Solution: Delta's inverter operation error

Create Date: 2024-8-30 12:03:23|Source: Delta/Delta

There are many setting parameters of the inverter, each parameter has a certain selection scale, and the inverter can not work normally due to the improper setting of a single parameter is often encountered in the application, therefore, the relevant parameters must be set correctly.

                               Solution: Delta's inverter operation error

1. Control mode

i.e. speed control, rotation control, PID control, or other means. After adopting the control mode, it is generally necessary to carry out static or dynamic identification according to the control accuracy.

2.*** Low working frequency

That is, the motor works at a small speed, when the motor works at a low speed, its heat dissipation function is very poor, and the motor works at a low speed for a long time, which will cause the motor to burn. In addition, at low speeds, the current in the cable will also increase, which will also cause the cable to heat up.

3.*** High working frequency

The general frequency converter has a large frequency to 60Hz, and some even to 400 Hz, and the high frequency will make the motor work at high speed, which is for the general motor, its bearing can not work at super extra speed for a long time, and whether the rotor of the motor can accept such centrifugal force.

4. Carrier frequency

The higher the carrier frequency setting, the larger the higher harmonic component, which is closely related to the length of the cable, the heating of the motor, the heating of the cable and the heating of the inverter.

5. Motor parameters

The inverter sets the power, current, voltage, speed, and maximum frequency of the motor in the parameters, and these parameters can be directly obtained from the motor nameplate.

6. Frequency hopping

At a certain frequency point, resonance may occur, especially when the whole device is relatively high; When operating the compressor, it is necessary to prevent the surge point of the compressor.

7. Acceleration and deceleration moments

The acceleration time is the time required for the output frequency to rise from 0 to the highest frequency, and the deceleration time is the time required to decrease from the largest frequency to 0. Acceleration and deceleration times are usually confirmed by the rise and fall of the frequency setting signal. When the motor is accelerating, the rise rate of the frequency setting must be constrained to prevent overcurrent, and when the motor is decelerating, the fall rate must be constrained to prevent overvoltage.

Speed up the time setting requirements: the acceleration current is constrained below the overcurrent capacity of the inverter, so that the overflow will not cause the inverter to trip; The key to setting the deceleration time is to prevent the voltage of the lubricating circuit from being too large, and not to cause the regenerative overvoltage to stall and trip the inverter. The acceleration and deceleration time can be calculated according to the load, but in the debugging, it is often used to set a longer acceleration and deceleration time according to the load and experience, and investigate whether there is an overcurrent and overvoltage alarm through the starting and stopping motors; Then the acceleration and deceleration setting time is gradually shortened, and the alarm does not occur in the work as the criterion, and the operation is repeated several times to confirm the best acceleration and deceleration time.

8. Torque lifting

Also known as torque compensation, it is a method to increase the low-frequency scale f/V in order to compensate for the decrease in torque at low speed caused by the resistance of the stator winding of the motor. When set to active, the voltage at the time of acceleration can be actively increased to compensate for the starting torque, so that the motor can be accelerated smoothly. In the case of manual compensation, the optimal curve can be selected by experiments according to the load characteristics, especially the starting characteristics of the load. For variable torque loads, if the selection is not appropriate, the output voltage at low speed will be too high, and the electric energy will be wasted, and even the motor will show a large current when the motor is started with a load, and the speed can not go up.

9. Electronic thermal overload maintenance

This function is set to maintain the overheating of the motor, which is that the CPU in the inverter calculates the temperature rise of the motor according to the working current value and frequency, so as to carry out overheating maintenance. This function is only applicable to the occasion of "one to one", and in the case of "one to many", thermal relays should be installed on each motor.

Electronic Thermal Maintenance Setpoint (%) = [Motor Extra Current (A) / Inverter Extra Output Current (A)]× 100%.

10. Frequency Constraints

That is, the upper and lower amplitudes of the output frequency of the inverter. Frequency restriction is a maintenance function to prevent misoperation or external frequency setting signal source from malfunctioning, which causes the output frequency to be too high or too low, so as to prevent damage to the equipment. In use, it can be set according to the actual situation. This function can also be used for speed limiting, such as belt conveyor, because the material is not too much, in order to reduce the wear and tear of machinery and belt, the inverter can be driven, and the upper frequency of the inverter is set to a certain frequency value, so that the belt conveyor can work at a fixed, lower working speed.

