1. Phenomenon
(1) When starting from the beginning, it trips as soon as the speed is raised. This is a very serious phenomenon of overcurrent. The main reasons are: short circuit of load, stuck mechanical parts; The inverter module is damaged; The torque of the motor is too small.
(2) Jump when powered on, this phenomenon generally cannot be reset, the main reasons are: bad module, bad drive circuit, bad current detection circuit.
(3) When starting from the beginning, it does not trip immediately but when accelerating, and the main reasons are: the acceleration time is set too short, the upper current limit is set too small, and the torque compensation (V/F) is set high.
2. Examples
(1) A 43.7kW inverter jumps "OC" as soon as it is started
Analysis and repair: open the cover did not find any traces of burnout, online measurement IGBT (7MBR25NF-120) is not a problem at all, in order to further identify the problem, the IGBT is removed after measuring 7 units of high-power transistor registration and closure are very good. When measuring the drive circuit of the upper half-bridge, it was found that one of the two channels was obviously different, and after careful inspection, it was found that the output pin of an optocoupler A3120 was short-circuited to the negative pole of the power supply, and the three channels were fundamentally the same after replacement. The module is powered on and running all outstanding.
(2) A 2.2kW inverter jumps "OC" when it is energized and cannot be reset.
Analysis and repair: First check the inverter module and find no problems. Secondly, there is no abnormal phenomenon in the drive circuit, it is estimated that the problem is not in this piece, perhaps in the overcurrent signal processing part, the circuit sensor is removed and powered on, and everything is normal, so it is thought that the sensor is broken, and everything is normal after the load test is replaced with a new product.
3. Overvoltage
The overvoltage alarm is generally presented at the time of shutdown, and the main reason is that the deceleration time is too short or there is a problem with the braking resistance and braking unit.
(1) Examples
A 3.7kW inverter jumps "OU" when it stops.
Analysis and repair: Before repairing this machine, we must first figure out the reason for the "OU" alarm, this is because when the inverter is decelerating, the speed of the rotor winding of the motor cutting the rotating magnetic field accelerates, the electromotive force and current of the rotor increases, so that the motor is in a state of power generation, and the energy fed back flows to the DC link through the diode connected in parallel with the high-power switch tube in the inverter link, so that the DC bus voltage rises, so we should focus on looking at the braking circuit, there is no problem in measuring the discharge resistance, and the brake tube ( ET191) was found to have broken down, and after replacement, it was powered on and running, and there was no problem with rapid shutdown.
4. Undervoltage
Undervoltage is also a problem that we often encounter in application. The main reason is that the voltage of the main circuit is too low (220V series is lower than 200V, 380V series is lower than 400V), the main reason: a certain road of the rectifier bridge is damaged or there is abnormal operation in the three ways of the thyristor, which may lead to the presentation of undervoltage problems, and secondly, the main circuit contactor is damaged, resulting in the voltage loss of the DC bus on the charging resistor. There is also a problem of undervoltage due to the failure of the voltage detection circuit.
Example
(1) An 18.5kW inverter is powered on to jump "Uu".
Analysis and repair: After checking the rectifier bridge charging resistance of this inverter, it is good, but the contactor action is not heard after powering on, because the charging circuit of this inverter is not using thyristor but relying on the contactor to complete the charging process, so it is believed that the problem may be in the contactor or control circuit and power supply part, remove the contactor and add 24V DC contactor to work normally. Then check the 24V DC power supply, after careful checking, the voltage is output after the voltage stabilization of the LM7824 regulator tube, measure that the voltage regulator tube has been damaged, find a new product to replace the power on operation normally.
(2) A frequency converter appears normal when powered on, but the load jumps "DCLINKUNDERVOLT" (DC loop voltage is low).
Analysis and repair: this inverter is more special from the phenomenon point of view, but if you carefully analyze the problem is not so messy, the same inverter is also through the charging circuit, contactor to complete the charging process, no abnormal phenomenon was found when powering on, it is estimated that the voltage drop of the DC circuit is caused by the load increase, and the voltage of the DC circuit is rectified by the full wave of the rectifier bridge, and then provided by the capacitor after the flat wave, so we should focus on looking at the rectifier bridge, and the rectifier bridge is found to have a bridge arm open circuit. The problem is solved after replacing the new product.
5. Overheating
Overheating is also a relatively common problem, the main reasons: the surrounding temperature is too high, the fan is stalled, the temperature sensor performance is poor, and the motor is overheated.
