Schneider's method of improving the power factor of UPS power supplies

Create Date: 2024-8-30 12:03:23|Source: Schneider/Schneider

One. The significance of the progressive power factor.

1. Make full use of the ability of power equipment.

Each power supply unit has additional capacity, i.e. depending on the power. The total power output of the power supply equipment, - part of the active power, the other part is the reactive power, the smaller the active power in the circuit, the increased value can make the equipment of the same capacity to supply more power to the user. Then the energy utilization of the power supply equipment is improved.

A fluorescent lamp with 40 W (=0.4) can carry 400 bulbs at a power supply capacity of SN = 40 kVA, while an incandescent lamp with 40 W (=1) can carry 1000 bulbs.

It can be seen that the power factor has increased from 0.4 to 1, and the number of electrical appliances used in the normal power supply of the generator has also increased from 400 to 1000, so that the power supply is the same as the power supply, and the energy utilization rate of the power supply equipment has been greatly improved. When the UPS power supply voltage is punctual, the lower the power factor, the larger the current, and the greater the voltage drop and power loss on the power supply line.

Therefore, the lower the power factor of the electrical appliance, the greater the current absorbed by the electrical appliance from the power supply, and the greater the voltage drop and power loss on the line; The higher the power factor of the consumer, the less current the appliance absorbs from the power supply, and the smaller the voltage drop and power loss of the transmission line. Therefore, the improvement of the power factor can reduce the voltage loss and voltage loss of the power supply line.

For example, a 220V/40W incandescent lamp current is 0.18A; Since its cosφ=0.4 and current is 0.455A, it is clear that the voltage drop and power loss caused by the line resistance are also much larger.

If the voltage drop of the power supply line is too large, it will cause the power grid to be in a low-voltage operation state for a long time, affecting its normal operation. In order to reduce losses and improve the quality of power supply, it is necessary to improve the power factor.

                              Schneider's method of improving the power factor of UPS power supplies

Second, the method of improving the power factor.

1. Progress natural power factors.

The power factor of the power equipment itself is also called the natural power factor.

The correct selection of the motor makes the capacity of the motor match the mechanical load being dragged and avoids the phenomenon of "horse-drawn trolley".

The motor should not be allowed to idle as much as possible, and the power factor of the circuit can be improved by the active replacement of ^-Y wiring when the load is usually running at light load.

2. Turn on the capacitance compensation.

The current in the receiver load circuit lags behind the voltage, and 90 can occur after the capacitor is connected in parallel. The current of the capacitor branch is offset by the current that lags behind the voltage, so that the total current of the circuit is reduced, and then the impedance angle is reduced, and the power factor is improved.

The additional voltage of the capacitor is combined with the grid voltage, and the triangulation method should be selected.

UPS power supply factor is generally compensated to 0.9 or above, if the capacitance is too large, resulting in "overcompensation", it will make the circuit capacitive and reduce the power factor.

More on that
Schneider inverter frequency signal source mode Schneider inverter frequency signal source mode

In order for the inverter to operate normally, it must have two basic conditions, that is, the frequency signal and the operating signal, let's talk about the first condition, which is the frequency signal of the inverter. Our intention to use the inverter is to change the ...

Frequency converter and PLC connection problems - Schneider Frequency converter and PLC connection problems - Schneider

When the inverter is used to form an automatic control system for control, in many cases, the PLC and the inverter are used together, and how to correctly connect the PLC and the inverter together has become the key to the success of the system. 1.PLC switch ...

U-tube manometer error analysis – Schneider U-tube manometer error analysis – Schneider

(1) Temperature error. This refers to the change of the length of the scale and the density of the working fluid due to the change of ambient temperature, and the former can be ignored in general, and the latter should be appropriately corrected. For example, when water is changed from 10°C to 20°C, its density changes from 999. 8kg/m^3 reduced to 999.8kg/m^3 ...

The difference between vector inverter and general-purpose inverter - Schneider The difference between vector inverter and general-purpose inverter - Schneider

There are two main differences between vector inverters and general-purpose inverters. One is high control accuracy, and the other is high output torque at low speed. Vector special inverter: The operating principle of the vector special inverter is to carry out inverter after rectification, ...

The energy-saving effect of using frequency converter for fan and pump loads The energy-saving effect of using frequency converter for fan and pump loads

Why is the use of inverter for fan and pump loads to save energy? According to the basic laws of fluid mechanics, it can be seen that the fan pump load is a typical square rotation load, and its main characteristics are: speed n and torque T and load ...

Precautions for Schneider motors when operating above 60Hz Precautions for Schneider motors when operating above 60Hz

When operating beyond 60Hz, the following precautions should be taken (1) 1 Machinery and devices should be able to operate at this speed (mechanical strength, noise, oscillation, etc.). (2) The motor enters the constant power output range, and its output ...

