RHK thermostat – a rapid detection method for common air conditioner thermostats

Create Date: 2024-8-30 12:03:23|Source: RKC

1. Bellows or diaphragm air conditioner thermostat

1. Fault phenomenon: poor contact or burning, resulting in the circuit can not be connected; The frequent action of the contact arc and sticking causes the circuit to be unbreakable; The thermostat in the temperature sensing chamber leaks, causing the contact to fail to operate and lose control.

Maintenance method: After turning the knob of the air conditioner thermostat in the forward and reverse directions several times, use the multimeter R×l file to measure the two terminals of the temperature controller in the connected state, if the resistance value is very small, indicating that the contact is normal; If the resistance is very large, it means that the contact contact is poor; If it doesn't, it may be a leak of the thermostat.

Whether there is leakage can be first visually inspected, observe whether the sealing welding head of the temperature sensing head is broken, whether the temperature sensing package is damaged and cracked, whether there are bending marks of the temperature sensing tube, etc., and then put the temperature sensing package in warm water of 30-40-C to test whether the contact is closed, if the contact is still not closed. indicates that the thermostat in the temperature sensor package has been leaked; If the contact can be closed, then take out the temperature sensing bag from the water, and the contact is disconnected after being placed in a low temperature environment for a period of time, indicating that the temperature adjustment range of the thermostat is improper, which can be corrected by adjusting the temperature range of the adjusting screw, turn L in the counterclockwise direction, and try again after 2 hiding.

2. Fault phenomenon: after the contact of the air conditioner thermostat is adhered due to ignition. The contacts cannot jump open automatically, and the compressor cannot be stopped.

Maintenance method: Put the temperature sensor bag in the refrigerator (5-lO°C) of the double-door refrigerator, and measure whether the two-wire terminals of the temperature controller are disconnected. If you don't keep opening. Indicates that the contact is adhesive, and the contact can be mechanically forced to break with a flat screwdriver; If the contact can be jumped open, the temperature control range of the thermostat drifts and is low, and the temperature control range adjustment screw can be adjusted clockwise.

3. Fault phenomenon: leakage of thermostat

Maintenance method: Use a hot towel to heat the temperature sensing tube, adjust the knob to the lowest temperature, and use a multimeter to measure whether the switch of the thermostat is turned on. If the switch doesn't work. This indicates that the thermostat has leaked, and the thermostat should be replaced with a new one.

2. Thermostat for hot and cold air conditioners

The thermostat used in electric air conditioners has two sets of contact mechanisms (cold contacts and hot contacts) in the contact control box, and the same temperature sensing bellows is used to control the heat and cold. Its fault phenomenon and inspection method are basically the same as those of ordinary thermostats, but it should be noted that it should also be checked whether the cold and hot switching actions are sensitive, that is, the compressor circuit should be connected when the refrigeration position is connected, and the electric heater circuit should be connected when the heating position is made.

3. Defrost air conditioner thermostat

The defrost temperature controller is an element installed in the control circuit of a thermal air conditioner specifically for switching the solenoid reversing valve.

Its thermostat is placed on the coil of the heat exchanger on the outdoor side. When heating in winter, the frost layer of the outdoor side heat exchanger thickens so that the temperature is lower than a certain set value. Contact action of the defrost controller.

Disconnect the solenoid directional valve. The original heating cycle is changed to a cooling cycle. There are two commonly used structural forms: one is the thermal bimetal sheet type: the other is the ordinary thermostat.

The method of detection is to place the temperature sensing part in water or air at the corresponding temperature. Use a multimeter to measure whether the two terminals are disconnected or on. You can know the good and the bad. Thermal bimetal thermostats are also used for indoor side cold air control.

Fourth, temperature sensing resistance

Electronic air-conditioning thermostats or microcomputer-controlled air-conditioners use thermistors as the temperature sensing element.

A thermistor is a component whose resistance changes significantly with temperature. Thermistor for ten vertical measurement of return air temperature of air conditioner. It generally has a negative temperature coefficient characteristic: the resistance value decreases with increasing temperature.

Specific to the thermistor used in a certain brand of abyss device, its resistance value changes with temperature is generally drawn into a chart in the random manual for testing, and the detection can be in a certain environment. Measurements are made with semiconductor thermometers and multimeters.