11. Bias frequency

Some are also called deviation frequency or frequency deviation setting. Its use is that when the frequency is set by an external analog signal (voltage or current), this function can be used to adjust the output frequency when the frequency setting signal is low. When the frequency setting signal is 0%, the deviation value can be in the scale of 0 - fmax, and some inverters (such as Ming Dianshe and Sanken) can also set the bias polarity. If the output frequency of the inverter is not 0Hz but xHz when the frequency setting signal is 0% in the debugging, then the bias frequency can be set to negative xHz at this moment to make the output frequency of the inverter 0Hz.

12. Frequency setting signal gain

This function is only effective when the frequency is set with an external analog signal. It is used to compensate for the inconsistency between the externally set signal voltage and the internal voltage (+10V) of the inverter; When setting, when the imitation input signal is large (such as 10v, 5v or 20mA), find the frequency percentage that can output the f/V graph and set it as a parameter; If the external setting signal is 0 - 5V, if the output frequency of the inverter is 0 - 50Hz, the gain signal can be set to 200%.

13. Torque constraint

There are two types of driving torque constraint and brake torque restraint. It is based on the output voltage and current values of the inverter, and the torque is calculated by the CPU, which can significantly improve the shock load recovery characteristics during acceleration and deceleration and constant speed operation. The torque restraint function can complete active acceleration and deceleration control. Assuming that the acceleration and deceleration time is less than the load inertia time, the motor can also be guaranteed to actively accelerate and decelerate according to the torque set value.

The drive torque function provides a strong starting torque, in the steady state work, the torque function will control the motor to deteriorate, and the motor torque is constrained within the largest set value, when the load torque suddenly increases, even when the acceleration time is set too short, it will not cause the inverter to trip. When the acceleration time is set too short, the motor torque will not exceed the maximum set value. A large drive torque is good for starting, so it is better to set it to 80 - 100%.

The smaller the braking torque setting value, the greater the braking force, which is suitable for the occasion of rapid acceleration and deceleration, such as the overvoltage alarm phenomenon when the braking torque setting value is set too much. If the braking torque is set to 0%, the total amount of regeneration applied to the main capacitor can be close to 0, so that the motor can decelerate to a stop without using a braking resistor when decelerating. However, on some loads, such as when the braking torque is set to 0%, there will be a short idling phenomenon when decelerating, resulting in repeated start of the inverter, large fluctuations in current, and the inverter will trip when it is severe, which should be noted.

More on that
Delta's A2 server maintenance location controller is faulty Delta's A2 server maintenance location controller is faulty

Delta's A2 series servo system is one of the more common and used servers on the market today, and the following describes the fault details of the azimuth controller in the repair of Delta's A2 servo drive and the corresponding repair methods Delta ...

DC governor overhaul method - Delta DC governor overhaul method - Delta

DC governor is a kind of motor speed regulation equipment, including motor DC governor, pulse width DC governor, thyristor DC governor, etc. Generally, it is a modular DC motor governor, which integrates power supply, control and drive circuits, selects three-dimensional structure layout, and selects micro-power consumption elements for control circuits.

Tips and methods for using PLC - Delta PLC Tips and methods for using PLC - Delta PLC

First, the selection of output module The output modules are divided into transistors, triacs, and contact types: (1) The switching speed of the transistor type is fast (generally 0.2ms), but the load can be small, about 0.2-0.3A, 24VDC, suitable for fast switching, signal contact...

Failure analysis of Delta inverter VFD-VL series Failure analysis of Delta inverter VFD-VL series

Fault 1: Overcurrent in acceleration Clarification: Overcurrent in acceleration Solution 1: Check whether the wiring from U-V-W to the motor is poorly insulated; 2: Increase acceleration and deceleration time; 3: Replace the inverter with a larger output capacity; 4: Reduced (P54) torque ...

Reduce the failure rate of Delta's inverters Reduce the failure rate of Delta's inverters

Daily View Item 1: Check whether the sound of the motor changes abnormally during operation, including whether there is vibration during the operation of the motor. Project 2: Check if the environment of the inverter unit has changed. For example, whether the ambient temperature is normal. Familiar with Delta's inverter ...

Delta's inverter energy-saving method Delta's inverter energy-saving method

Delta's inverter energy-saving method is mainly manifested in the application of fans, pumps, and hoists. In order to ensure the reliability of production, all kinds of production machinery are designed with power drive, and there is a certain amount of surplus. Power Factor Supplement ...

PLC control belt conveyor soft start method - Delta PLC control belt conveyor soft start method - Delta

Belt conveyor is a kind of continuous conveyor, which is one of the most important types of stationary or escorted cranes. The belt conveyor is the use of friction to convey the dynamics, with belts, steel belts, steel fiber belts and chemical fiber belts as a kind of adaptation to the transmission of materials and traction operations.

