1. How to complete the control of ATV38 and ATV58 through the operation panel?
First, in the control menu, set "LCC" to "YES" (panel operation); Enter the "LFR" parameter in the adjustment menu, press the up and down keys to adjust the given value, and complete the control of the inverter.
How can multiple ATV71/61 inverters connected to the same bus communicate with a graphical display terminal? The [Communication] menu→ [Network MODBUS] → [MODBUS Address] (ADD) set the address of each inverter. When multiple inverters are connected to the same display terminal, the terminal will actively display the inverter address. All menus can be accessed in multipoint mode, but the graphical display is not allowed to control the inverter.
2. In the use of motor reactors, why is the interval required for shielded cables shorter than those of unshielded cables?
Because parasitic capacitance is generated between the shield layer and the conductor of the shielded cable, the cable should not be too long.
3. The main circuit of the high-power ATV71/61 inverter has been energized, why does NLP (main circuit not energized) sometimes prompt?
This is because there is no short wiring between the terminals PO and PA/+ connected to the DC reactor, and the main circuit cannot be supplied with power. The short-wired of the frequency conversion less than 90KW has been connected when leaving the factory, and the frequency conversion greater than or equal to 90KW needs to be short-circuited by the customer.
4. What is the function of the inverter DC reactor?
Reduce the higher harmonic interference of the input current and improve the power factor of the input power supply.
5. What is the significance of forced local operation of the inverter?
Local operation refers to the control of the terminal or display module by the inverter, and the corresponding communication control. If you want to switch between communication control and local operation, you must configure a logical input terminal as "FLO", that is, force local operation. When the input is condition 1, the local operation is forced; When the input is condition 0, the communication control is useful.
|
More on that
|
Schneider Modicon M100 Programmable Controller Features and Benefits
The Schneider Electric Modicon M100 programmable controller is part of the Easy Series and is suitable for simple I/O logic control machines.
characteristic
AC power supply
High-speed processor with 0.2μs/boolean amount
Built-in a ...
|
|
Schneider inverter knowledge points
1. Use the analog output port to indicate the motor frequency, when the motor frequency is 50Hz, why is the output only 16mA?
Due to the maximum output frequency parameter of the inverter "TFR", the factory default value is 60Hz. So when the inverter output is 50Hz, the analog output is 16mA. At this time, only ...
|
|
Schneider Intermediate Relay Model Letter Meaning
RXM: Schneider's miniature center relay
The first 2: indicates the number of contacts, and the normally open contact is 2
LB: Indicates that the product has LED light
The second 2: indicates the number of contacts, and the normally closed contacts are 2
BD: Indicates that the supply voltage used is DC 24V
...
|
|
For the first time, Schneider presents a new lightweight MES in packaging
Packaging Lightweight MES is a production line and workshop-level digital management and processing solution created by Schneider Electric based on more than 20 years of experience in packaging machine automation, combined with the digital transformation needs of the FMCG (Consumer Packaged Goods) profession, which can be widely used in food and beverage, life ...
|
|
Schneider ATV71 inverter installation and modulation setting steps
1. Schneider inverter menu:
(1) Simple start:
Self-tuning: If the manifestation is "unfinished", then select "supplication self-tuning" until the manifestation is "finished", i.e., the completion of self-tuning;
Acceleration moment: a ...
|
|
Schneider inverter ATV61 OPF failure analysis
Q: 250KW ATV61 with 250KW fan, when decelerating to low speed, OPF (motor missing three-phase) problem will be reported occasionally. There are no contactors or switches between the inverter and the motor.
Answer: This situation seems to be a problem with the inverter, which is a false alarm. Not really! The fan is decelerating ...
|
|
Motor control mode of Schneider inverter
Fundamentals of magnetic flux vector manipulation
The control of a three-phase asynchronous motor is much more complicated than that of a DC motor because the current, voltage, induced potential, magnetic flux, etc., of the stator and rotor are all alternating.
