Common faults and solutions of Megmeet PLC

Create Date: 2024-8-30 12:03:23|Source: MEGMEET

1. Do not execute the program: The input check is identified by the input LED indicator or the input monitor composed of a writer. When the input LED is not lit, it can be preliminarily determined that the external input system is faulty, and then check with the multimeter.

If the output voltage is abnormal, it can be determined that the input unit is faulty. When the LED is on but the internal monitor is not displayed, it is considered to be a fault of the input unit, CPU unit, or expansion unit.

The program performs a check through a monitor check on the writer. When the contact status of the ladder diagram does not match the result, it is a program error (e.g., double use of internal relays, etc.), or a malfunction in the calculation part.

Output checks can be identified using the output LED indicator. If the calculation result is correct but the output LED indicates an error, it can be considered as a fault of the CPU unit or 1/0 interface unit. When the output LED is bright but there is no output, it can be determined that the output unit is faulty, or the external load system is faulty.

2. Some programs are not executed: the check method is the same as the previous item, but if the input time of the counter, step controller, etc. is too short, there will be no response failure, then the input time should be checked whether the input time is large enough, and the verification can be carried out according to the relationship between the input time < the * response time of the input unit + the operation scanning time multiplied by 2.

3. If the power supply is powered off for a short time, the program content will also disappear: in order to make the microprocessor start correctly, the PLC is equipped with an initial reset point circuit and a saving program circuit when the power supply is disconnected. When such a circuit fails, the program cannot be saved. Check the on/off of the available power supply.

4. The PROM cannot be operated: first check whether the PROM is inserted well, and then determine whether the chip needs to be replaced.

5. After the power supply is re-invested or reset, the action stops: this fault can be considered as caused by noise interference or poor internal contact of the PLC. The cause of noise is generally caused by the reduction of the capacitance of the small capacitor in the circuit board or the poor performance of the components, and the cause of the poor contact can be checked by gently tapping the PLC body. Also check the plugged in status of the cables and connectors.
Common faults and solutions of Megmeet PLC

More on that
Megmeet PLC – the three programming languages of PLC Megmeet PLC – the three programming languages of PLC

1. The ladder diagram language is the most commonly used programming language in PLC programming. The CPU reads physical input into a memory table, often referred to as an "input table". The form is evaluated for use in the procedure. Different platforms, using different types of registers; In each scan cycle, follow from left to right, ...

Megmeet inverter - the selection principle and precautions of the inverter Megmeet inverter - the selection principle and precautions of the inverter

1. Select the inverter according to the load characteristics A: Fans and pumps are the most common loads: the requirements for the inverter are the simplest, as long as the inverter capacity is equal to the capacity of the motor (air compressors, deep water pumps, sediment pumps, and fast-changing music fountains need to increase their capacity). ...

Megmeet PLC - the basic composition of PLC Megmeet PLC - the basic composition of PLC

a. Power supply The power supply of the PLC plays a very important role in the whole system. It can't work properly without a good and reliable power supply system, so PLC manufacturers also attach great importance to the design and manufacture of power supplies. General AC voltage fluctuations are +10% (+15%) ...

Solutions to common faults of Megmeet inverter (2) Solutions to common faults of Megmeet inverter (2)

Fault three Fault phenomenon: There is a rebound phenomenon when the rotation starts Solution: 1. Set the start frequency P08.02 and start frequency time P08.03 appropriately (such as P08.02=P08.03=0.5) 2. Appropriately reduce the stator resistance (P03.07) and no-load current value (P03.11 ...

Various welding methods for Megmeet welding machines Various welding methods for Megmeet welding machines

1) Hand arc welding (STICK) Shielded Arc Welding (abbreviated SMAW) in English, The principle is: the arc occurs between the coating electrode and the base metal, and the welding method of arc thermal ablation electrode and base metal is used. The outer layer of the electrode is covered with solder, which is dissipated in case of heat.

Megmeet PLC – the maintenance steps of the PLC control cabinet Megmeet PLC – the maintenance steps of the PLC control cabinet

1. Data backup When carrying out maintenance, we must cut off the power, data backup between power outages is an important link, for the data that needs to be archived for a long time, you can back up the historical trend data to the mobile hard disk, and then turn off the Windows-based operating system (Note...

Megmeet PLC - What is the difference between PLC and MCU? Megmeet PLC - What is the difference between PLC and MCU?

1. PLC is a relatively mature control system composed of single-chip microcomputer, which is the product of a mature and stable single-chip microcomputer application system that has been debugged. It is highly versatile. 2. The single-chip microcomputer can form a variety of application systems, and the application range is wider. In the case of a single "microcontroller", it ...

Megmeet inverter - the role and application of the inverter control cabinet introduction Megmeet inverter - the role and application of the inverter control cabinet introduction

Inverter control cabinet (inverter electrical control cabinet / electric control cabinet / electric control box) is an electrical control cabinet developed by using inverters from Siemens, ABB, Schneider, Fujifilm, Mitsubishi, Panasonic, Delta, Shilin, Inovance and other manufacturers. According to the needs of working conditions, AC transmission can be installed in the frequency conversion cabinet.