Schneider miniature circuit breaker model and parameter difference Schneider miniature circuit breaker model and parameter difference

Schneider miniature circuit breakers are commonly used in C65, C120, EA9, INT125 and other products. Parameter differences: N -------- breaking ability, N is 6000A, H is 10000A, L is 15kA ...

NSX molded case circuit breaker selection - Schneider NSX molded case circuit breaker selection - Schneider

The Schneider NSX molded case circuit breaker has a double rotary contact construction for maintenance, and the high-end electronic trip unit allows for accurate measurement and easy communication. Schneider NSX molded case circuit breaker conforms to IEC60947-2, GB14048.2, China's CCC certification and multinational classification certification...

Schneider UPS power supply preventive maintenance precautions Schneider UPS power supply preventive maintenance precautions

1 Contingency plan Contingency plans are the top priority of preventive protection. Arrangements need to be better partnered with service providers to be part of the corporate programme. This means implementing processes and procedures for every type of thing, including contingency plans. ...

Schneider ATS48 soft starter issue Schneider ATS48 soft starter issue

1. What type of ATS48 power supply is? The control power supply of ATS48 selects communication input, and supplies power to the controller, input and output ports through internal power processing; The control power supply of Q series products is 220V-415V; Handling of the Y-Series ...

Frequency converter control motor leakage solution - Schneider Frequency converter control motor leakage solution - Schneider

Because the current at the input and output ends of the inverter contains high-frequency components, the leakage current formed by the high-frequency components when the inverter is driven is greater than that when the grid power supply is supplied. Because there are many varieties of circuit breakers, in some cases, even the inverter wires and motors ...

Diode selection and substitution method - Schneider Diode selection and substitution method - Schneider

1. Selection of detection diode Point-contact germanium diodes are generally used for detection diodes, such as 2AP series. When selecting, the detection diode with high operating frequency, small reverse current and large forward current should be selected according to the specific requirements of the circuit. Despite the ...

Advantages of Schneider molded case circuit breaker Advantages of Schneider molded case circuit breaker

The contact orientation is 100% secure As for the circuit breaker, the indication of the handle can also be said to be the fault indicator of the circuit breaker, if it is "blurred" for a while, it may cause irreparable damage. Therefore, according to the requirements of the national standard, in any case, the hand of the circuit breaker ...

The protection function of the inverter - Schneider The protection function of the inverter - Schneider

Protective functions can be divided into the following two categories: (1) After detecting the abnormal situation, the correction action is automatically carried out, such as overcurrent loss speed avoidance, regeneration overvoltage stall avoidance. (2) After detecting the abnormality, the PWM control signal of the power semiconductor equipment is closed, so that the motor automatically stops. As...

How to operate the transformer DC resistance tester – Schneider How to operate the transformer DC resistance tester – Schneider

1. The instrument test has a total of YN winding three-phase test, YN winding three-phase phase-by-phase test, low-voltage winding magnetization method test of iron-core five-column low-voltage angular transformer, low-voltage winding phase selection test and general four-terminal method of ironcore three-column low-voltage angular transformer. ...

Schneider touch screen touch deviation causes Schneider touch screen touch deviation causes

(1) Problem--: Contact deviation Phenomenon 1: The direction of the finger does not coincide with the mouse arrow. Reason 1: After installing the driver, there is no vertical contact with the bullseye center when calibrating the alignment. Deal 1: Correct the position from the beginning. Phenomenon 2: Some districts ...

Causes of Schneider UPS power supply damage Causes of Schneider UPS power supply damage

1. Air conditioning: It is generally forbidden to use UPS power supply, because the air conditioning is very large and belongs to the rational load. Not suitable for belt loads 2. Motor: It is necessary to choose a large-capacity UPS power supply, because it is a rational load, and it is ...

Schneider UPS power supply common fault analysis Schneider UPS power supply common fault analysis

1. When there is mains power, the UPS output is normal, and when there is no mains power, the buzzer beeps for a long time and there is no output Fault analysis: From the phenomenon to identify some problems of the battery and inverter, you can view it according to the following procedures: 1. Check the battery voltage to see if the battery is undercharged.

Schneider UPS uninterruptible power supply debugging precautions Schneider UPS uninterruptible power supply debugging precautions

1. Check whether all switches are in the disconnected position; 2. Check whether there are foreign objects in the UPS uninterruptible power supply cabinet and transformer; Check whether the flat cable connection is correct and whether it is loose; 3. Check that the connected plug is ...

Pay attention to the problem when using UPS power supply - Schneider Pay attention to the problem when using UPS power supply - Schneider

1. The parameters set in the host cannot be changed at will during use. In particular, the parameters of the battery pack will directly affect the service life. With the change of ambient temperature, the float charge voltage should be adjusted accordingly. Generally, 25 °C is the standard, and when the ambient temperature rises or falls by 1 °C, the float charge ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top