21。 The unit is overheating

The radiator in the unit is equipped with a temperature switch (normally closed point), and when the temperature exceeds 85°C, the normally closed point of the temperature relay is disconnected, and the unit is overheated and faulty.

Check whether the fan on the top of the cabinet is working normally, whether the fan switch of the unit cabinet is tripped, and whether the filter screen is blocked (take a piece of A4 paper and put it on the filter screen to see if it can be adsorbed, otherwise the filter screen needs to be cleaned); Whether it works in an overload state for a long time, whether the ambient temperature is too high (the ambient temperature should be lower than 45 °C, otherwise it is necessary to strengthen ventilation), install a ventilator on the wall or install an air duct or refrigeration equipment on the top of the cabinet;

The unit control board is broken, and finally check whether the power unit temperature relay is normal.

22。 The unit is overpressurized

The DC bus voltage exceeds the protection value, and the inverter reports that the unit is overvoltage.

When the inverter is running, if the output voltage of a unit is low, it will cause the three-phase output to be unbalanced, and the unit will be overvoltaged; During the commissioning of the no-load motor, it is easy to overvoltage the DC bus and the overvoltage of the A1/B1/C1 unit, at this time, the reference voltage can be appropriately lowered.

Check whether the input high-voltage power supply exceeds the allowable maximum value (when the supply voltage is too high, the transformer tap can be adjusted to 105%);

If there is an overvoltage during the deceleration process, please increase the deceleration time setting value of the inverter appropriately.

23。 Fiber failure

When the system fails to detect unit communication in the power-on state, the optical fiber fault is reported. The power unit controls whether the power supply is normal (when normal, the green indicator light is on), otherwise replace the power unit; Whether the fiber optic connector of the power unit and controller has fallen off and whether the optical fiber has been broken.

24。 Unit bypass

When the hardware of the unit is configured with a bypass, and the number of bypass stages in the parameter setting is non-zero, if the unit has three faults: drive failure, fuse failure, and unit overheating, the unit bypass will occur.

If a unit fails and is bypassed, the other two units in the same position will also be bypassed, at this time, the inverter can still start and run, but due to the reduction of the number of series units per phase, the rated output voltage and rated capacity will be reduced. When the unit bypass occurs, the cause must be identified, and the faulty unit must be shut down as soon as possible to replace (the remaining two-phase bypassed unit does not need to be replaced);  Clean up the unit driver board and unit control board, if the dust collection of these two circuit boards is too thick, it may cause false alarms.

25。 The operating frequency is not consistent with the given frequency

There are several reasons for this situation: In the process of acceleration and deceleration, limited by the acceleration and deceleration time, there is a process for the output frequency to reach a given frequency;

When the system voltage is too high, the frequency converter cannot stay at a numerical point to avoid DC bus overvoltage protection due to the requirements of its own protection. At this time, it is recommended to connect the transformer tap to 105%; If the output current of the inverter exceeds the set current limiting current value, the inverter will automatically reduce the frequency to reduce the output current and avoid overcurrent protection tripping. This usually occurs when the input voltage is too low or the load bursts;

In the event of an instantaneous power failure, in order to maintain the motor in a controllable state, the inverter will automatically decelerate and obtain energy from the motor; A Hall element, cell detection board, or signal board is faulty.

26。 The monitor has a black screen

Press the system reset button on the cabinet door (the system reset will not affect the normal operation of the inverter); If it still cannot be recovered, check whether the power terminal of the monitor is off, whether the connection wire is loose, whether the 5V and 15V power supply are normal, and whether the monitor line is obviously damaged;

If there is interference, otherwise replace the monitor.

27。 Parameters cannot be modified

If the parameter modification option is set to Forbidden in a function parameter, all parameters except for the parameter and the given frequency or given parameter cannot be modified.

Most of the parameters cannot be modified during operation.

28。 The inverter automatically restarts after a shutdown

In remote control mode, the start and stop can only be done through the remote terminal.

If the starting mode in the parameter setting is level start (closed start, disconnected stop), the inverter will be automatically started and run when the emergency stop signal is disconnected or the inverter is stopped by other means during operation, but when the emergency stop signal is re-closed, because the remote start level signal is still there, the inverter will automatically start running.

29。 When the inverter is powered on, due to the excitation inrush current of the transformer and the charging of the unit capacitance, the instantaneous current effective value can reach up to 6-7 times of the rated current of the inverter, and the duration is tens of milliseconds; If the setting value of the upper current protection of the inverter is too small, it will cause the upper level switch quick break protection to trip.

Adjust the setting value of quick-break protection of the upper switch cabinet.

