Megmeet inverter – the energy-saving principle of low-voltage inverter

Create Date: 2024-8-30 12:03:23|Source: MEGMEET

Inverter energy saving

The energy saving of the inverter is mainly manifested in the application of fans and pumps. In order to ensure the reliability of production, all kinds of production machinery are designed with power drive, and there is a certain amount of surplus. When the motor cannot run at full load, in addition to meeting the requirements of power drive, the excess torque increases the consumption of active power and causes a waste of electric energy. The traditional speed regulation method of fans, pumps and other equipment is to adjust the air supply volume and water supply by adjusting the baffle plate and valve opening of the inlet or outlet, and the input power is large, and a large amount of energy is consumed in the interception process of the baffle and valve. When using inverter speed regulation, if the flow requirement is reduced, the speed of the pump or fan can be reduced to meet the requirements.

From fluid mechanics, P (power) = Q (flow) × H (pressure), the flow rate Q is proportional to the square of the speed N, the pressure H is proportional to the square of the speed N, and the power P is proportional to the cube of the speed N. That is, the relationship between the power consumption of the pump motor and the speed is approximately proportional. When the required flow rate Q is reduced, the output frequency of the inverter can be adjusted to reduce the motor speed n proportionally. At this time, the power P of the motor will be greatly reduced according to the cubic relationship, and the energy saving is 40% to 50% more energy-saving than the adjusting baffle and valve, so as to achieve the purpose of power saving.

For example, when the power of a centrifugal pump motor is 55 kilowatts, when the speed drops to 4/5 of the original speed, its power consumption is 28.16 kilowatts, saving 48.8%, and when the speed drops to l/2 of the original speed, its power consumption is 6.875 kilowatts, saving 87.5%.

Power factor compensation saves energy

Reactive power not only increases the line loss and the heating of the equipment, but also the reduction of the power factor leads to the reduction of the active power of the power grid, a large amount of reactive energy is consumed in the line, the equipment is inefficient, the waste is serious, after the use of frequency conversion speed regulation device, due to the effect of the internal filter capacitor of the frequency converter, the reactive power loss is reduced, and the active power of the power grid is increased.

Soft-start energy saving

The hard start of the motor will cause a serious impact on the power grid, and it will also require too high the capacity of the power grid, and the large current and vibration generated during the start will cause great damage to the baffle and valve, and the service life of the equipment and pipeline will be extremely unfavorable. After the use of frequency conversion energy-saving device, the use of the soft start function of the frequency converter will make the starting current start from zero, and the maximum value will not exceed the rated current, which reduces the impact on the power grid and the requirements for power supply capacity, and prolongs the service life of equipment and valves. The maintenance cost of the equipment is saved.
Megmeet inverter – the energy-saving principle of low-voltage inverter

More on that
Megmeet MC100 series plc – the right hand man in refrigeration equipment Megmeet MC100 series plc – the right hand man in refrigeration equipment

First, the process requirements When the low-pressure pressure collected by the system is greater than the upper low-pressure pressure set by the touch screen, the compression time will be loaded according to the set loading time, and the lower pressure will be reduced according to the set load reduction time. The high pressure collected is greater than that on the high pressure ...

Megmeet inverter - the fault handling method of low-voltage inverter Megmeet inverter - the fault handling method of low-voltage inverter

Before using the inverter, the inverter parameters should be carried out from the following aspects: First, confirm the motor parameters, the inverter sets the power, current, voltage, speed, and maximum frequency of the motor in the parameters, and these parameters can be directly obtained from the motor nameplate. Clause...

Various welding methods for Megmeet welding machines Various welding methods for Megmeet welding machines

1) Hand arc welding (STICK) Shielded Arc Welding (abbreviated SMAW) in English, The principle is: the arc occurs between the coating electrode and the base metal, and the welding method of arc thermal ablation electrode and base metal is used. The outer layer of the electrode is covered with solder, which is dissipated in case of heat.

Megmeet drives – how should high-voltage drives be maintained after they are shut down? Megmeet drives – how should high-voltage drives be maintained after they are shut down?

1. Check the surrounding situation - carefully check the ventilation and lighting of the inverter and the surrounding environment. It is necessary to ensure that the ventilation equipment is functioning properly and that the lighting equipment is in working order. 2. Check the internal cable - open the inverter cabinet door and check whether the internal cable is damaged, the cable ...

Megmeet drives – what are the components of a drive? Megmeet drives – what are the components of a drive?

The inverter is composed of a main circuit, a rectifier, a flat wave circuit, and an inverter. 1) Main circuit: The main circuit is the power conversion part that provides voltage regulation and frequency regulation power supply for the asynchronous motor, and the main circuit of the inverter can be roughly divided into two categories: the voltage type is the DC ...

Common faults of Megmeet drives and how to deal with them Common faults of Megmeet drives and how to deal with them

1. When the oscilloscope looks at the current monitoring output of the driver, it finds that it is all noisy and cannot be read Cause: The current monitoring output is not blocked from the AC power supply (transformer). Solution: You can use a DC voltmeter to detect and investigate. 2. Servo motor high speed ...