However, the stator winding of the three-phase asynchronous motor is a symmetrical three-phase winding, which exerts a ...
|
|
Schneider soft starter fault alarm maintenance method
1. Question-F 05 (frequency error):
This problem is caused by a problem with the soft starter processing the internal power signal, which is causing errors in the power supply frequency. This situation needs to be handled by the company's product development software design engineer. Mainly start the power supply circuit design ...
|
|
Schneider ATS48 soft starter issue
1. What type of ATS48 power supply is?
The control power supply of ATS48 selects communication input, and supplies power to the controller, input and output ports through internal power processing;
The control power supply of Q series products is 220V-415V;
Handling of the Y-Series ...
|
|
Schneider instrumentation maintenance precautions
1. Don't blindly knock and bump when overhauling to avoid expansion failures, and the more you repair, the worse it gets.
2. Do not plug and unplug various control boards and plugs with electricity. Due to the strong induced electromotive force generated by plugging and unplugging the control board under the power-on condition, the instantaneous ...
|
|
Analysis of 10 reasons for frequent tripping of Schneider leakage switches
1. Defective device
If the lead wire of each pile head is not firmly connected and loosened for a long time, it will cause the pile to heat and oxidize, burn out the outer insulation of the wire, and announce sparks and burnt smell, resulting in undervoltage of the line and air switch action.
2. Leakage switch with ...
|
|
Schneider selection of different types of circuit breakers
Miniature circuit breakers are: A9 (iC65, iDPN, etc.), M9 (C65, DPN, C120, NG125, etc.), E9, OSMC32N/OSMC65H, etc.
Molded case circuit breakers are: NSX, NSE, EZD, NSC, large molded case NS.
Structural circuit breakers include: MT, MTE, etc.
...
|
|
The method of controlling the speed of the motor by the inverter - Schneider
1. Why can the rotation speed of the motor be changed freely?
Motor rotation speed unit: r/min number of rotations per minute, can also be expressed as rpm.
Example: 2-pole motor 50Hz 3000 [r/min]
4-pole motor 50Hz 1500 [r/min]
Conclusion:...
|
|
The cause of leakage in the motor using the inverter - Schneider
1. The output of the inverter is controlled by PWM (pulse width modulation, similar to high-speed switching), so high-frequency leakage current will occur.
The PE points of the three transmission equipment of the inverter, the pre-power supply transformer and the motor must be connected together and then grounded consistently.
Frequency conversion...
|
|
Schneider's method of improving the power factor of UPS power supplies
One. The significance of the progressive power factor.
1. Make full use of the ability of power equipment.
Each power supply unit has additional capacity, i.e. depending on the power. The total power output of the power supply equipment S, - part of the active power, the other part is the reactive power, the smaller the ...
|
|
Schneider miniature circuit breaker C type D type difference
The difference between Schneider OSMC32N3D10 and OSMC32N3C10
After type comparison, one is Schneider D10A and the other is Schneider C10A.
Schneider circuit breaker type D, suitable for power equipment, such as motor load, air conditioner, etc.;
Schneider circuit breaker type C, suitable ...
|
|
Key points of operation of Schneider disconnectors
Features of Schneider Barrier Switch: First of all, Schneider Barrier Switch can be used to block the power supply, it can disconnect the live equipment from the high-voltage maintenance equipment, and can also see the obvious disconnection point on it. Secondly, Schneider barrier switches can cooperate with circuit breakers to change the operation of the system.
|
|
The difference between Schneider and Siemens PLC
There are three main differences, namely: different uses, different products, and different characteristics.
1. Different use cases: The programmable manipulator produced by Siemens in Germany is also widely used in China, and has been used in metallurgy, chemical industry, printing production lines and other fields.
|
|
U-tube manometer error analysis – Schneider
(1) Temperature error. This refers to the change of the length of the scale and the density of the working fluid due to the change of ambient temperature, and the former can be ignored in general, and the latter should be appropriately corrected. For example, when water is changed from 10°C to 20°C, its density changes from 999. 8kg/m^3 reduced to 999.8kg/m^3 ...
|
|
The difference between high voltage and low voltage of Schneider inverter
1. What is the difference between high-voltage inverter and low-voltage inverter?
Frequency converters can be broadly divided into two categories: high-voltage frequency converters and low-voltage frequency converters.
In terms of use, the applicable objects are different, and the high-voltage motor is the same from the principle of speed regulation. From the topology ...
|
|