30。 The output frequency oscillates at low speed during start-up

At low speed, some motors fluctuate very much because of the influence of cogging effect, etc., and the inverter may have current limiting at this time, so that the inverter can accelerate, limit the current and decelerate, etc., and cannot accelerate normally.  Increase the current limit current setting; Reduced start-up time; If the output voltage of a unit is low, replace this unit;

31。 When the automatic bypass cabinet is automatically bypassed, the upper switch cabinet trips

Check whether the time of the delay pick-up time relay in the bypass cabinet is between 1.5S and 3S; Whether the setting value of the switch cabinet is too small (it should be more than 5 times the rated current of the motor); The quick-break protection time of the switch cabinet is set to be greater than 0.1S.

32。 The external terminal has an induced AC voltage

It may be remote start/stop, high-voltage breaking, system reset signal line induced voltage, it is recommended that the passive signal and the 220V AC power supply be wired separately, in this case, it is best to use the shielded wire to ground at both ends;

It may be that the signal line on the remote control box is tied together with the power line to cause the induced voltage, it is recommended to re-wire in the remote control box, and it is best to use the shielded wire for the signal without reason, and the shielded wire stripping wire should not be too long; The 4-20mA current signal has an AC induced voltage (below 10V), and can be connected between the current signal and ground with a 275V/0.33uf.
Megmeet Inverter - Summary of Common Faults of High Voltage Inverter (21-32)

More on that
Failure and maintenance of welding machines Failure and maintenance of welding machines

1. Damage to the welding power supply. Due to the high current and high voltage during welding, when the welding current exceeds 20% of the rated value, overcurrent protection will appear, so that the circuit will automatically cut off the power supply. In addition, if the welding time is too long, it can also cause overcurrent. Therefore, we should try our best to ...

Megmeet inverter – three ways to connect the PLC to the inverter Megmeet inverter – three ways to connect the PLC to the inverter

(1) Use the analog output module of PLC to control the analog output module of the inverter The analog output module of the PLC outputs 0-5V voltage signal or 4-20mA current signal, which is used as the analog input signal of the inverter to control the output frequency of the inverter. This control method is simple to wiring, but it needs to be selected and changed.

Megmeet PLC – Analysis of common failures of PLC Megmeet PLC – Analysis of common failures of PLC

1. The CPU is abnormal When the CPU is abnormally alarmed, check all the devices connected to the internal bus of the CPU unit. The specific method is to replace the potentially problematic units sequentially, find out the problematic units, and deal with them accordingly. Second, the memory is abnormal Memory anomaly alarm ...

Megmeet welding machine - the application and precautions for the use of butt welding machine Megmeet welding machine - the application and precautions for the use of butt welding machine

The butt welding machine should be settled indoors, and should have a reliable grounding or zero connection, when a plurality of butt welding machines are connected to each other, the distance from each other shall not be less than 3m, and they should be connected to different corresponding power grids, and should have their own knife switches. Before welding, the pressure of the butt welder should be checked and determined.

Megmeet PLC - What is the difference between PLC and servo control system Megmeet PLC - What is the difference between PLC and servo control system

1. The meaning of the representation is different: PLC is the abbreviation of planar optical waveguide (technology), the so-called planar optical waveguide, means that the optical waveguide is located in a plane. A servo control system is a feedback control system used to accurately follow or reproduce a certain process.

Megmeet PLC - the installation method and functional requirements of the PLC Megmeet PLC - the installation method and functional requirements of the PLC

Installation: The installation mode of PLC system is divided into centralized, remote I/O and distributed with multiple PLC networking. Centralized does not need to set up the drive remote I/O hardware, the system response is fast, and the cost is low; Remote I/O is suitable for large systems with a range of ...

Megmeet MC100 series plc – the right hand man in refrigeration equipment Megmeet MC100 series plc – the right hand man in refrigeration equipment

First, the process requirements When the low-pressure pressure collected by the system is greater than the upper low-pressure pressure set by the touch screen, the compression time will be loaded according to the set loading time, and the lower pressure will be reduced according to the set load reduction time. The high pressure collected is greater than that on the high pressure ...

Megmeet welding machine - the working principle of the spot welding machine and its advantages and disadvantages are introduced Megmeet welding machine - the working principle of the spot welding machine and its advantages and disadvantages are introduced

Safety operation procedures for spot welding machines: 1. Before operation, the oil stain of the upper and lower electrodes should be removed. After power-on, the body shell should be free of leakage. 2. Before starting, the steering switch of the control line and the small switch of welding current should be connected, the number of poles should be adjusted, and then the water source and gas source should be connected.