Megmeet PLC - the core components of PLC introduction Megmeet PLC - the core components of PLC introduction

(1) Central Processing Unit (CPU) The central processing unit (CPU) is the control center of the PLC. It accepts and stores user programs and data typed from the programmer, checks the status of the power supply, memory, I/O and alert timer in accordance with the functions assigned by the PLC system program, ...

Megmeet inverter - common faults and treatment methods of high-voltage inverters Megmeet inverter - common faults and treatment methods of high-voltage inverters

1. Control through this abnormal failure The abnormal fault of the control channel is usually caused by the optical fiber communication between the sub-PWM board and the power unit board, which is generally caused by the following situations: 1. Poor contact of the optical fiber connection part or falling off of the optical fiber head; 2. Optical fiber signal transmitter/receiver ...

Megmeet inverter - what are the main aspects of the development of inverter in the future? Megmeet inverter - what are the main aspects of the development of inverter in the future?

1. Intelligent network The intelligent inverter does not need to set a lot of parameters when it is used, and it has the function of fault self-diagnosis, which has high stability, high reliability and practicability. The Internet can be used to realize the linkage of multiple inverters, and even the inverter complex in the factory.

Megmeet PLC - Introduction to the basic structure of PLC controller Megmeet PLC - Introduction to the basic structure of PLC controller

1. Power supply The power supply of the PLC plays a very important role in the whole system. It can't work properly without a good and reliable power supply system, so PLC manufacturers also attach great importance to the design and manufacture of power supplies. General AC voltage fluctuations are +10% (+15%) ...

Megmeet inverter - common faults and treatment methods of high-voltage inverters Megmeet inverter - common faults and treatment methods of high-voltage inverters

The high-voltage inverter has a highly intelligent computing level and a perfect fault detection circuit, and can provide accurate positioning of all faults, and make clear instructions on the main control interface. In practical application, we find that common faults can be divided into abnormal control channels, IGBT overcurrent, overvoltage...

Megmeet PLC - What is the difference between PLC and servo control system Megmeet PLC - What is the difference between PLC and servo control system

1. The meaning of the representation is different: PLC is the abbreviation of planar optical waveguide (technology), the so-called planar optical waveguide, means that the optical waveguide is located in a plane. A servo control system is a feedback control system used to accurately follow or reproduce a certain process.

Megmeet PLC - the connection method between the PLC and the server Megmeet PLC - the connection method between the PLC and the server

The first is that the PLC sends a start/stop signal to the server through the I/O point, and the server controls the operation of the servo motor. The PLC controls the operation/stop of the servo through the digital output, so as to achieve the purpose of controlling the servo motor. The second is through the pulse output of the PLC, which ...

Megmeet inverters – what are the development directions of inverter-related technologies? Megmeet inverters – what are the development directions of inverter-related technologies?

1. Intelligent network The intelligent inverter does not need to set a lot of parameters when it is used, and it has the function of fault self-diagnosis, which has high stability, high reliability and practicability. The Internet can be used to realize the linkage of multiple inverters, and even the inverter complex in the factory.

Megmeet drives – safety precautions for the installation of drives Megmeet drives – safety precautions for the installation of drives

When the inverter is installed and wired; Note: When more than two inverters are installed in the same cabinet, please pay attention to the installation position and spacing to ensure the heat dissipation effect. Dangerous: 1. It should be operated by professional electrical engineering personnel, otherwise there is a risk of electric shock. 2. Please make sure before wiring...

Megmeet PLC - an introduction to the classification of PLC Megmeet PLC - an introduction to the classification of PLC

There are many types of PLC products, and their specifications and performance also vary. PLCs are usually classified according to their different structural forms, differences in functions, and the number of I/O points. 2.1 Classification by structural form According to the structural form of PLC, PLC can be divided into whole ...

Features of Megmeet CO2/MAG all-digital heavy-duty welder Features of Megmeet CO2/MAG all-digital heavy-duty welder

1. The arc is stable in the field of full current, the spatter is small, and the same welding machine is not only suitable for small current base welding, but also suitable for high current and high deposition rate work 2. Arc concentration and strong penetration. With the same penetration depth, the heat input is reduced by more than 20% compared with other gas shielded welding machines, and the thermal deformation ...

Megmeet inverter - what are the control methods of the inverter? Megmeet inverter - what are the control methods of the inverter?

Sinusoidal Pulse Width Modulation (SPWM) control mode It is characterized by simple structure of control circuit, low cost, good hardness of mechanical characteristics, and can meet the smooth speed regulation requirements of general transmission, and has been widely used in various fields of industry. However, this type of control is at low frequencies, ...

Megmeet drive common fault repair methods Megmeet drive common fault repair methods

When the oscilloscope looks at the current monitoring output of the driver, it is all noisy and cannot be read Cause: The current monitoring output is not blocked from the AC power supply (transformer). Solution: You can use a DC voltmeter to detect and investigate. Servo motor high-speed rotation ...

Megmeet PLC - how the PLC communicates with the host computer Megmeet PLC - how the PLC communicates with the host computer

The PLC communicates with the host computer, and BlandC is used to write the communication program between the host and the PLC, and the COM1 port must be initialized, the baud rate is 9600bps, and the parity check bit adopts even check, and the seven-digit valid data is used. When the computer receives the response character ACK from the PLC, it ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top