Megmeet servo drive - common faults and treatment methods of servo drives Megmeet servo drive - common faults and treatment methods of servo drives

1. The motor runs differently in both directions Cause of failure: The phase of the brushless motor is wrong; The deviation potentiometer is in the wrong position. Solution: Detect or detect the correct phase; Reposition the potentiometer. 2. The motor speed is abnormal Cause of failure ...

Megmeet inverter - maintenance precautions and items for high-voltage inverters Megmeet inverter - maintenance precautions and items for high-voltage inverters

Precautions for maintenance of high-voltage inverters 1. Carefully monitor and record the display parameters on the man-machine interface of the inverter, and reflect the abnormality immediately 2. Carefully monitor and record the ambient temperature of the inverter room, and the ambient temperature should be between -5 °C and 40 °C. Phase-shifting transformers ...

Megmeet PLC - how the PLC communicates with the host computer Megmeet PLC - how the PLC communicates with the host computer

The PLC communicates with the host computer, and BlandC is used to write the communication program between the host and the PLC, and the COM1 port must be initialized, the baud rate is 9600bps, and the parity check bit adopts even check, and the seven-digit valid data is used. When the computer receives the response character ACK from the PLC, it ...

Common faults and solutions of Megmeet inverter Common faults and solutions of Megmeet inverter

Fault one Fault phenomenon: the leakage protection switch trips, the inverter is energized or the equipment leakage protection switch is operated during operation Solution: 1. When the inverter drives the motor, the leakage value is larger than that of the non-inverter system, and the leakage protection value of the leakage protection switch is required to be more than 150mA, ...

Megmeet inverter - inverter braking mode and advantages and disadvantages introduction Megmeet inverter - inverter braking mode and advantages and disadvantages introduction

What are the braking methods of the inverter? Generally speaking, braking refers to the technical measures taken during the operation of the motor due to fault protection or man-made active shutdown, and the commonly used inverter braking methods include energy consumption braking, feedback braking, DC braking and DC feedback braking. ...

Megmeet inverter - introduction to the classification of inverters Megmeet inverter - introduction to the classification of inverters

1. Classified according to the input voltage level According to the input voltage level, the inverter can be divided into low-voltage inverter and high-voltage inverter, and the low-voltage inverter is common in China with single-phase 220 V inverter, three-phase 220 V inverter, and i-phase 380 V inverter. High-voltage inverters are commonly used in 6 kV, 10 kV transformers.

Megmeet drives – routine and regular maintenance of drives Megmeet drives – routine and regular maintenance of drives

1. Maintenance items and scope: Daily maintenance and maintenance of inverter Due to the influence of environmental temperature, humidity, dust and vibration, it will lead to the aging of the internal components of the inverter, resulting in the potential failure of the inverter or reducing the service life of the inverter. Therefore, there is a must ...

Megmeet inverter - common faults and treatment methods of high-voltage inverters Megmeet inverter - common faults and treatment methods of high-voltage inverters

1. Control through this abnormal failure The abnormal fault of the control channel is usually caused by the optical fiber communication between the sub-PWM board and the power unit board, which is generally caused by the following situations: 1. Poor contact of the optical fiber connection part or falling off of the optical fiber head; 2. Optical fiber signal transmitter/receiver ...

Megmeet PLC – System integration for PLC Megmeet PLC – System integration for PLC

In the manufacturing industry, there are a large number of open-loop sequential control based on switching quantities, which carries out sequential action numbers according to logical conditions and operates in chronological order; In addition, there is the control of chain protection actions according to the logical relationship that is not related to the sequence and timing; As well as a large number of switching quantities, pulse quantities, gauges...

New Arrivals! Hollysys' two blockbuster products were unveiled at the Zhongguancun Forum Technology Trading Conference New Arrivals! Hollysys' two blockbuster products were unveiled at the Zhongguancun Forum Technology Trading Conference

On September 24, the 2021 Zhongguancun Forum, co-sponsored by the Ministry of Science and Technology of China, the Chinese Academy of Sciences, the China Association for Science and Technology, and the Beijing Municipal People's Government, officially opened in Beijing. As one of the main agendas of the forum, the Zhongguancun International Technology Exchange Conference closely follows the "smart· healthy· carbon neutrality...

Megmeet drives – what are the basic requirements for regular replacement of drive components? Megmeet drives – what are the basic requirements for regular replacement of drive components?

1. It is necessary to figure out the basic parameters and shape of the device that needs to be replaced. The basic parameters include the rated operating current, the capacitance of the capacitor, the resistance value of the resistor, the value of the GTR Darlington device (current amplification factor), the switching characteristics of the IGBT (including IPM) device, and the saturation voltage ...

The cause and treatment method of the fault code Eroc1 of Megmeet inverter The cause and treatment method of the fault code Eroc1 of Megmeet inverter

1. Overcurrent fault of inverter Fault Code: OCF. (1) Fault name: inverter overcurrent fault (2) The cause of the failure: the motor nameplate data input is incorrect: the load dragged by the motor is too heavy: the machinery is stuck; Motor stalled. (3) ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top