Introduction to Megmeet welding machine Introduction to Megmeet welding machine

The EhaveCM350AR is a fully digital inverter melting multi-functional industrial heavy-duty Megmeet welding machine launched by Megmeet for global metalworking manufacturing. It brings customers higher quality and higher efficiency welding experience and value with excellent arc characteristics, reliability and high efficiency, and helps customers ...

Megmeet inverters – seven areas of application for high-voltage inverters Megmeet inverters – seven areas of application for high-voltage inverters

1. Metallurgical industry - the application of high-voltage inverter in the metallurgical profession mainly includes plate and wire rod rolling mills, coilers, fans, slurry pumps, etc., with the primary intention of motor energy saving. 2. Electric power industry - China's power generation capacity ranks second in the world, second only to United States. The power profession is also changing.

The principle of Megmeet plasma cutting and its characteristics The principle of Megmeet plasma cutting and its characteristics

5) PLASMA The principle of plasma cutting is: arc discharge between the base metal (including the nozzle in the cutting torch) and the electric in the cutting torch, and use the discharge heat energy to make the compressed gas produce a high-temperature and high-speed plasma arc to fuse the cutting method of the base metal. The small hole of the nozzle ...

Megmeet inverter maintenance and testing method Megmeet inverter maintenance and testing method

Megmeet inverter maintenance and testing method   1. The Megmeet rectifier module is damaged It is usually caused by grid voltage or internal short circuit. In the case of sweeping internal short circuits, the rectifier bridge is replaced. When dealing with shortcomings on site, the user power grid should be checked. Such as electricity ...

Megmeet PLC - the connection method between the PLC and the server Megmeet PLC - the connection method between the PLC and the server

The first is that the PLC sends a start/stop signal to the server through the I/O point, and the server controls the operation of the servo motor. The PLC controls the operation/stop of the servo through the digital output, so as to achieve the purpose of controlling the servo motor. The second is through the pulse output of the PLC, which ...

Common faults of Megmeet drives and how to deal with them Common faults of Megmeet drives and how to deal with them

1. When the oscilloscope looks at the current monitoring output of the driver, it finds that it is all noisy and cannot be read Cause: The current monitoring output is not blocked from the AC power supply (transformer). Solution: You can use a DC voltmeter to detect and investigate. 2. Servo motor high speed ...

Megmeet welding machines – the main application area of resistance welding Megmeet welding machines – the main application area of resistance welding

(1) Spot welding: The weldment is pressed between the two cylindrical electrodes, heated by electricity, so that the weldment melts at the contact to form a nugget, and then the power is cut off, and it solidifies and crystallizes under pressure to form a dense solder joint. Spot welding is suitable for welding thin plates (laps) and steel bars below 4 mm.

Megmeet PLC - how the PLC communicates with the host computer Megmeet PLC - how the PLC communicates with the host computer

The PLC communicates with the host computer, and BlandC is used to write the communication program between the host and the PLC, and the COM1 port must be initialized, the baud rate is 9600bps, and the parity check bit adopts even check, and the seven-digit valid data is used. When the computer receives the response character ACK from the PLC, it ...

Megmeet welding machine - Classification and difference of laser spot welding machine Megmeet welding machine - Classification and difference of laser spot welding machine

Laser spot welding machine, also known as resistance welding machine, is usually divided into three categories according to the nature of the welding power source: 1. AC spot welding machine; 2. Energy storage spot welding machine; 3. DC spot welding machine. 1. AC spot welding machine Precision AC spot welding machine generally refers to the spot welding machine with a power of less than 16KVA.

Megmeet inverter - inverter braking mode and advantages and disadvantages introduction Megmeet inverter - inverter braking mode and advantages and disadvantages introduction

What are the braking methods of the inverter? Generally speaking, braking refers to the technical measures taken during the operation of the motor due to fault protection or man-made active shutdown, and the commonly used inverter braking methods include energy consumption braking, feedback braking, DC braking and DC feedback braking. ...

Megmeet Inverter - Precautions for the Use of Inverter (1-10) Megmeet Inverter - Precautions for the Use of Inverter (1-10)

1. The inverter must be selected correctly. 2. Read the product manual carefully, and wiring, installation and use in accordance with the requirements of the manual. 3. The inverter device should be reliably grounded, and the radio frequency interference should be suppressed to prevent the inverter from causing electric shock due to leakage. 4、 ...

Megmeet PLC – The importance of PLC industrial gateways Megmeet PLC – The importance of PLC industrial gateways

1. Realize remote control of industrial field equipment; 2. The PLC industrial gateway realizes remote upgrade of equipment firmware, downloads the program, and can flexibly access various equipment management platforms; 3. Realize remote control of industrial site touch screen and remote mapping of configuration screens; 4. PLC industry ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top