(1) Examples
A 22kW inverter was reported by a customer who jumped "OH" after about half an hour of operation.
Analysis and repair: because it is a problem after a period of operation, so the temperature sensor may not be bad, perhaps the temperature of the inverter is indeed too high, after the power is on, it is found that the fan rolls slowly, and the protective cover is filled with a lot of cotton wool (because the inverter is used in the textile industry), after cleaning, the fan runs outstandingly, and there is no jump after a few hours of operation.
6. The output is unbalanced
The output imbalance is generally manifested as motor flutter and unstable speed, the main reasons: bad module, bad drive circuit, bad reactor, etc.
(1) Examples
A 11KW inverter, the output voltage difference is about 100V.
Analysis and repair: open the machine to check the inverter module (6MBI50N-120) online no problem, measure the 6-way drive circuit did not find a problem, remove the module and measure it found that there is a bridge high-power transistor can not be turned on and closed normally, the module is now damaged, after confirming that the drive circuit is fine, everything is normal after replacing the new product.
7. Overload
Overload is also one of the problems of frequency converter beating, usually see the overload phenomenon we should first analyze whether it is the motor overload or the inverter itself overload, generally speaking, the motor can be stronger because of overload, as long as the motor parameters of the inverter parameter table are set properly, it is generally not likely to present motor overload. The inverter itself is poor because of overload, and it is very simple to present an overload alarm. We can detect the output voltage of the inverter, the current detection circuit, and other fault-prone points to eliminate the fault one by one.
(1) Examples
A 55KW inverter often jumps "OL" when running.
Analysis and repair: According to the customer, this machine was originally used on a 37kw motor, but now it is used on a 55kw motor. The parameters have not been set from the beginning, so the problem may lie in the parameters, after checking the frequency conversion current limit set to the rated current of the 37kw motor, after the parameters are set from the beginning with the load everything is normal.
|
More on that
|
Reynolds assisted Sinopec Weirong shale gas project
With the rapid development of China's national economy, the supply and demand situation of oil and gas resources is becoming increasingly severe, and the import of oil and gas is increasing year by year, so it is urgent to expand the field of domestic oil and gas exploration and development. Strengthening the exploration and development of shale gas resources can make up for the lack of conventional oil and gas resources and promote the sustainability of the oil and gas industry.
|
|
Inverter selection conditions and precautions - Reynolds
1. When selecting the inverter, select the inverter with the appropriate control method according to the load characteristics
In addition to the inverter manufacturing process, it is also important to choose which control method of the inverter. The control method of the inverter is mainly divided into two types: open-loop control and closed-loop control. In the meantime, the open-loop control method ...
|
|
Rated current analysis of inverter leakage circuit breaker
The output of the inverter is controlled by PWM (pulse width modulation, similar to high-speed switching), so a high frequency leakage current will occur, if you want to install a general leakage disconnect switch on the primary side of the inverter, it is recommended to select a sensitivity current of more than 200mA for each inverter and the action time is 0.1 seconds ...
|
|
The object of protection of frequency converters in overload protection - Reynolds
Inverters are mainly divided into two categories according to the frequency conversion method: communication/DC/communication and communication/communication inverters. Here we take the widely used general "communication/DC/communication" as an example to briefly talk about its structure and operating principle. As can be clearly seen from the above diagram, the communication/...
|
|
Analysis and repair of inverter failure cases - Reynolds
1. The inverter can not speed up the frequency increase when it starts with load
The 1366S-BR 040 inverter carries a load of 37 kW fan motors. During the trial operation, it was found that the inverter could not speed up the frequency increase normally, and the HIM display was speeding up. The inverter only swings at 1-4 Hz, and the motor emits a buzzing ...
|
|
Wiring of Reynolds frequency converters
1 Main circuit wiring
(1) Reynolds inverter three-phase AC input terminal (R, S, T)
The power input terminal is connected to the three-phase AC power supply through the circuit breaker of the circuit breaker for line protection, regardless of the connection phase sequence. It should be noted here that the three-phase AC power supply is not ...
|
|
The cause of overheating of servo motor bearings - Reynolds
The motor itself:
1) The inner and outer rings of the bearing are too tightly cooperated.
2) There are problems with the shape and position tolerance of parts, such as the coaxiality of parts such as machine base, end cover, shaft and other parts is not good.
