The method of controlling the speed of the motor by the inverter - Schneider

Create Date: 2024-8-30 12:03:23|Source: Schneider/Schneider

1. Why can the rotation speed of the motor be changed freely?

Motor rotation speed unit: r/min number of rotations per minute, can also be expressed as rpm.

Example: 2-pole motor 50Hz 3000 [r/min]

4-pole motor 50Hz 1500 [r/min]

Conclusion: The rotational speed of the motor is divided into two parts of the frequency

The rotational speed of an induction AC motor (hereinafter referred to as a motor) is approximately determined by the number of poles and frequency of the motor. The number of poles of the motor is fixed by the operating principle of the motor. Because the pole value is not a continuous value (a multiple of 2, e.g. the pole number is 2, 4, 6), it is generally not suitable to adjust the speed of the motor by changing the value.

In addition, the frequency can be adjusted outside the motor and then supplied to the motor, so that the rotation speed of the motor can be freely controlled.

Therefore, the inverter for the purpose of controlling the frequency is the preferred equipment for motor speed regulation equipment.

  n = 60f/p

n: Synchronization speed

f: Power frequency

p: Number of pole pairs of the motor

Conclusion: Changing the frequency and voltage is the best way to control the motor

If you only change the frequency without changing the voltage, the motor may burn out due to overvoltage (overexcitation) when the frequency drops. Therefore, it is necessary to change the voltage of the inverter at the same time as changing the frequency. When the output frequency is above the additional frequency, the voltage cannot be continuously added, and the maximum voltage can only be equal to the additional voltage of the motor.

For example, if the output frequency of the inverter is changed from 50 Hz to 25 Hz in order to halve the rotation speed of the motor, the output voltage of the inverter needs to be changed from 400 V to about 200 V

                            The method of controlling the speed of the motor by the inverter - Schneider

2. What happens to the output torque of a motor when its rotation speed (frequency) is changed?

The starting torque and maximum torque when driven by the inverter are less than those driven by direct industrial frequency power supply.

The starting and acceleration impact of the motor is large when the power frequency power supply is used, and when the power supply is used by the inverter, these shocks are weaker. A large starting current will occur when the power frequency is directly started. When the inverter is used, the output voltage and frequency of the inverter are gradually added to the motor, so the starting current and impact of the motor are smaller.

In general, the torque generated by the motor decreases as the frequency decreases (speed decreases). Practical data for the reduction is explained in some inverter manuals.

By using a magnetic flux vector-operated inverter, the lack of torque in the motor at low speed will be improved, and the motor can output the torque that meets the requirements even at low speed.

3. When the speed of the inverter is adjusted to a frequency greater than 50Hz, the output torque of the motor will decrease

The general motor is planned and manufactured according to the voltage of 50Hz, and its additional torque is also given in this voltage range. Therefore, the speed regulation under the extra frequency is called constant torque speed regulation. (T=Te, P)

When the output frequency of the inverter is greater than the frequency of 50Hz, the torque of the motor decreases in a linear relationship inversely proportional to the frequency.

When the motor is running at a frequency speed greater than 50Hz, it is necessary to consider the size of the motor load to avoid the lack of motor output torque.

For example, the torque of a motor at 100 Hz drops to about 1/2 of that at 50 Hz.

Therefore, the speed regulation above the additional frequency is called constant power speed regulation. (P=Ue*Ie)

4. The application status of the inverter above 50Hz

We know that the extra voltage and extra current are constant for a particular motor. For example, the additional value of the inverter and the motor is: 15kW/380V/30A, and the motor can operate above 50Hz.

When the speed is 50Hz, the output voltage of the inverter is 380V and the current is 30A. At this time, if the output frequency is increased to 60Hz, the maximum output voltage and current of the inverter can only be 380V/30A, and the output power is obviously unchanged. That's why we call it constant power speed regulation.

What is the torque situation at this time? Because P=wT (w: angular velocity, T: torque). Since P does not change, w is added, so the torque decreases accordingly.

