(1) The E end of the high-voltage inverter should be connected to the shell of the control cabinet and the motor, and should be connected to the ground, and the grounding resistance should be less than 100Ω, which can absorb surge interference.

(2) The input or output of the high-voltage inverter is equipped with an inductive magnetic ring filter. Flatness and 3-4 turns, which helps to suppress higher harmonics (this method is simple and inexpensive).

(3) The above-mentioned magnetic ring filter can also be wound on the incoming line of the control signal end of the high-voltage inverter or the given end of the analog signal according to the field situation.

(4) In the electric control cabinet equipped with high-voltage inverter, the power line and signal line should be separated from the pipe and wire, and the metal hose should be well grounded.

(5) The analog signal line should be shielded wire, and the single-ended should be connected to the simulated ground at the high-voltage inverter.

(6) The interference can also be improved by adjusting the carrier frequency of the high-voltage inverter. The lower the frequency, the less interference, but the greater the electromagnetic noise.

(7) The RS485 communication port must be connected to the host computer by photoelectric isolation transmission mode to improve the anti-interference performance of the communication system.

(8) The power supply of the external computer or instrument should be separated from the power supply of the power unit of the high-voltage inverter, and an internal transformer should be avoided as much as possible.

(9) Independent shielding should be carried out in the interference of the instrument equipment, and the thermostat, PID regulator, PLC, sensor or transmitter and other instruments on the market should be equipped with a metal shielding shell and connected to the security ground. If necessary, the above-mentioned inductive magnetic ring filter can be installed at the power inlet end of such instruments.
Megmeet inverter - a common measure for anti-interference of high-voltage inverters

More on that
Common faults and solutions of Megmeet PLC Common faults and solutions of Megmeet PLC

1. Do not execute the program: The input check is identified by the input LED indicator or the input monitor composed of a writer. When the input LED is not lit, it can be preliminarily determined that the external input system is faulty, and then check with the multimeter. If the output voltage is not normal, it can be determined that ...

Megmeet PLC - What places should be avoided when installing PLC control? Megmeet PLC - What places should be avoided when installing PLC control?

(1) The ambient temperature exceeds the range of 0-50 °C; (2) The relative humidity exceeds 85% or there is dew condensation (caused by sudden temperature changes or other factors); (3) direct sunlight; (4) There are corrosive and flammable gases, such as hydrogen chloride, ...

Megmeet inverter - common faults and treatment methods of high-voltage inverters Megmeet inverter - common faults and treatment methods of high-voltage inverters

The high-voltage inverter has a highly intelligent computing level and a perfect fault detection circuit, and can provide accurate positioning of all faults, and make clear instructions on the main control interface. In practical application, we find that common faults can be divided into abnormal control channels, IGBT overcurrent, overvoltage...

Megmeet PLC common faults Megmeet PLC common faults

1. External equipment failure. Such faults come from external devices such as various sensors, switches, actuators, and loads. The failure of this part of the equipment will directly affect the control function of the system. This type of failure is usually caused by the quality and longevity of the equipment itself. 2. System failure ...

Megmeet inverter - the selection principle and precautions of the inverter Megmeet inverter - the selection principle and precautions of the inverter

1. Select the inverter according to the load characteristics A: Fans and pumps are the most common loads: the requirements for the inverter are the simplest, as long as the inverter capacity is equal to the capacity of the motor (air compressors, deep water pumps, sediment pumps, and fast-changing music fountains need to increase their capacity). ...

Megmeet Inverter - Summary of Common Faults of High Voltage Inverter (21-32) Megmeet Inverter - Summary of Common Faults of High Voltage Inverter (21-32)

21。 The unit is overheating The radiator in the unit is equipped with a temperature switch (normally closed point), and when the temperature exceeds 85°C, the normally closed point of the temperature relay is disconnected, and the unit is overheated and faulty. Check whether the cabinet top fan is working properly, whether the unit cabinet fan switch is tripped, and whether the filter screen is blocked.

The application of Megmitte industrial control products in high-speed precision CNC machine tools The application of Megmitte industrial control products in high-speed precision CNC machine tools

With the rapid development of the machinery manufacturing industry, the traditional general machine tool can no longer meet the changing parts processing needs of the shopping mall. CNC machine tools have undeniably become the mainstream processing equipment of today's machinery manufacturing. In response to the special application needs of the machine tool industry, Megmeet has launched the MV series of high-function ...

Hollysys edge intelligent controller and edge intelligent all-in-one machine launched new products Hollysys edge intelligent controller and edge intelligent all-in-one machine launched new products

Transportation power, urban rail responsibility. With the vigorous development of emerging technologies such as 5G, cloud computing, big data, and artificial intelligence, more innovative technologies are accelerating the empowerment of urban rail transit, and smart urban rail is ushering in a "golden age" of development. As a deep cultivator in the field of smart urban rail, Hollysys adheres to technological innovation.