Introduction to Delta's PLC maintenance knowledge Introduction to Delta's PLC maintenance knowledge

1. Delta's PLC power on running light does not light up, and the ERROR flashes, the reason may be: no program 2. Delta's PLC cannot communicate with the computer, which may be: RS23 port is broken 3. Delta's PLC power light does not light up: The power supply is bad ...

Delta's inverter power-on debugging method Delta's inverter power-on debugging method

After the inverter is installed, disconnect the output of the inverter, use the diode file of the digital meter to measure the input and output of the inverter before the power is not turned on, ensure that there is no short circuit, and then turn on the working power supply of the inverter.

How to choose Delta's power supply How to choose Delta's power supply

  1. First of all, calculate the maximum power consumption of the computer The power consumption of the computer is different in different operating states, such as 95W on startup, 35W on standby, and up to 480W when the game is fully loaded. The power consumption of the power supply is based on the computer ...

Instrument classification standard - Delta Instrument classification standard - Delta

The appearance of the instrument is a comprehensive product of a variety of science and technology, with a wide variety of varieties, wide application, and constantly updated, with a variety of classification methods. According to the intention and use of the use of the main measuring instrument, car appearance, tractor appearance, marine appearance, aviation appearance, navigation instruments, control instrument ...

PLC Peripherals – Delta PLC PLC Peripherals – Delta PLC

Programming equipment: simple programmer, most only accept mnemonic programming, and some can also be programmed graphically (such as Japan's Toshiba EX programmable controller). The cluttered one has a graphical programmer, which can be programmed in the trapezoidal language. Some also have dedicated computers that can be used for other ...

Delta's touch screen downloads programs and communication settings Delta's touch screen downloads programs and communication settings

1. Touch screen download program (1) Device software DOPSoft; (2) The communication line uses a square port data line; (3) device drive; (4) Configuration screen; (5) In the Stuff, select Download All Materials. 2. Communication settings (1) Touch screen settings ...

Precautions before installation of Delta inverters Precautions before installation of Delta inverters

Delta's inverter should be thoroughly inspected for initial installation or long-term use. The items and methods to check are as follows: 1) Check whether the Delta inverter is damaged, whether the metal parts are rusty, and whether there is frost. If there is frost and condensation, it should be dry for 4 hours (60°C) or in ...

Delta's servo drive ASDA-B2-F motion control alarm Delta's servo drive ASDA-B2-F motion control alarm

Abnormal alarm indication Abnormal alarm title Abnormal alarm action content Sweeping method Indicate DO servo status Switch AL111 DMCNET Packet Receive Overfill Rx Buffer Overfill (more than two DMCNET packets received within 1 millisecond) ALM ON AL185 DMCNET Bus Hardware ...

The principle of Delta's inverter inverter The principle of Delta's inverter inverter

As far as I know, since the advent of active induction motors, there has been a variable frequency operation in the way of communicating generators. Change the rotational speed of the generator, and change its output frequency. Before the advent of high-speed transistors, this was one of the main ways to change the speed of the motor, but due to the decrease in the speed of the generator ...

How to use Delta's inverter operation How to use Delta's inverter operation

(1) When the speed of the motor is controlled by the Delta inverter, the noise and temperature rise of the motor are higher than that of the frequency of the motor. When the motor is running at low speed, because the speed of the motor blades is low, the temperature rise of the motor becomes high.

The impact of inverters on motors – Delta inverters The impact of inverters on motors – Delta inverters

1. Overvoltage The output of the inverter has the function of voltage detection, and the inverter can actively adjust the output voltage so that the motor does not withstand overvoltage. Even when the output voltage adjustment fails and the output voltage exceeds 110% of the normal voltage, the inverter will be shut down and the motor will become infected. ...

Precautions for cleaning dust in the inverter - Delta Precautions for cleaning dust in the inverter - Delta

1. Each VFD should be cleaned and protected once a quarter. Protecting and cleaning equipment must have specific records and the signature of the person in charge. As long as the management is in place, the task can be completed with quality and quantity; 2. Before cleaning, the power supply must be blocked, and the voltage must be reduced to a safe voltage before starting to work. ...

Delta's servo protection parameters are written Delta's servo protection parameters are written

A3, B3 servo P5-97 Motion Control Mobilization Commands 0x0003 Maintenance Activation (Successful Return 0x1003) 0x0004 Maintenance Waiver (Successful Return 0x1004) If the wrong cipher code is entered, the error code Ennn will be sent back to exempt the loss, during which nnn indicates that there is a ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top