First, the selection of output module
The output modules are divided into transistors, triacs, and contact types:
(1) The switching speed of the transistor type is fast (generally 0.2ms), but the load can be small, about 0.2-0.3A, 24VDC, suitable for fast switching, signal contact equipment, generally connected with frequency conversion, DC equipment and other signals, should pay attention to the impact of transistor leakage current on the load.
(2) The advantage of the thyristor type is that it has no contact and has the characteristics of communication load, so the load can not be large.
(3) The relay output has the characteristics of AC and DC load, and the load can be large. In conventional control, relay contact output is generally used, and the disadvantage is that the switching speed is slow, generally about 10ms, which is not suitable for high-frequency switching applications.
2. Other matters to be paid attention to
(1) Do not connect the communication power cord to the input terminal, so as not to burn out the PLC;
(2) The grounding terminal should be grounded independently, not connected in series with the grounding terminal of other equipment, and the cross-sectional area of the grounding wire should not be less than 2mm²; (3) The auxiliary power supply is small and can only drive the equipment with small power (photoelectric sensors, etc.);
(4) Some PLCs have a certain number of occupancy points (i.e., empty address terminals), do not connect the wires;
(5) When there is no maintenance in the PLC output circuit, the fuse and other maintenance equipment should be used in series in the external circuit to avoid damage caused by short circuit of the load.
3. Disturbance treatment
The environment of the industrial site is relatively harsh, and there are many high and low frequency disturbances. These disturbances are typically introduced into the PLC via cables connected to the field device.
In addition to grounding measures, attention should be paid to the adoption of anti-disturbance measures in the design selection and laying of cables:
(1) The imitation signal is a small signal, which is very susceptible to the influence of external disturbance, and a double-layer shielded cable should be selected;
(2) High-speed pulse signals (such as pulse sensors, digital disks, etc.) should be shielded cables, which not only avoid external disturbance, but also avoid the disturbance of high-speed pulse signals to low-level signals;
(3) The frequency of communication cables between PLCs is high, and the cables supplied by the manufacturer should generally be selected, and in the case of low requirements, twisted pair cables with shielding can be selected;
(4) The imitation signal line and DC signal line cannot be routed in the same line slot as the communication signal line;
(5) It is necessary to grounding the shielded cable introduced in the control cabinet, and it should not be directly connected to the equipment through the terminal;
(6) Communication signals, DC signals and analog signals cannot share a single cable, and the power cable should be laid separately from the signal cable.
(7) During on-site maintenance, the solutions to the disturbance are: the disturbed line is shielded and laid from scratch; Participate in the anti-disturbance filtering code in the program.
Fourth, eliminate the capacitance between the lines to avoid malfunction
There is a capacitance between the wires of the cable, and a qualified cable can constrain this capacitance within a certain range.
Even if the cable is qualified, when the cable length exceeds a certain length, the capacitance value between the wires will exceed the required value, and when the cable is used for PLC input, the capacitance between the lines may cause PLC malfunction, and many incomprehensible phenomena will appear.
These phenomena are mainly manifested as: the wiring is correct, but the PLC has no input; There are no inputs that the PLC should have, but there are no inputs that should not have, that is, the PLC inputs disturb each other. To address this problem, it is necessary to:
(1) Cables twisted together with cable cores;
(2) Shorten the length of the cable as much as possible;
(3) Separate the input cables that disturb each other;
(4) Use shielded cables.
5. Grounding problem:
The grounding requirements of the PLC system are relatively strict, and it is good to have an independent special grounding system, and it is also necessary to pay attention to other equipment related to PLC to be reliably grounded. When multiple circuit addresses are connected together, unexpected currents can occur, causing logic errors or damage to the circuit. When devices that are far apart are connected by communication cables or sensors, the current between the cable and the ground will flow through the entire circuit, and even over a short distance, the load current of a large device can change between it and the ground potential, perhaps through electromagnetic action. Between incorrectly connected power supplies, there is a potential for a devastating current to occur in the circuit, which can damage the device. The PLC system generally uses a one-point grounding method. In order to improve the ability to resist common mode disturbance, the shielding floating skill can be used for the imitation signal, that is, the shielding layer of the signal cable is grounded at one point, the signal loop is floating, and the insulation resistance with the ground should not be less than 50MΩ.
|
More on that
|
Problems with Delta's compact pressure transmitters
1. The transmitter does not return to zero under no pressure?
Answer: The cleaning method is to remove the transmitter from the device position, investigate whether the zero position is normal, and replace the pipeline sealing ring if it is normal. Check together whether the transmitter is perpendicular to the piping assembly, and if not, adjust the transmitter zero.
...
|
|
Description of Delta inverter problems and solutions
Problem Description:
What is stall avoidance?
