1. Why can the rotation speed of the motor be changed freely?
Motor rotation speed unit: r/min number of rotations per minute, can also be expressed as rpm.
Example: 2-pole motor 50Hz 3000 [r/min]
4-pole motor 50Hz 1500 [r/min]
Conclusion: The rotational speed of the motor is divided into two parts of the frequency
The rotational speed of an induction AC motor (henceforth referred to as a motor) is approximately determined by the number of poles and frequency of the motor. The number of poles of the motor is fixed by the working principle of the motor. Because the pole value is not a continuous value (a multiple of 2, e.g. the pole number is 2, 4, 6), it is generally not suitable to adjust the speed of the motor by changing the value.
In addition, the frequency can be adjusted outside the motor and then supplied to the motor, so that the rotation speed of the motor can be freely controlled.
Therefore, the inverter with the intention of controlling the frequency is the preferred equipment for motor speed regulation equipment.
n = 60f/p
n: Synchronization speed
f: Power frequency
p: Number of pole pairs of the motor
Conclusion: Changing the frequency and voltage is the best way to control the motor
If only the frequency is changed but not the voltage, the motor may burn out due to overvoltage (overexcitation) when the frequency drops. Therefore, the frequency converter must change the voltage at the same time as changing the frequency. When the output frequency is above the additional frequency, the voltage cannot be further added, and the maximum voltage can only be equal to the additional voltage of the motor.
For example, if the output frequency of the inverter is changed from 50 Hz to 25 Hz in order to halve the rotation speed of the motor, the output voltage of the inverter needs to be changed from 400 V to about 200 V
2. What happens to the output torque of a motor when its rotation speed (frequency) is changed?
The starting torque and maximum torque when driven by the inverter are less than those driven by direct industrial frequency power supply.
The motor starts and accelerates when the power frequency power supply is very large, and when the inverter is used for power supply, these impacts are weaker. A large starting current will occur when the power frequency is directly started. When the inverter is used, the output voltage and frequency of the inverter are gradually added to the motor, so the starting current and impact of the motor are smaller.
In general, the torque generated by the motor decreases as the frequency decreases (speed decreases). Practical data for the reduction is illustrated in some inverter manuals.
By using a magnetic flux vector-operated inverter, the lack of torque in the motor at low speeds will be improved, and the motor can output sufficient torque even at low speeds.
3. When the speed of the inverter is adjusted to a frequency greater than 50Hz, the output torque of the motor will decrease
The general motor is planned and made according to the voltage of 50Hz, and its additional torque is also given in this voltage range. Therefore, the speed regulation under the extra frequency is called constant torque speed regulation. (T=Te, P)
When the output frequency of the inverter is greater than the frequency of 50Hz, the torque of the motor decreases in a linear relationship inversely proportional to the frequency.
When the motor is running at a frequency speed greater than 50Hz, the size of the motor load must be considered to prevent the lack of motor output torque.
For example, the torque of a motor at 100 Hz drops to about 1/2 of that at 50 Hz.
Therefore, the speed regulation above the additional frequency is called constant power speed regulation. (P=Ue*Ie)
4. The use of the inverter above 50Hz
As you know, for a particular motor, the extra voltage and extra current are constant. For example, the additional value of the inverter and the motor is: 15kW/380V/30A, and the motor can work above 50Hz.
When the speed is 50Hz, the output voltage of the inverter is 380V and the current is 30A. At this time, if the output frequency is increased to 60Hz, the maximum output voltage and current of the inverter can only be 380V/30A, and the output power is obviously unchanged. That's why we call it constant power speed regulation.
What about the torque? Because P=wT (w: angular velocity, T: torque). Since P does not change, w is added, so the torque decreases accordingly.
