Frequency converters need to be replaced regularly – Reynolds

Create Date: 2024-8-30 12:03:23|Source: RENLE/RENOLDS

The inverter is composed of many electronic parts, such as semiconductor components, etc., which involves the replacement of a related component in the application and protection, because of the composition or physical characteristics of the inverter, it will deteriorate in a certain period of time, which will reduce the characteristics of the inverter, and even cause failure. Therefore, it is necessary to carry out regular replacement in order to protect against it.

                              Frequency converters need to be replaced regularly – Reynolds

1. Replace the cooling fan

The main circuit of the inverter is cooled by the semiconductor equipment to speed up the heat dissipation and ensure the normal operation below the allowable Wendy. The life of the cooling fan is limited by the bearing, which is about 10000-35000h. When the drive is running continuously, the fan or bearing needs to be replaced once after a few years. The replacement period of the cooling fan is greatly affected by the ambient temperature, and the cooling fan must be replaced immediately when abnormal sound and abnormal oscillation are found.

2. Replace the capacitor

Large-capacity electrolytic capacitors are used in the central DC circuit, and their performance deteriorates due to factors such as pulse current. The deterioration is greatly affected by the ambient temperature and operating conditions, and under normal conditions, the service cycle is about 5 years, and the deterioration of the capacitor develops rapidly after a certain time, so the maximum viewing week is one year, and the final life expectancy is less than half a year.

3. Replace the timer

The timer will change greatly after several years of use, so replace it after checking the action time.

4. Replace the fuse

The rated current of the fuse is large and the load current is large, and the life expectancy is about 10 years under normal operating conditions, and it is required to check the protection or even replace it at this time.

5. Replace relays/contactors

After the relay and contactor reach a certain cumulative number of switching times, the contact defect will occur, which needs to be checked and replaced.

Secondly, knowing the meta-equipment that may need to be replaced, here is a brief addition to the basic requirements for replacing meta-equipment.

1) Find out the basic parameters and appearance of the equipment to be replaced. The basic parameters include the rated operating current, the capacitance of the capacitor, the resistance value of the resistor, the value of the GTR Darlington device (current amplification factor), the switching characteristics of the IGBT (including IPM) device, and the full voltage. The form factor requirements include external dimensions, terminal position and mounting form, etc., and then replace the required equipment according to the same requirements.

2) All connectors should be recorded or marked when disassembled to avoid misplacement during replacement or rehabilitation.

3) The contact surface between the power equipment and the radiator should be evenly coated with thermal grease and fastened with screws.

ultimately

In most cases, the machine is in operation, and when the machine is not running, the inverter needs to be properly stored.

1) Storage

The room should be boring, no direct sunlight, no corrosive gases, and no dust; The relative humidity is 20%-90% and there is no frost; The temperature is between -10 and 30 °C (if the temperature is about 40 °C, the storage period should not exceed 6 months; About 50°C, the storage period does not exceed 3 months).

2) Protection

Because the main circuit and control circuit of the inverter use more electrolytic capacitors, if not used for a long time, the leakage will increase, the withstand voltage will decrease, that is, accelerate the deterioration (the higher the temperature, the faster the deterioration), therefore, at least once a year, the external power supply is added, so that the repair power-on time is 30-60min, the characteristic is that only the inverter monomer is energized (do not have to be connected to the motor), and the input end of the inverter can be connected to the power supply.

More on that
Reynolds soft starter problem solving Reynolds soft starter problem solving

1. The soft starter does not start and the fault-free code appears, perhaps because the control power supply is not connected, the solution is to check the power supply of the control power supply to see if the circuit connection is correct. 2. The motor starts when the motor announces a hum/no start signal, perhaps because of the thyristor/module ...

The working principle of the motor soft starter – Reynolds The working principle of the motor soft starter – Reynolds

Motor soft starter is the primary selection of power electronics skills and microprocessing skills and modern control theory and design and production of advanced level of new engine equipment, motor soft starter mainly has anti-interference function, high reliability, multiple protection functions and other characteristics, according to these characteristics of electric ...

Rated current analysis of inverter leakage circuit breaker Rated current analysis of inverter leakage circuit breaker

The output of the inverter is controlled by PWM (pulse width modulation, similar to high-speed switching), so a high frequency leakage current will occur, if you want to install a general leakage disconnect switch on the primary side of the inverter, it is recommended to select a sensitivity current of more than 200mA for each inverter and the action time is 0.1 seconds ...

Characteristics and Discrimination of Resistance Damage - Reynolds Characteristics and Discrimination of Resistance Damage - Reynolds

I often see many beginners tossing on the resistor when overhauling the circuit, and it is dismantling and welding, in fact, it is repaired a lot, as long as you understand the damage characteristics of the resistor, you don't have to bother. Resistors are the most numerous in electrical equipment ...

Reynolds inverter FAQ - parameter class Reynolds inverter FAQ - parameter class

1. What are the factory parameters of inverter rehabilitation? N600 = 100 (often press the WR button for 3-5 seconds), it is necessary to be in the shutdown state to be effective. 2. In the parameters of the N308 motor of the inverter, [motor leakage inductance reactance] is the specified sub...

Lightning protection measures for Reynolds frequency converters Lightning protection measures for Reynolds frequency converters

The lightning protection measures of the inverter equipment are another important peripheral measure to ensure the safe operation of the inverter, especially in the area where lightning is active or in the lively season, this problem is particularly important. Today's inverter products are generally equipped with mines.

