fault, first check whether the 0UT indicator light of the meter is lit at this time, and whether the No. 3 and No. 4 terminals of the meter with the DC voltage level of the "multimeter" have 12VDC output. If the lights are not on, there is no 12VDC output at terminals 3 and 4. This indicates that the problem is with the control device of the heating element (e.g.; AC contactors, solid state relays, relays, etc.).
Solution: Check whether the control device has a short circuit, the contact cannot be opened, and the wrong line is connected in real time.
|
More on that
|
RLC thermostat - introduction to the performance characteristics of intelligent digital display controller
1. The special integrated instrument chip has more reliable anti-interference and stability.
2. Signal input, which can be matched with commonly used thermal signals through menu settings.
3. The display range, transmission output range, alarm value and alarm mode can be modified online.
4. Soft ...
|
|
Parameter setting operation of RLC temperature control table CH402
Model: CH402FS01-8*HN (for PECVD temperature control)
1) Single press SET: SV can be set (set temperature manually)
2) Press and hold the SET button for 2 seconds, ALI=1000 (absolute alarm temperature setting) and then press the SET button, ATU=1 (self-defining, self-interpreting a set of PID parameters) to exit ...
|
|
RLC thermostat - temperature controller control method classification and working principle
1. The temperature controller control method is generally divided into two types:
One is controlled by the temperature change of the cooled object, and the vapor pressure temperature controller is mostly used, and the other is controlled by the temperature difference change of the cooled object, and the electronic temperature controller is mostly used.
...
|
|
RRC Thermostat – Instructions for use of smart thermostats
1. Turn on the power of the smart thermostat, and the current temperature is displayed on the display. Because the sensor is not in contact with other devices, but is exposed directly to the air, this is the current temperature: 31 degrees Celsius, which is not too hot.
2. At the bottom right of the display is the "Startup Temperature" setting.
|
|
RKC thermostat REX-C400 model settings and parameter instructions
Japan RIKA RKC REX-C400 temperature controller product introduction
REX-C400 Digital Thermostat RKC PID Temperature Controller Thermostat (SSR Output) + Type K Thermocouple + *Large 40A SSR Relay
1. Dual display set temperature and process temperature
2. General Digital Programmable Temperature ...
|
|
RLC Thermostat - Introduction to the function of mechanical temperature control
1. The temperature setting is set by the knob, which is convenient and intuitive 2. It can be directly installed on the standard junction box on the wall.
3. Beautiful appearance and reliable performance.
4. The switch adopts toggle type, which feels comfortable and has a long life.
5. It can control two-wire or three-wire electric (ball...
|
|
RHK thermostat – a rapid detection method for common air conditioner thermostats
1. Bellows or diaphragm air conditioner thermostat
1. Fault phenomenon: poor contact or burning, resulting in the circuit can not be connected; The frequent action of the contact arc and sticking causes the circuit to be unbreakable; The thermostat in the temperature sensing chamber leaks, causing the contact to fail to operate and lose control.
...
|
|
RK Level Gauge - Typical Fault Problems and Solutions of Pontoon Level Gauges
1. There is no liquid level display or lower liquid level display
When the sewage is discharged, only a small amount of condensate flows out, and it is judged that the pontoon is blocked.
Treatment: Dismantle the outer pontoon and find that the pontoon is almost filled with dirt and impurities. Clean, calibrate, and return to normal.
2. The liquid level display is ...
|
|
RKC thermostat – the correct way to adjust the thermostat
1. Set temperature: Press the SET button to set or view the temperature set point. Press the SET key digital tube character start flashing, indicating that the appearance has entered the setting state, press the △ key to increase the set value, press the ▽ key to decrease the set value, press and hold the △ key or ▽ key The data will change rapidly, press the SET key again The appearance will return ...
|
|
RKC thermostat - how to set the PID of the thermostat?
1. Setup (XMT201-D): Press the SET button for 3 seconds to enter the inner parameter setting state. E: This parameter is the advance of heating stop when P = 0, when P is not equal to 0, the instrument is the intelligent PID working mode, and when P is not equal to 0, the E parameter is meaningless.
2.P: is the proportional band, that is, the proportional ...
|
|
RKC converter - an introduction to the classification of converters
Analog-to-digital converters
The analog-to-digital converter comprises a first transmission circuit, which receives an input voltage and an output clock signal, which is phase-shifted, depending on the input voltage, and a second transmission circuit receives a reference voltage and an input clock signal, and outputs a reference clock signal, which ...
|
|
Precautions for the use of RKC thermostats
fold
When the RKC thermostat comes out, it is a single-loop regulator, that is, it only has a heating function, which is called the basic meter, which is generally sent to the agent, and the agent will expand the multi-channel adjustment and alarm output control function, which is called "changing the meter" in the industry, so as to ensure that there is very little hardware cost.
|
|
Analysis of common fault causes of RKC temperature controller
1. The power indication is normal, but the temperature controller has no screen display. Most of this fault is caused by the heating of the voltage regulator element (7805 or 7812) on the thermostat during long-term use, which causes the solder joint to show a breakpoint, and sometimes it is caused by the phenomenon of virtual soldering at the factory.
2. Temperature controller ...
|
|
RK Thermostat - Part of the LCD shows the status quo of floor heating thermostats
1) The LCD interface is too large or the display symbols are not proportional or standard.
2) The terminal blocks or circuits (components) that control the output cannot withstand large currents.
3) The cable of the external sensor (ground probe) is a thin and flexible wire, which cannot be inserted into the embedded pipe, and it is also a hidden danger for future maintenance.
...
|
|
RKC thermostat wiring needs to pay attention to
Wiring Notes:
1. For thermocouple input, the corresponding compensation wire should be used.
2. RTD input, 3 wires with low resistance and no difference should be used.
3. The input signal line should be far away from the power line of the instrument. Power supply and load lines to avoid noise interference.
...
|
|
RRKC thermostat wiring installation and some precautions
The rkc controller was developed by Japan and is mainly used in plastics and stoves. Of course, it is also widely used in China's industry, there are many people who do not know much about the rkc controller, and some even feel unfamiliar.
|
|
RHK thermostats – an introduction to the classification of displays
(1) Categorize by display color
1. Monochrome display
There are two types of displays: multi-grayscale monochrome display and VGA multi-frequency monochrome display. These displays are small, lightweight, clear and inexpensive, making them suitable for highly mobile workplaces.
2. Color ...
|
|
RKC Level Gauge – Precautions for the installation of float level gauges
1. The specific gravity of the liquid to be measured must be greater than the specific gravity of the float
2. The measured medium should not contain ferromagnetic impurities
3. The float level gauge should be installed in an unobstructed position when the float moves up and down
4. Magnets are not allowed to be close around the float level gauge, otherwise it will affect the float.
|
|
RLC thermostat – how to install the thermostat
1. In which room should the thermostat be installed?
It is very important to choose a reasonable location to install the thermostat, which will directly affect the work of the wall-hung furnace in your home, the main living room (living room) should be your best choice, you can also install the thermostat in the bedroom according to your personal needs.
|
|
RKC Level Gauges - Advantages and Disadvantages of Several Common Level Gauges Introduction
1. Float level gauge is an instrument that relies on the principle of buoyancy to measure the liquid level. Usually by means of a float in conjunction with a scale, the observer can visually read the height of the liquid level.
Advantages: fast and intuitive reading; Low price; Easy to install.
Shortcoming:...
|
|