Calculation method of inverter capacity - Schneider

Create Date: 2024-8-30 12:03:23|Source: Schneider/Schneider

1. Accounting of inverter capacity when the load is continuously changed periodically

In many cases, the load of the motor changes periodically. Obviously, in this case, picking the capacity of the inverter by the minimum load will be overloaded, and it will be uneconomical to pick by the maximum load. It follows that the capacity of the inverter can be appropriately selected between the maximum load and the minimum load, so that the inverter can be fully utilized without being overloaded.

Firstly, the motor load current diagram n=Φt) and I=f(t) are made, and then the average load current Iav is calculated, and then the capacity of the inverter is pre-selected, and the following formula is used for the calculation of Iav:

  Iav=(I1t1+I2t2+…+Ijtj+…)÷(t1+t2+…+tj+…)

Considering that during the transition process, the electric motor will absorb more current from the inverter than during stable operation, and the above IAV does not reflect the situation in the transition process. Therefore, the capacity of the inverter is pre-selected according to IFN≥ (1.1-1.2) IAV correction (where, Ij is the average current in the j-section operation state, tj is the corresponding time in the j-section operation state, and if the transition process accounts for a large proportion in the whole working process, the coefficient (1.1-1.2) is selected as the larger value.

                              Calculation method of inverter capacity - Schneider

2. Accounting of inverter capacity when non-periodic change load is running continuously

This kind of scene is generally difficult to make a load current diagram, you can calculate the rated current of the inverter according to the current of the motor when the maximum torque is output, the formula can be used:

IFN≥IM(max)/KFg (where IM(max) is the current of the motor when the maximum torque is output).

More on that
Schneider Electric has announced the launch of its Pacific Foundation Schneider Electric has announced the launch of its Pacific Foundation

Schneider Electric has announced the launch of its Pacific Foundation, which will provide financial and advisory support to charitable foundations in the Pacific region to address fundamental human rights issues of access to energy. Four foundations were selected as the Foundation's initial recipients.

The difference between vector and general use of inverter - Schneider The difference between vector and general use of inverter - Schneider

1. The control accuracy of the vector type is higher than that of the general-purpose type. 2. The vector type has a large output torque at low speed, which can make the motor get a larger starting torque, which is suitable for application in the occasion of heavy load starting, such as: high-power long belt, hoist, etc. If used in some of the more common fields ...

Schneider DC air open up plus or minus? How to connect the incoming and outgoing lines? Schneider DC air open up plus or minus? How to connect the incoming and outgoing lines?

The air switch is divided into the upper inlet line and the lower inlet line of the power supply, 1 is - 3 is + 2 is + 4 is - when the upper line is inlet, 2 is + 4 is - This is related to the internal trip curve. DC circuit breaker is used for DC system operation method conversion or fault removal ...

Schneider Vijeo-Designer compilation error factor Schneider Vijeo-Designer compilation error factor

Q1833: Because you are using an older version of Runtime, the download does not last. Please use the Runtime Device program on the Vijeo Designer CD to upgrade the runtime. When you download to an older runtime ...

Commissioning steps for Schneider drives Commissioning steps for Schneider drives

1. Type recognition: Recognize whether the type of inverter is common with the type of inverter purchased. 2. Transportation acknowledgement: After opening the package, check whether the inverter is damaged during transportation. 3. Voltage recognition: the power supply voltage on the site should be borne by the inverter.

Schneider disconnector operation inspection content and requirements Schneider disconnector operation inspection content and requirements

(1) Whether the closing of the barrier switch is defective, whether there is no failure or dislocation; (2) The porcelain insulation of the barrier switch should be free of cracks, discharge phenomena and flashover traces; (3), contact viewing: a, view ...

Frequency characteristics of frequency converters – Schneider Frequency characteristics of frequency converters – Schneider

a. Output frequency scale. The output frequency scale that can be controlled by the general inverter is generally 0.1Hz, and the highest frequency is different according to the functional indicators of the inverter, generally 400Hz, and some models are 650Hz. No matter how high the output frequency is, it belongs to the scale of high-frequency inverter. ...

Methods to reduce the interference of Schneider inverters themselves Methods to reduce the interference of Schneider inverters themselves

When there are high-frequency impact loads such as welding machines, electroplating power supplies, electrolytic power supplies, or slip ring power supply near the power supply system of Schneider inverter, the inverter itself is simply protected due to interference. It is recommended that users choose the following methods: ...