Let's also look at it from another angle: the stator voltage of the motor U = E + I*R (I is the current, R is the electronic resistance, E is the induced potential) It can be seen that when you and I are unchanged, E is also constant. E = k*f*X, (k: constant, f: frequency, X: flux), so when f is from 50–>60Hz, X decreases accordingly
For motors, T = K*I*X (K: CONSTANT, I: CURRENT, X: MAGNETIC FLUX), SO THE TORQUE T WILL DECREASE WITH THE DECREASE OF MAGNETIC FLUX X. Together, when it is less than 50Hz, because I*R is very small, when U/f=E/f is constant, the magnetic flux (X) is constant, and the torque T is proportional to the current. This is why the overcurrent ability of the inverter is generally used to describe its overload (torque) ability. It is also called constant torque regulation (the additional current does not change – > the maximum torque does not change)
Conclusion: When the output frequency of the inverter is increased from 50Hz or more, the output torque of the motor will decrease.
5. Other elements related to output torque
Heat generation and heat dissipation can determine the output current of the inverter, which affects the output torque of the inverter.
Carrier frequency: Generally, the additional current marked by the inverter is the value that can ensure the continuous output at the highest carrier frequency and the highest ambient temperature. If the carrier frequency is lowered, the current of the motor will not be affected, but the heat generation of the components will be reduced.
Ambient temperature: Just like the inverter maintenance current value will not be increased because the ambient temperature is low.
Altitude: Altitude is added to have an impact on heat dissipation and insulation. Generally, less than 1000m can be considered. The above 5% reduction per 1000 meters is enough.
|
More on that
|
Schneider servo model introduction
LXM23DU01M3X servo drive 0.1 kW
LXM23DU02M3X servo drive 0.2 kW
LXM23DU04M3X Servo drive 0.4 kW
LXM23DU07M3X Servo drive 0.75 kW
LXM23DU10M3X ...
|
|
Schneider frame circuit breaker MT circuit breaker does not close the brake problem
Schneider structural circuit breaker is not stored (check the power supply of the energy storage motor, if it is normal, check whether it can be manually stored for energy)
MX shunt coil live (disconnect MX coil power)
The MN coil is not charged or faulty (a voltage higher than 0.85Un is applied to the MN)
The circuit breaker is latched in ...
|
|
Schneider instrumentation winter insulation measures
The methods adopted usually are: selection, thermal insulation and heat tracing, protection (point inspection, sewage discharge) and so on.
Selection method
Choose the appearance of the type with insulation equipment. According to the category and use of the appearance and the geographical location of the proposed equipment, the insulation and antifreeze requirements of the appearance are proposed, and then submitted to the manufacturer for processing. ...
|
|
Schneider inverter debugging steps and brief description
Commissioning process of the Schneider 61 series
1. Preparations
1. Measure insulation. Connect the power supply side (R.S.T) and the motor side (U.V.W) of the inverter
Disconnect the cable, insulate the cable with a 500 megaohm or 1000 megaohm shake meter, and if it meets the requirements, restore it.
|
|
Precautions for the use and maintenance of instruments and meters - Schneider
Attention should be paid to the following matters during the use and maintenance of the appearance of the instrument:
1. Don't blindly knock and bump when overhauling, so as not to expand the problem, and the more you repair, the worse it will become.
2. Do not plug and unplug various control boards and plugs with electricity. Due to the power-on ...
|
|
Dual-fan inverter selection - Schneider
1. Qualified after inspection
When selecting a double fan inverter, it must be strictly checked for its quality. The first requirement is that it must have relevant certificates of qualified inspection, and some qualified materials must be taken out. This is the only way to ensure that this change ...
|
|
Servo motor selection process – Schneider
1. Load organization (acknowledging the type of tissue and its specific data, such as ball screw length, ball screw diameter, stroke, pulley diameter, etc.)