The difference between heavy-duty inverter and light-duty inverter The difference between heavy-duty inverter and light-duty inverter

1. The starting time is different: light load generally refers to the small inertia of the equipment load, and the energy storage balance time of the demand for start-up is short, that is, the starting time is short. Heavy load generally refers to the long time of energy storage balance when the equipment load inertia is large and needs to be turned on, that is, the time of start-up. 2. The requirements for working current are not ...

The reason for the preferred DC mode in the intermediate link of the inverter - Reynolds The reason for the preferred DC mode in the intermediate link of the inverter - Reynolds

The development of the inverter has experienced a slow and gradual process, and the inverter at the beginning of the first century did not choose this kind of AC-DC: communication to DC and then to communication, but direct AC, no central DC link. This kind of inverter is called alternating frequency converter, and now this kind of inverter is in the ultra-high power ...

Structural characteristics of Reynolds RHY series inverter governor Structural characteristics of Reynolds RHY series inverter governor

1. Technology: (PC or PLC) is used to make the equipment complete the intelligent constant pressure variable supply water supply according to the requirements of water supply and fire protection; 2. High efficiency and energy saving: the system can set the pressure according to the demand, and the system actively adjusts the speed of the pump and the number of pumps according to the set pressure, so that the equipment can run in ...

Reynolds drive soft troubleshooting Reynolds drive soft troubleshooting

1. Phenomenon (1) When starting from the beginning, it trips as soon as the speed is raised. This is a very serious phenomenon of overcurrent. The main reasons are: short circuit of load, stuck mechanical parts; The inverter module is damaged; The torque of the motor is too small. (2) Jump when powered on, this phenomenon generally can't ...

Inverter power and box structure selection - Reynolds Inverter power and box structure selection - Reynolds

First, the selection of inverter power The system power is equal to the product of the inverter power and the motor power, and the system power is higher only when both are operating at a higher power. From the perspective of power, when selecting the power of the inverter, we should pay attention to the following points: 1) ...

Analysis and repair of inverter failure cases - Reynolds Analysis and repair of inverter failure cases - Reynolds

1. The inverter can not speed up the frequency increase when it starts with load The 1366S-BR 040 inverter carries a load of 37 kW fan motors. During the trial operation, it was found that the inverter could not speed up the frequency increase normally, and the HIM display was speeding up. The inverter only swings at 1-4 Hz, and the motor emits a buzzing ...

DCS and PLC and other control cabinets are inspected before leaving the factory DCS and PLC and other control cabinets are inspected before leaving the factory

1. Test preparation: 1. It is necessary to remove all power switches before powering on the PLC control cabinet or IO cabinet. 2. It is necessary to completely cut off the connection between the PLC or DCS card and the outside. All front adapters are to be loosened and raised. 3. Check the power terminal wires and connectors.

Reynolds inverter control method Reynolds inverter control method

The actuator commonly used in the industrial field of Reynolds inverter has good speed regulation performance and simple and convenient operation method. Therefore, it is widely used in the automation system. Typical wiring method for the main circuit of a Reynolds frequency converter ...

Frequency conversion cabinet external conduit wiring method - Reynolds Frequency conversion cabinet external conduit wiring method - Reynolds

When it is required to wiring outside the frequency conversion cabinet, it is generally necessary to use the conduit for wiring, which requires suitable mechanical pressure and unsuitable mechanical damage, moisture-proof and corrosion-resistant. Conduits include the following two wiring methods: 1. Kim ...

Difference Between Soft Starter and Inverter – Reynolds Difference Between Soft Starter and Inverter – Reynolds

Soft starters and frequency converters are two completely different products. The inverter is used in the local area where speed regulation is required, and its output not only changes the voltage but also changes the frequency at the same time; A soft starter is actually a voltage regulator, which is used when starting a motor, and the output only changes the voltage and does not change the frequency. Change...

Inverter selection conditions and precautions - Reynolds Inverter selection conditions and precautions - Reynolds

1. When selecting the inverter, select the inverter with the appropriate control method according to the load characteristics In addition to the inverter manufacturing process, it is also important to choose which control method of the inverter. The control method of the inverter is mainly divided into two types: open-loop control and closed-loop control. In the meantime, the open-loop control method ...

Precautions for the use of frequency converters - Reynolds Precautions for the use of frequency converters - Reynolds

In order to ensure the safe, efficient and reliable operation of the inverter, the following keys should be grasped when using the inverter: 1) It is necessary for the grounding terminal of the inverter to be firmly grounded, so as to effectively press the radio frequency disturbance and enhance the reliability of the system: the frequency conversion speed regulation system is best to use independent grounding, grounding resistance...

The inverter cannot adjust the frequency solution - Reynolds The inverter cannot adjust the frequency solution - Reynolds

In the course of inverter repairs, if there is no significant damage to the hardware and the maximum torque of the VFD is usually less than the torque of the load increase. It means that the load capacity of the frequency conversion speed control equipment has decreased significantly. So how do you deal with this? ...

Inverter control loop wiring taboo - Reynolds Inverter control loop wiring taboo - Reynolds

1. The wires laid out in the inverter control circuit should be separated from the main circuit cable (power line), so as to avoid the harmonic disturbance components on the side of the main circuit of the inverter from polluting the inverter control circuit; 2. Due to the faulty signal of the inverter and ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top