Abnormal alarm indication Abnormal alarm title Abnormal alarm action content Sweeping method Indicate DO servo status Switch

AL111 DMCNET Packet Receive Overfill Rx Buffer Overfill (more than two DMCNET packets received within 1 millisecond) ALM ON

AL185 DMCNET Bus Hardware Anomaly DMCNET Bus Disconnection ALM ON

AL201 DMCNET Data Initial Error An error occurs when the EEPROM loads the data. Re-energize WARN ON

AL235 Azimuth Command Overfill The azimuth command counter is overloaded, and then the absolute addressing command is executed The host computer issues a strange alarm reset WARN ON

AL245 Positioning Timeout Positioning Instruction Fulfillment Exceeds Time Limit Ditto WARN ON

AL283 Software Forward Limit The azimuth command is greater than the software forward limit and actively clears the WARN ON after disengagement

AL285 Software Reverse Limit The azimuth command is less than the software reverse limit and actively clears the WARN ON after disengagement

AL289 Azimuth Counter Overflow The Bearing Command Counter Generates an Overflow The upper computer issues a different alarm reset WARN ON

AL301 DMCNET Synchronization Failure DMCNET mode and host computer synchronization failure Same as above WARN ON

AL302 DMCNET Sync Signal Too Fast DMCNET Sync Signal Received Too Early Ditto WARN ON

AL303 DMCNET Synchronization Signal Timeout DMCNET's Synchronization Signal Not Received Within the Time Limit Ditto WARN ON

AL304 DMCNET IP INSTRUCTION FAILS INSTRUCTION CANNOT BE TRANSMITTED IN DMCNET MODE DITTO WARN ON

AL555 System Failure Drive Processor Abnormal None None Switching

                           Delta's servo drive ASDA-B2-F motion control alarm

More on that
The technical advantages of the three-axis positioner - Delta The technical advantages of the three-axis positioner - Delta

1. The welding station is actively handed over, and the operator has been loading and unloading parts in a fixed position, which effectively reduces the labor and logistics intensity of the operator, and the welding products of the whole set of equipment have strong compatibility and strong automatic welding scalability. 2. All ...

Principles of daily protection and maintenance of Delta inverters Principles of daily protection and maintenance of Delta inverters

1. Record the operation data and shortcomings of the Delta: The operation data of the Delta inverter and the motor should be recorded every day, including the output frequency, output current, output voltage, DC voltage inside the inverter, radiator temperature and other parameters, and compare them with reasonable data, so as to facilitate early detection of defects.

Analysis and correction of the cause of Delta servo drive alarm Analysis and correction of the cause of Delta servo drive alarm

Analyze and correct the cause of Delta servo drive alarms.   Control current and undervoltage protection. Alert Number: 11. Reason: The voltage at the end of the dynamic DC bus is lower than the specified value. Due to the instantaneous shortage of power supply capacity, the control voltage is too low. Measure: Measure the DC bus ...

Basic parameter setting of special inverter for wind turbine - Delta Basic parameter setting of special inverter for wind turbine - Delta

1. Control mode: i.e. speed control, torque control, PID control or other methods. After the control method is adopted, static or dynamic identification should generally be carried out according to the control accuracy. 2. Minimum operating frequency: That is, the minimum speed of the motor. When the motor is working at low speed, the ...

Precautions for the inverter installation environment – Delta Precautions for the inverter installation environment – Delta

(1) Ambient temperature: Like other electronic equipment, the inverter has certain requirements for the ambient temperature, which is generally "-10-+40°C". Because the inverter is a high-power electronic equipment, it is very easy to be affected by the working temperature, but in order to ensure the safety of the inverter's work.

Delta's inverter power-on debugging method Delta's inverter power-on debugging method

After the inverter is installed, disconnect the output of the inverter, use the diode file of the digital meter to measure the input and output of the inverter before the power is not turned on, ensure that there is no short circuit, and then turn on the working power supply of the inverter.

How to choose Delta's power supply How to choose Delta's power supply

  1. First of all, calculate the maximum power consumption of the computer The power consumption of the computer is different in different operating states, such as 95W on startup, 35W on standby, and up to 480W when the game is fully loaded. The power consumption of the power supply is based on the computer ...