Solution(s):
If the given acceleration and deceleration time is too short, the output frequency of the inverter changes faster than the motor speed, and the inverter will stop working due to overcurrent, which is called stalling. In order to make the motor ...
|
|
The difference between a general-purpose inverter and a vector inverter - Delta
There are two main differences between vector inverter and general inverter, the first is high control accuracy, and the other is high output torque at low speed. It can output 150%-200% of the rated torque. It should be vector frequency conversion is to decompose the motor current into D-axis current and Q-axis current, where D-axis current is excitation current ...
|
|
Introduction to Delta's PLC maintenance knowledge
1. Delta's PLC power on running light does not light up, and the ERROR flashes, the reason may be: no program
2. Delta's PLC cannot communicate with the computer, which may be: RS23 port is broken
3. Delta's PLC power light does not light up: The power supply is bad
...
|
|
Replaced by discontinued models of Delta inverters
Delta's new generation of compact and efficient vector-controlled inverter MH300, adhering to the good driving function of Delta's inverter, has six advantages: compact size, flexible application, stable system, reliable quality, and easy installation.
|
|
PLC Peripherals – Delta PLC
Programming equipment: simple programmer, most only accept mnemonic programming, and some can also be programmed graphically (such as Japan's Toshiba EX programmable controller). The cluttered one has a graphical programmer, which can be programmed in the trapezoidal language. Some also have dedicated computers that can be used for other ...
|
|
The principle structure of low-voltage circuit breaker - Delta
Low-voltage circuit breakers, commonly known as active air switches, are one of the primary electrical switches in low-voltage distribution networks. It can not only turn on and off normal load current, motor operation current and overload current, but also turn on and off short circuit current.
It is mainly used as a low-voltage distribution line or a switch cabinet that is not often operated ( ...
|
|
Analysis of abnormal operation of Delta inverter
There are many setting parameters of the inverter, each parameter has a certain selection range, and the phenomenon that the inverter can not operate normally is often encountered in the application due to the improper setting of a single parameter, so the relevant parameters must be set correctly.
...
|
|
Delta's inverter model selection
1. VFD-B series
This series has a variety of communication voltage standard model options, in addition to providing a variety of I/O signal functions, and can supply the appropriate current and voltage vector value according to the external load torque, to meet the needs of customers with high quality and low price.
...
|
|
Precautions for the inverter installation environment – Delta
(1) Ambient temperature:
Like other electronic equipment, the inverter has certain requirements for the ambient temperature, which is generally "-10-+40°C". Because the inverter is a high-power electronic equipment, it is very easy to be affected by the working temperature, but in order to ensure the safety of the inverter's work.
|
|
A brief introduction to Delta's inverters and their models
Delta's VFD drives have now established a wide range of brand awareness in the industrial automation market. Each series of products is designed for different operation needs such as torque, loss, overload, overspeed work, etc., and is adjusted according to different industrial machinery attributes; It can provide customers with a variety of choices, and a wide range of ...
|
|
How to use Delta's inverter operation
(1) When the speed of the motor is controlled by the Delta inverter, the noise and temperature rise of the motor are higher than that of the frequency of the motor. When the motor is running at low speed, because the speed of the motor blades is low, the temperature rise of the motor becomes high.
|
|
Introduction to the common sense of Delta inverter
The low-voltage fuse cannot be used as an overload maintenance for the motor.
It is necessary that the additional voltage of the fuse is greater than or equal to the operating voltage of the distribution line.
The additional current of the fuse must be greater than or equal to the additional current of the melt.
...
|
|
Analysis of communication problems of Delta inverters
Problem Clarification:
Communication Transmission Timeout: The Modbus transmission between the VFD and the Keypad times out
Solution:
VFD does not respond to Keypad's communication commands.
1. Confirm the communication quality of the communication wiring and contacts.
2. Please use the RESET key to clear the Fault ...
|
|
Misunderstandings in the application of Delta inverters
The capacity selection of the inverter is based on the rated power of the motor
Myth: The capacity selection of the inverter is based on the rated power of the motor
Compared with the electric motor, the price of the inverter governor is more expensive, so it is important to ensure that the ...
|
|
Delta's active front-end inverter partner
The ubiquity of AC drives brings significant energy savings to industrial applications. However, the high-frequency switching signal generated by the inverter is easy to form electromagnetic disturbance, which affects the power quality. It is especially significant in occupations with large loads such as lifting and elevators.
At this time, the inverter ...
|
|
Servo motor speed improvement method - Delta
When many engineers debug servo motors, they often have such a problem: why is my servo motor so slow, how can I improve the speed, and how much can the maximum speed reach? The basis for the confirmation of the speed method of the servo motor: the speed of the servo motor.
...
|
|
Delta's high-performance servo ASDA-A3 series is a new product
With the rapid development of automation technology and shopping malls, customers have higher and higher requirements for the speed, accuracy and function diversification of servo products. In order to get used to the needs of shopping malls, recently, Delta launched the high-performance motion control high-end AC servo system ASDA-A3 series ...
|
|
The reason for the shaking of the inverter for the motor - Delta
When using the motor dragged by the inverter, sometimes the motor flutters and the over-fire flutter may burn out the motor and cause immeasurable losses. So what is the reason for this phenomenon?
1. The motor is damaged ...
|
|
Delta inverter repair steps
Delta inverters still have a certain influence in the industry, but even if the reputation is good, it will inevitably show some failures. Let's take a look.
...
|
|