Megmeet PLC – the three output types of PLC Megmeet PLC – the three output types of PLC

The first is relay output, the relay output response speed is slow, the output current is large, generally can reach 2A, but the electric shock life is short, the output frequency is low, the maximum is 1HZ; The second is transistor output, the transistor output response speed is fast, the output current is small, and the contact life is relatively small.

Megmeet welding machines – the main application area of resistance welding Megmeet welding machines – the main application area of resistance welding

(1) Spot welding: The weldment is pressed between the two cylindrical electrodes, heated by electricity, so that the weldment melts at the contact to form a nugget, and then the power is cut off, and it solidifies and crystallizes under pressure to form a dense solder joint. Spot welding is suitable for welding thin plates (laps) and steel bars below 4 mm.

Megmeet inverter - the speed regulation method of high-voltage inverter Megmeet inverter - the speed regulation method of high-voltage inverter

1. Hydraulic coupling method. That is, a hydraulic coupling device is inserted between the motor and the load in series, and the size of the coupling force between the motor and the load is adjusted by the height of the liquid level, so as to realize the speed adjustment of the load; 2. Cascade speed regulation. Tandem speed regulation must use a wound asynchronous motor, and the rotor ...

Megmeet PLC – System integration for PLC Megmeet PLC – System integration for PLC

In the manufacturing industry, there are a large number of open-loop sequential control based on switching quantities, which carries out sequential action numbers according to logical conditions and operates in chronological order; In addition, there is the control of chain protection actions according to the logical relationship that is not related to the sequence and timing; As well as a large number of switching quantities, pulse quantities, gauges...

Megmeet inverter - what are the control methods of the inverter? Megmeet inverter - what are the control methods of the inverter?

Sinusoidal Pulse Width Modulation (SPWM) control mode It is characterized by simple structure of control circuit, low cost, good hardness of mechanical characteristics, and can meet the smooth speed regulation requirements of general transmission, and has been widely used in various fields of industry. However, this type of control is at low frequencies, ...

Introduction to Megmeet welding machine Introduction to Megmeet welding machine

The EhaveCM350AR is a fully digital inverter melting multi-functional industrial heavy-duty Megmeet welding machine launched by Megmeet for global metalworking manufacturing. It brings customers higher quality and higher efficiency welding experience and value with excellent arc characteristics, reliability and high efficiency, and helps customers ...

Megmeet inverter - precautions for inverters at high temperatures Megmeet inverter - precautions for inverters at high temperatures

1. Carefully monitor and record the display parameters on the man-machine interface of the inverter, and reflect the abnormality immediately; 2. Carefully monitor and record the ambient temperature of the frequency conversion room, and the ambient temperature should be between -5 °C and 40 °C. The temperature rise of the phase-shifting transformer should not exceed 130°C; 3. Summer ...

Megmeet PLC – The importance of PLC industrial gateways Megmeet PLC – The importance of PLC industrial gateways

1. Realize remote control of industrial field equipment; 2. The PLC industrial gateway realizes remote upgrade of equipment firmware, downloads the program, and can flexibly access various equipment management platforms; 3. Realize remote control of industrial site touch screen and remote mapping of configuration screens; 4. PLC industry ...

Megmeet MC100 series plc – the right hand man in refrigeration equipment Megmeet MC100 series plc – the right hand man in refrigeration equipment

First, the process requirements When the low-pressure pressure collected by the system is greater than the upper low-pressure pressure set by the touch screen, the compression time will be loaded according to the set loading time, and the lower pressure will be reduced according to the set load reduction time. The high pressure collected is greater than that on the high pressure ...

Megmeet inverter - how to choose the inverter? Megmeet inverter - how to choose the inverter?

1. Understand the type of variable frequency load The correct selection of the frequency converter is very critical for the proper operation of the control system. When selecting a frequency converter, it is important to fully understand the load characteristics driven by the frequency converter. In practice, production machinery is often divided into three types: constant torque load, constant ...

Megmeet inverter mv600 alarm code ENOC2 Megmeet inverter mv600 alarm code ENOC2

1. If there is a sharp acceleration or deceleration, please extend the acceleration and deceleration time. 2. Avoid rapid increase in load. 3. Check whether there is a short circuit in the UVW of the motor terminal. 4. The module is damaged, and the drive circuit is damaged, resulting in an overcurrent alarm. ...

Megmeet PLC - the core components of PLC introduction Megmeet PLC - the core components of PLC introduction

(1) Central Processing Unit (CPU) The central processing unit (CPU) is the control center of the PLC. It accepts and stores user programs and data typed from the programmer, checks the status of the power supply, memory, I/O and alert timer in accordance with the functions assigned by the PLC system program, ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top