We can also look at it from another point of view: the stator voltage of the motor U = E + I*R (I is the current, R is the electronic resistance, E is the induced potential) It can be seen that when you and I are unchanged, E is also constant. E = k*f*X, (k: constant, f: frequency, X: flux), so when f is from 50–>60Hz, X decreases accordingly

For motors, T = K*I*X (K: CONSTANT, I: CURRENT, X: MAGNETIC FLUX), SO THE TORQUE T WILL DECREASE WITH THE DECREASE OF MAGNETIC FLUX X. Together, when it is less than 50Hz, because I*R is very small, when U/f=E/f is constant, the magnetic flux (X) is constant, and the torque T is proportional to the current. This is why the overcurrent ability of the inverter is generally used to describe its overload (torque) ability. It is also called constant torque regulation (the additional current does not change – > the maximum torque does not change)

Conclusion: When the output frequency of the inverter is increased from 50Hz or more, the output torque of the motor will decrease.

5. Other elements related to output torque

Heat generation and heat dissipation can determine the output current of the inverter, which affects the output torque of the inverter.

Carrier frequency: Generally, the additional current marked by the inverter is the value that can ensure continuous output at the highest carrier frequency and the highest ambient temperature. If the carrier frequency is lowered, the current of the motor will not be affected, but the heat generation of the components will be reduced.

Ambient temperature: Just as the inverter protection current value will not be increased because the ambient temperature is low.

Altitude: Altitude is added to have an impact on heat dissipation and insulation. Generally, less than 1000m can be considered. The above 5% reduction per 1000 meters is enough.

More on that
Schneider inverter knowledge points Schneider inverter knowledge points

1. Use the analog output port to indicate the motor frequency, when the motor frequency is 50Hz, why is the output only 16mA? Due to the maximum output frequency parameter of the inverter "TFR", the factory default value is 60Hz. So when the inverter output is 50Hz, the analog output is 16mA. At this time, only ...

Schneider thermal relay selection method Schneider thermal relay selection method

1. In principle, the ampere-second characteristics of the Schneider thermal relay should be as close as possible to or even coincide with the overload characteristics of the motor, or under the overload characteristics of the motor, and at the same time, the Schneider thermal relay should not be affected (not acting) at the moment of short-term overload and start of the motor. ...

Features of Schneider explosion-proof inverter box Features of Schneider explosion-proof inverter box

1. Aluminum alloy shell or steel plate welding, surface spraying; 2. Built-in inverters, circuit breakers, signal lights and other components produced by domestic or Schneider and other companies; 3. It is mainly adjusted by changing its output frequency to adjust the speed of ordinary three-phase asynchronous motor, so as to reach the production process.

Schneider instrumentation maintenance precautions Schneider instrumentation maintenance precautions

1. Don't blindly knock and bump when overhauling to avoid expansion failures, and the more you repair, the worse it gets. 2. Do not plug and unplug various control boards and plugs with electricity. Due to the strong induced electromotive force generated by plugging and unplugging the control board under the power-on condition, the instantaneous ...

Schneider power supply configuration UPS backup battery method Schneider power supply configuration UPS backup battery method

In order to ensure that the APCUPS power supply can continue to provide high-quality power to the computer in the event of a power outage, it is particularly important to equip the battery backup battery. When the frequency load does not agree to be supplied with power, the backup time of the UPS battery in the communication room should be greater than the time from the suspension of the mains power to the recovery or until the generator set is normal.

Functions of input/output pins P0, P1, P2, P3 – Schneider Functions of input/output pins P0, P1, P2, P3 – Schneider

P0.0——P0. 7 : Port P0 is an 8-bit open-drain bidirectional I/O port. When visiting off-chip memory, it is time-shared for a low-8-bit address and an 8-bit bidirectional data bus. When EPROM is programmed, the instruction byte is input by P0, and when the program is verified, it outputs ...

Schneider seizes the opportunity of e-commerce Schneider seizes the opportunity of e-commerce

Beijing, China, 24 August 2021 – Looking at the history of the logistics industry, the changes brought about by the development of e-commerce in recent years are rare. According to Digital Commerce 360, in 2020, United States customers spent $861.12 billion online, a year-on-year increase.

Inverter braking resistor selection – Schneider Inverter braking resistor selection – Schneider

In the process of fast parking, because of the inertia, a lot of regenerative electric energy will occur, which will directly act on the intermediate DC part of the inverter, and if this part of the electric energy is not consumed, the inverter will be faulty or the inverter will be damaged. The braking resistor is used to dissipate this part of the electrical energy. ...