2. Form of action (acknowledging the form of action of manipulating the target, the relationship between time and speed; Will manipulate ...
|
|
"Five Ways" to Solve Life Sciences Industry Challenges – Schneider
In life sciences careers, equipment performance is critical to ensuring business continuity and useful production time. The main challenges faced by the industry include: maintaining the positive impact of environmental parameters on product quality, managing multiple systems in a "siloed" state, and using existing infrastructure sensitively and efficiently.
|
|
Precautions for setting parameters of Schneider inverter
Debugging parameters:
1. Acceleration and deceleration time
Speed up the time setting requirements: the acceleration current is constrained below the overcurrent capacity of the inverter, so that the overflow will not cause the inverter to trip; Deceleration time setting key ...
|
|
Deterioration site and the principle of higher harmonic generation - Schneider
1. Electrical equipment will produce higher harmonics when it produces abnormality and deterioration, and the abnormality and deterioration of motors, loads, and inverters are used to distinguish the higher harmonics from 2 to 40 times, and the data is changed by FFT, and the analysis is made on the basis of the analysis data of long-term savings.
|
|
Precautions for the installation of low-voltage electrical appliances - Schneider
1. Low-voltage electrical appliances should be equipped in a place without violent vibration, and should have an appropriate height from the ground. It is necessary to connect the power cord such as the knife switch and the load switch to the fixed contact, and it is forbidden to hang the power cord on the knife switch.
2. Low-voltage ...
|
|
Automatic control instrument construction content and procedures - Schneider
1. Construction preparation. Including the preparation of operating conditions (construction skills documents and detailed planning documents), construction organization planning, equipment list, data budget, and list of machined parts;
2. Cooperate with civil engineering majors to do a good job of embedding, ...
|
|
Schneider Thermal Relay Model Meaning
The function of the thermal relay is mainly used to carry out overload maintenance on the asynchronous motor, and his operating principle is that after the overload current passes through the thermal element, the bimetal sheet is heated and twisted to advance the action organization to drive the contact action, so as to disconnect the motor control circuit to realize the motor power-off thermal relay ...
|
|
Precautions for false load connection in Schneider inverter debugging
There are many novices who are not familiar with the fake load when repairing the inverter, and the repair of the inverter saves many of their modules with the false load, because the novice repairer generally does not know how to do this, and now the light is on to make it clear that the module is going to be broken. A false load is a resistor with a few hundred ohms ( ...
|
|
Two of Schneider's low-voltage power distribution products won the Germany Red Dot Award
Beijing, China, April 6, 2022 – Recently, the list of "Red Dot Planning Awards", known as one of the world's three cutting-edge industrial planning awards, was grandly announced in Germany.
|
|
Schneider Vijeo-Designer compilation error factor
Q1833: Because you are using an older version of Runtime, the download does not last. Please use the Runtime Device program on the Vijeo Designer CD to upgrade the runtime.
When you download to an older runtime ...
|
|
Schneider's new Modicon programmable controller PLC series
Schneider Electric, the global energy efficiency management specialist, has launched the new Modicon Programmable Manipulator (PLC) M221 series, M241 series and M251 series under the MachineStruxure machine automation channel. This series of new products is tailored for industrial OEM shopping malls, relying on Schneider Electric global ...
|
|
Schneider UPS uninterruptible power supply debugging precautions
1. Check whether all switches are in the disconnected position;
2. Check whether there are foreign objects in the UPS uninterruptible power supply cabinet and transformer; Check whether the flat cable connection is correct and whether it is loose;
3. Check that the connected plug is ...
|
|
THE DIFFERENCE BETWEEN SCHNEIDER CIRCUIT BREAKER EASYPACT AND MASTERPACT
First of all, both are low-voltage circuit breakers (below 1000V)
Let's start with Schneider Masterpact, which is a structural circuit breaker. The current rating of the structure varies from 800A ---- 6300A. The Masterpact series is divided into M series and MT series. The M series has been on the market since 1986 and was screened and delisted in 2002.
|
|
Schneider inverter frequently asked questions
1. Schneider inverter uses analog output port to indicate the motor frequency, when the motor frequency is 50Hz, why is the output only 16mA?
Answer: Because of the large output frequency parameter "TFR" of the inverter, the factory default value is 60Hz. So when the inverter output is 50Hz, the analog output is ...
|
|