The reason for the low voltage trip of the inverter - Delta The reason for the low voltage trip of the inverter - Delta

The low voltage of the inverter mainly refers to the low voltage of the central DC circuit, and the reasons for the low voltage of the central DC circuit generally come from two aspects: ​ (1) Low voltage from the input side of the power supply The power supply under normal conditions ...

Ways to reduce the failure rate of Delta drives Ways to reduce the failure rate of Delta drives

If you want to reduce the fault rate of Delta inverter, it is necessary to check it daily, and what are the detailed items? Delta inverter fault repair ...

The inverter needs to be equipped with a braking resistor-Delta The inverter needs to be equipped with a braking resistor-Delta

The inverter is equipped with a braking resistor, mainly to consume part of the energy on the DC bus capacitor through the braking resistor to avoid the voltage of the capacitor being too high. Theoretically, if the capacitor stores a lot of energy, it can be used to release it to drive the motor to avoid energy waste, but the capacity of the capacitor is limited.

Solution to Delta inverter fault CE1 and CE2 Solution to Delta inverter fault CE1 and CE2

Product range: CP/CH/CT/C2000/C200/MS300/MH300/VE/ED/VJ Problem Code: CE1 Problem Description: Communication is abnormal Solution: 1. Communication error: RS-485 Modbus function code may be faulty ...

The basic control loop of Delta's inverter The basic control loop of Delta's inverter

There are two fundamental circuits for communicating with external signals: analog and digital: 1. 4-20mA current signal loop (imitation); 1 - 5V/0 - 5V voltage signal loop (imitation). 2. Switch signal circuit, inverter start and stop command, forward rotation command, etc.

Delta's key steps in inverter maintenance Delta's key steps in inverter maintenance

First, the maintenance of the inverter must first check whether the sound in the operation of the motor is abnormal, including, whether the motor is in operation to form a sensation. ​ 2. Check whether the natural environment of the inverter installation has changed. ...

Introduction to Delta's PLC maintenance knowledge Introduction to Delta's PLC maintenance knowledge

1. Delta's PLC power on running light does not light up, and the ERROR flashes, the reason may be: no program 2. Delta's PLC cannot communicate with the computer, which may be: RS23 port is broken 3. Delta's PLC power light does not light up: The power supply is bad ...

Delta unveiled the ASDA-A2 series of AC servo motors and drives Delta unveiled the ASDA-A2 series of AC servo motors and drives

New Delhi, September 2, 2010 – Delta Group, the world's largest supplier of switching power supplies and brushless DC fans, is committed to innovation, energy efficiency and environmental protection, and has launched a new and advanced high-performance ASDA-A2 series of servo motors and servo drives for motion control and networking in India.

Touch screen controls the inverter step – Delta Touch screen controls the inverter step – Delta

1. The touch screen is controlled by PLC inverter 1. At present, the general control of the inverter needs to choose PLC to communicate with the inverter, read the information of the inverter, and then the touch screen communicates with the PLC to complete the control of the inverter to start, stop, and monitor the operation of the inverter.

Advantages and disadvantages of Delta's open-loop and closed-loop control Advantages and disadvantages of Delta's open-loop and closed-loop control

1. Open-loop control There is no reverse connection between the controller and the controlled target, and the control is carried out in one direction. Strengths: Simple, stable and reliable. If the characteristics and parameter values of the components that make up the system are relatively stable, and the external disturbance is small, the open-loop control energy Enough...

Solution: Delta's inverter operation error Solution: Delta's inverter operation error

There are many setting parameters of the inverter, each parameter has a certain selection scale, and the inverter can not work normally due to the improper setting of a single parameter is often encountered in the application, therefore, the relevant parameters must be set correctly. ...

Inverter optocoupler device type - Delta Inverter optocoupler device type - Delta

1. One is a triode type photocoupler, such as PC816, PC817, 4N35, etc., which is commonly used in the output voltage sampling and error voltage amplification circuit of the switching power supply circuit, and is also used in the digital signal input loop of the inverter control terminal. The structure is the simplest, and the input side consists of a light-emitting two...

Delta's Ultron NT series UPS escorts flight safety at international airports Delta's Ultron NT series UPS escorts flight safety at international airports

The rapid development of the national economy has opened up a broad shopping mall space for the growth of the civil aviation industry. In order to meet the surge in the number of flights, an international airport in Northwest China has invested in the third phase of the expansion project, and has been listed as the "number one project" for civil aviation development and the "benchmark demonstration project" for national civil aviation.

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top