Schneider inverter simple question Schneider inverter simple question

1. How to complete the control of ATV38 and ATV58 through the operation panel? First, in the control menu, set "LCC" to "YES" (panel operation); Enter the "LFR" parameter in the adjustment menu, press the up and down keys to adjust the given value, and complete the control of the inverter. ...

Schneider instrumentation accuracy Schneider instrumentation accuracy

It refers to the degree to which the average value measured repeatedly under certain test conditions is consistent with the true value, which is indicated by error. It is used to indicate the magnitude of the error in the system. In practice, control tests are generally carried out with standardized substances or normative methods, and when there are no standardized substances or normative methods, it is often used to add ...

Schneider ATV71 inverter installation and modulation setting steps Schneider ATV71 inverter installation and modulation setting steps

1. Schneider inverter menu: (1) Simple start: Self-tuning: If the manifestation is "unfinished", then select "supplication self-tuning" until the manifestation is "finished", i.e., the completion of self-tuning; Acceleration moment: a ...

Precautions for motor operation over 60Hz - Schneider Precautions for motor operation over 60Hz - Schneider

What problems should be paid attention to when the motor works beyond 60Hz? The following precautions should be taken when operating beyond 60Hz (1) Machinery and equipment should have sufficient potential to work at this speed (mechanical strength, noise, vibration, etc.). (2) ...

Anti-electromagnetic interference method - Schneider Anti-electromagnetic interference method - Schneider

There are three main sources of electromagnetic disturbance to the industrial system: first, space field disturbance, which enters the system through electromagnetic wave radiation; the second is power disturbance, which directly damages the system; The third is the signal disturbance channel, which enters the system through the front and rear channels connected to the host. In order to ensure that the instrumentation ...

Fault check steps for frequency converters - Schneider frequency converters Fault check steps for frequency converters - Schneider frequency converters

1. Check whether the appearance of the inverter is in good condition, including whether the indicator light is running normally, whether the task control function of the operation panel is complete, and carefully observe the appearance of the inverter in the operating state, and do the corresponding recording work; When repairing the inverter, check whether the voltage value and current value exceed the allowable ...

Schneider UPS uninterruptible power supply debugging precautions Schneider UPS uninterruptible power supply debugging precautions

1. Check whether all switches are in the disconnected position; 2. Check whether there are foreign objects in the UPS uninterruptible power supply cabinet and transformer; Check whether the flat cable connection is correct and whether it is loose; 3. Check that the connected plug is ...

Schneider molded case and miniature circuit breaker recommended models Schneider molded case and miniature circuit breaker recommended models

  Molded case circuit breaker recommendation Schneider EZD series Create a high-quality circuit breaker for secondary power distribution EZD molded case circuit breaker is a product series of molded case circuit breakers specially designed for secondary power distribution by Schneider Electric, which is especially suitable for ...

The selection method of inverter power - Schneider The selection method of inverter power - Schneider

The system power is equal to the product of the inverter power and the motor power, as long as both are operating at a higher power, the system power is higher. From the power point of view, when selecting the power of the inverter, the following points should be noted: ...

A brief description of the working principle of Schneider power soft starter A brief description of the working principle of Schneider power soft starter

Schneider ATS48 soft starter is composed of three opposite parallel thyristors, which are connected in series between the three-phase power supply and the motor, by changing the trigger angle of the thyristor gate pulse, the conduction angle of the thyristor gradually increases from zero, according to the pre-set soft starter parameter curve, the motor output torque ...

Rebecca · Lowell · Edwards Schneider Electric's first Global Head of Communications Rebecca · Lowell · Edwards Schneider Electric's first Global Head of Communications

GENEVA – Rebecca Lowell Edwards, who has been with the International Olympic Committee for the past 18 months·· has joined Schneider Electric as the company's first global communications chief. In the new work that starts today, love ...

Maintenance of Schneider circuit breakers Maintenance of Schneider circuit breakers

In order to keep the main Schneider circuit breaker in excellent operating condition, it is necessary to strengthen the maintenance management. 1. Insist that the air is moist or unclean, and the pipes are not clean, may have the following consequences: (1) The wet gas is decomposed into mixed gases such as hydrogen and oxygen under the action of electric arc, which damages the ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top