Schneider ATV630 VFD series advantages Schneider ATV630 VFD series advantages

Depending on the customer's requirements, wall-mounted drives, built-in cabinets and floor-mounted free-standing solutions in protection classes IP 21, IP 23, IP 54 and IP 55 are available. Thanks to the built-in pump monitoring function, the device reacts immediately when pump efficiency drops, resulting in ...

Schneider Instrumentation Classification Schneider Instrumentation Classification

1. Industrial automation appearance and control system. This is generally referred to as PA, FA in foreign countries. PA is called process automation, and FA is called factory automation. The appearance and control system used in process automation and factory automation belong to this category, and some parts of the appearance of analytical instruments and electrical instruments also belong to the ...

Deterioration site and the principle of higher harmonic generation - Schneider Deterioration site and the principle of higher harmonic generation - Schneider

1. Electrical equipment will produce higher harmonics when it produces abnormality and deterioration, and the abnormality and deterioration of motors, loads, and inverters are used to distinguish the higher harmonics from 2 to 40 times, and the data is changed by FFT, and the analysis is made on the basis of the analysis data of long-term savings.

Precautions for the installation of low-voltage electrical appliances - Schneider Precautions for the installation of low-voltage electrical appliances - Schneider

1. Low-voltage electrical appliances should be equipped in a place without violent vibration, and should have an appropriate height from the ground. It is necessary to connect the power cord such as the knife switch and the load switch to the fixed contact, and it is forbidden to hang the power cord on the knife switch. 2. Low-voltage ...

Schneider low-voltage circuit breaker selection Schneider low-voltage circuit breaker selection

1. Determine the type and maintenance situation of Schneider circuit breaker according to the maintenance requirements of the line, and determine the selection of frame type, device type or current limiting type. Generally speaking, the Schneider frame circuit breaker can break the short-circuit current with a large device type and a large volume. Usually, the branch line chooses ...

Maintenance of multiple models of Schneider inverters Maintenance of multiple models of Schneider inverters

Schneider inverter our most common problem is that the power is not visible, the series of inverter switching power supply uses a UC2842 chip as a waveform generator, the damage of the chip will lead to the switching power supply can not operate, so that it can not be displayed normally, in addition, the operating power supply of the chip is not ...

Inverter power settings, waveform test issues Inverter power settings, waveform test issues

1. After the inverter is repaired, the power number demand is corrected, don't forget Generally, an inverter corresponds to a power number (also known as the number of horsepower), for example, a 75 kilowatt inverter is set under heavy load, and 100 kilowatts is set under light load. In this way, the customer will not use it to present ...

How to choose Schneider circuit breaker How to choose Schneider circuit breaker

The origin orientation is incorrect, and the encoder debugs/zeros the bit First, the value of the current at each branch is calculated (1) Purely resistive loads, such as bulbs, electric heaters, etc., are directly divided by the indicated power by the voltage. Formula I = power/220v; ...

How to identify the quality of an inverter – Schneider How to identify the quality of an inverter – Schneider

Nowadays, the function of domestic inverters is becoming more and more mature, with a wide variety and dazzling. Many brands have been tested by the market, but there are also some brands that have been imitated and counterfeited to disrupt the market. One of the major characteristics of domestic brands is that they are both like domestic brands and imported brands. The brand's ...

NSX molded case circuit breaker selection - Schneider NSX molded case circuit breaker selection - Schneider

The Schneider NSX molded case circuit breaker has a double rotary contact construction for maintenance, and the high-end electronic trip unit allows for accurate measurement and easy communication. Schneider NSX molded case circuit breaker conforms to IEC60947-2, GB14048.2, China's CCC certification and multinational classification certification...

Analysis of the causes of Schneider touch screen touch deviation Analysis of the causes of Schneider touch screen touch deviation

(1) Fault--: Contact error Phenomenon 1: The direction of the finger does not coincide with the mouse arrow. Reason 1: After installing the driver, there is no vertical contact with the bullseye center when correcting the bearing. Solution 1: Re-align the bearing. Phenomenon 2: Some districts ...

Inverter power-saving method - Schneider Inverter power-saving method - Schneider

First, it is a fan/pump load Second, the device itself has a power-saving function (software support) Third, we need to work for a long time The above are the three conditions that reflect the results of power saving. If it is said that the power frequency of the inverter is energy-saving without conditions, it is ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top