When the thermistor is aging and the performance drifts, that is, the correspondence between temperature and resistance value changes, a new thermistor sensor should be replaced.

Failures can occur when the system is not working properly or after a long period of aging. In the maintenance process, sometimes the replacement method is adopted, that is, a good thermostat of the same model and specification is replaced, which not only saves maintenance time, but also can easily identify the quality of the original thermostat.
RHK thermostat – a rapid detection method for common air conditioner thermostats

More on that
Causes and treatment methods of inverter overvoltage Causes and treatment methods of inverter overvoltage

 1. According to the theory of cutting off the overvoltage, when the transformer is cut off, the current in the transformer inductance cannot be abruptly changed, and the stored magnetic field energy forms a vibration between the excitation inductance of the transformer and the ground capacitor, and the overvoltage occurs. 2. Transformer ...

RLC Thermostat - Overview and characteristics of mechanical thermostats RLC Thermostat - Overview and characteristics of mechanical thermostats

Mechanical thermostats are suitable for indoor temperature control in industrial, commercial and residential buildings. The mechanical thermostat uses an inflatable diaphragm box to sense the temperature and compare it with the user's set temperature to automatically control the air conditioning equipment to achieve the purpose of indoor constant temperature. For commercial, industrial and civil construction, available ...

What are the common devices for RKC thermostats – digital displays? What are the common devices for RKC thermostats – digital displays?

In a variety of electronic control equipment, digital display has become an indispensable and important link. The electronic devices and corresponding driving circuits used for digital display are called digital displays. Commonly used digital displays include glow digital tube displays, fluorescent digital tube displays, projection ...

RLC thermostat – the working principle of an electronic temperature controller RLC thermostat – the working principle of an electronic temperature controller

Electronic temperature controller, as the name suggests, is a kind of controller that controls the temperature through electronic circuits, it is mainly used for temperature control of electric heating and plumbing, it is easy to learn in the operation method, and the accuracy of control is also very accurate.

RKC Level Gauge – How to properly use a plug-in float level gauge for level measurement RKC Level Gauge – How to properly use a plug-in float level gauge for level measurement

1. Select the appropriate level gauge First of all, it is necessary to choose the appropriate level gauge. The following factors should be taken into account in the selection of a level gauge: Measure the properties of the medium: e.g., temperature, pressure, viscosity, corrosiveness, etc. Measuring range: i.e. the height range of the liquid ...

What are the characteristics of RLC thermostats – mechanical thermostats? What are the characteristics of RLC thermostats – mechanical thermostats?

1. Used to control fan coil unit, electric valve, damper and other equipment; 2. The switch adopts toggle type, which feels comfortable and has a long life; 3. Set the temperature by twisting (the temperature range can be limited); 4. The thermostat can be installed directly on the wall or on the standard junction box; ...

RKC Level Gauge – Some installation requirements for pontoon level gauges RKC Level Gauge – Some installation requirements for pontoon level gauges

1. The installation of the level gauge must be vertical to ensure that the inner pontoon can move up and down freely in the pipe body. 2. Install a shut-off valve between the container and the liquid level gauge to clean and overhaul the liquid level timing to cut off the material. 3. No magnets are allowed to approach around the main body of the pontoon level gauge, otherwise ...

How to set the parameters of RKC thermostat RH900 How to set the parameters of RKC thermostat RH900

1. Lower limit deviation alarm setting: press the SET key to select and display "SLP", the green display screen displays the value of the parameter, and select the shift, increment, and decrement keys to set or modify the parameter. This parameter indicates the difference between the alarm point and the master setpoint. 2. The upper limit deviation alarm is set ...

RLC Thermostat - Fault and Troubleshooting of Vapor Pressure Temperature Controller RLC Thermostat - Fault and Troubleshooting of Vapor Pressure Temperature Controller

Faulting and troubleshooting of vapor pressure temperature controllers (1) Common faults and common faults of the vapor pressure type temperature controller include contact burning or adhesion, failure of the mechanical transmission mechanism and leakage of temperature sensor in the temperature sensing tube. Its detection method is: put the thermostat knob in a parking position, and use ...