3) Improper selection of bearings.
4) The bearing is not smooth or the bearing is not clean, and there are impurities in the smooth grease. ...
|
|
Protection function of the Reynolds soft starter
1. Overload protection function: The soft starter introduces a current control loop, so that the change of motor current can be tracked and detected at any time. By increasing the setting of overload current and the anti-time control mode, the overload protection function is realized, so that when the motor is overloaded, the thyristor is turned off and an alarm signal is issued.
...
|
|
Inverter frequency regulation fault solution - Reynolds
Most of the applications of frequency converters (hereinafter referred to as -VFDs) are primarily due to the fact that VFDs can change the output frequency and thus change the speed of the motor. If the frequency of the VFD cannot be adjusted and no damage is found on the hardware, it can be considered that the maximum output torque of the VFD is less than the load progress torque ...
|
|
Reynolds frequency converters are remotely controlled for wiring
1. Connect X (switching input) drive terminal to control the inverter start-stop/positive rotation;
2. Connect to the AI (analog input) terminal to control the frequency of the inverter (perhaps made into PID closed-loop control automatic adjustment frequency)
3. ...
|
|
Wiring of the main circuit of the inverter - Reynolds
(1) Inverter three-phase communication input terminal (R, S, T)
The power input terminal is connected to the three-phase communication power supply through the circuit breaker of the circuit breaker for line protection, regardless of the connection phase sequence. It should be noted here that the three-phase communication power supply must not be directly connected to the inverter output ...
|
|
Reynolds inverter overhaul process
1) Query and query fault phenomena. The fault phenomenon of the inverter is varied, for example, the same type of problem may have different problem phenomena, and different types of problems may have the same kind of problem, which brings difficulties to find the problem. However, the problem phenomenon is the fundamental basis for repairing the inverter ...
|
|
Reynolds universal inverter start-up mode
1. Direct launch
The universal inverter insists on starting at the beginning of the time according to the set starting frequency and starting frequency, and then accelerates to a given frequency according to the selected acceleration time
Second, the speed of the tracking start
Universal inverter ...
|
|
The breaking capacity of the industrial control appliance switch
Assuming Icu=60KA, then when a faulty current of 60KA is generated in the line, the circuit breaker can safely cut off the circuit without abnormal conditions such as contact welding and blasting. Pay attention to the extreme breaking ...
|
|
Introducing the Reynolds JJR8000 series of intelligent soft starters
JJR8000 series of intelligent motor soft starter is the use of power electronics skills, microprocessor skills and modern control theory skills to produce today's international first-class starting equipment, the product can constrain the starting voltage of the asynchronous motor when starting, can be used in fans, water...
|
|
Reynolds inverter parameter settings
The use of Reynolds inverters in industrial production is very important, in addition to speed regulation, soft start effect, the important thing is to be able to save energy. There are many functional parameters of Reynolds inverter, and there are generally dozens or even hundreds of parameters for users to choose. In practice, it is not necessary to ...
|
|
The external configuration of the inverter is solved - Reynolds
With the improvement of the degree of automation of packaging machinery, packaging machine inverter (hereinafter referred to as VFD) plays an increasingly important role in packaging machinery. Capsule filling machine, high-speed tablet press, bottling production line, aluminum-plastic packaging machine, cartoning machine, each equipment will use VFD, mainly ...
|
|
The role of frequency conversion technology in work equipment - Reynolds
Because inverters are widely used, there are many differences in the corresponding types and specifications. We are broadly divided into two categories: voltage and current. The current type of inverter products is characterized by the use of a large inductor as the energy storage link in the middle DC link, and the reactive power will be buffered by this inductor. ...
|
|
Inverter control method - Reynolds
The output voltage of low-voltage general frequency conversion is 380-650V, the output power is 0.75-400kW, and the operating frequency is 0-400Hz. Its control methods have gone through the following four generations. 1U/f=C Sinusoidal Pulse Width Modulation (SPWM) Manipulation MethodIts Characteristics ...
|
|
"RNB6000 frequency conversion governor" was included in the National Torch Program
Recently, in the "2012 National Torch Program Project" issued by the Ministry of Science and Technology of the People's Republic of China, the "RNB6000 Frequency Conversion Governor" independently developed by Reynolds was included in the "2012 National Torch Program Project" with its domestic leading skills and efficient energy-saving conversion power.
|
|