RLC thermostats – a common failure of mechanical thermostats RLC thermostats – a common failure of mechanical thermostats

1. The terminal post of the thermostat is stuck and falls off Cause the compressor not to start, the thermostat dynamic and static contacts can not be disconnected, so that the compressor does not run, the thermostat contacts can not be disconnected, so that the motor of the refrigerator compressor does not stop, in addition to the balance elastic force is too weak, it can also be ...

RKG thermostat - an introduction to the relevant knowledge of temperature controllers RKG thermostat - an introduction to the relevant knowledge of temperature controllers

The temperature controller is an electrical switchgear that controls the temperature of an air-conditioned room. The temperature range in the air-conditioned room controlled by the temperature controller is generally 18°C--28°C. The temperature controller commonly used in window air conditioners uses the principle of pressure to push the contacts on and off. Its structure consists of bellows ...

RLC thermostat - common faults and solutions of intelligent temperature controllers RLC thermostat - common faults and solutions of intelligent temperature controllers

1. Heating for a period of time, the temperature does not change. Displays the ambient temperature of the site at all times (e.g. room temperature 25°C) In case of such failures, first check whether the SV value setting value is set, whether the instrument OUT indicator is lit, and whether the No. 3 and 4 terminals of the "multimeter" measuring instrument have 12VDC output.

RKC Level Gauges – An introduction to common types of level gauges RKC Level Gauges – An introduction to common types of level gauges

Explosion-proof float level switch Explosion-proof float level switch, also known as explosion-proof float level controller. It is a liquid level control instrument specially designed and manufactured for use in explosive atmospheres, this product is designed based on the principle of buoyancy and the principle of lever, when the liquid level in the container changes, ...

What are the solutions to the failure of the RRKC thermostat - the sudden thermostat? What are the solutions to the failure of the RRKC thermostat - the sudden thermostat?

1. The cleanliness and finish of the contact surface have a great impact on the working condition of the contact. When the surface of the contact is rough or there is excess material on the contact, it is easy to cause arcing and reduce the life of the contact. Therefore, the parts cleaning process should be improved to eliminate excess materials; Increasing the process of screening excess materials, ...

RKG thermostat - an introduction to the characteristics of digital displays RKG thermostat - an introduction to the characteristics of digital displays

1) It is a display of the common cathode. It uses the principle of the positive electrode as the segmented input, with the ground wire as the common output, and the segmented input is valid as a high-level input. 2) It is a display with a common anode. It uses an anode as an aggregate input, and in contrast to the common cathode, the segment is effective at a low level output ...

Common faults and failure analysis of RTC thermostats Common faults and failure analysis of RTC thermostats

1. The power indication is normal, but the temperature controller has no screen display. Most of this fault is caused by the heating of the voltage regulator element (7805 or 7812) on the thermostat during long-term use, which leads to the breakpoint of the solder joint, and sometimes it is caused by the phenomenon of virtual soldering at the factory, and the main re-soldering can be done. 2. Temperature controller ...

RKC thermostat Digital display controller parameter setting method RKC thermostat Digital display controller parameter setting method

A digital display controller is a simple controller with indication, control, remote transmission and alarm functions. As a secondary instrument commonly used in sensors, it is very important to operate and use it correctly. Applications such as level control, temperature control, pressure control and parameter value display of measured variables. ...

How to set the parameters of the RKG thermostat - intelligent digital display controller? How to set the parameters of the RKG thermostat - intelligent digital display controller?

1. First of all, the digital display should be installed on the cabinet, so the overall coordination should be considered, too large may not fit, too small to see the display numbers. 2. In addition, the large size of the instrument is generally more expandable, the same function price may be expensive, the small size of the instrument may be ...

RLC thermostat - common faults of temperature controllers and solutions RLC thermostat - common faults of temperature controllers and solutions

Fault 1: The device does not display after powering on Solution(s): First of all, check whether the terminals of the device have been connected to the neutral live wire, and make sure that the neutral live power supply can work normally. Then start to check whether the cable between the LCD motherboard and the device drive power supply is ...

RLC Thermostat – Precautions for Thermostat Operation RLC Thermostat – Precautions for Thermostat Operation

1) Measure the function Its temperature measurement scale is mainly between -20 °C and 80 °C, and the humidity measurement scale is mainly between 20% RH and 99% RH. In addition, it has a temperature resolution of 1°C and a humidity of 1%RH. 2) Parameters and data display functions Temperature and humidity control ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top