Siemens APT - ALH-0.66 series transformer FAQ

Create Date: 2024-8-30 12:03:23|Source: APT/Siemens Shanghai Ergong

1. What is the maximum voltage that can be used for an ALH transformer?

AC low voltage up to 720V

2. Is there a protective grade product for ALH transformers?

II-P AND III-P are available in both protective grades

3. What is the maximum primary current of ALH transformer?

The maximum primary side current is 8000A

4. Is an open circuit allowed on the secondary side of the transformer?

It is strictly forbidden to open the road on the secondary side

5. What are the common accuracy of the measurement transformers produced by our company? level

There are five levels: 0.2S, 0.5S, 0.2, 0.5, and 1

6. What is the difference between accuracy class with S and without S?

0.5S and 0.2S are generally used for measurement grade, and 0.5 and 0.2 are generally used for measurement grade

7. What is the maximum primary side current that the measurement-grade transformer can detect

1.2 times the rated current

8. What is the implementation standard of our transformer?

The latest national standards GB20840

9. What is the meaning of transformers P1 and P2 and S1 and S2?

P1P2 is the primary polar end, S1S2 is the secondary polar end, and P1S1 and P2S2 are the eponymous ends. Generally, P1+P2-, if P1P2 wiring is reversed, then the corresponding S1S2 is reversed.

10. What altitude can the transformer be used for?

According to GB20840.2-2014, it can be used at an altitude of 1000m, and can be used for capacity reduction above 1000m

11. Will on-site vibration affect the use of the transformer?

According to the national standard, vibrations or minor earthquakes caused by external causes can be ignored

12. Why does the transformer not provide the secondary winding resistance parameter?

It is a confidential parameter and will not be released to the public

13. When the distance between the transformer and the ammeter is long, how to select the transformer?

Calculated according to line distance, ammeter power, transformer capacity

14. What is the insulation grade of the transformer produced by our company?

Meet the requirements of the national standard: E grade, 120°C

15. What are the types of open transformers?

  HK NK SK

16. Which type of open current transformer belongs to the fully open and closed structure?

  NK

17. What is the aperture coverage of SK series open current transformers?

  6——46

18. Which current transformer adopts integrated TVS technology?

  SK

19. Which specification of current transformer insulation class B?

  SK

20. What is the minimum secondary side current of SK series open current transformer?

  2.5mA
Siemens APT - ALH-0.66 series transformer FAQ


More on that
Siemens APT – PB1 Series FAQs Siemens APT – PB1 Series FAQs

1. What are the installation methods of PB1 button? PB1S and PB1L are fastened with metal screws, and PB1J and PL1 are fastened with plastic nuts. 2. PB1 series pushbuttons can be assembled with up to several sets of contact modules as standard 2*3=6 3. PB1S shell ...

Introduction to the features of the full range of Siemens APT metal button FM products Introduction to the features of the full range of Siemens APT metal button FM products

Seeking advanced, perfect and excellent Xijia APT to concentrate on research and development, and constantly change customs, the launch of the metal flat button indicator FM series is to complete the perfect integration of appearance and performance. Ultra-thin flat round device, metal shell and buttons, high-value appearance Product ...

Siemens APT - FM series metal button indicator frequently asked questions Siemens APT - FM series metal button indicator frequently asked questions

1. Which series of metal buttons can produce two-color buttons with light? FM25N 2. Which series can produce knobs? FM-N series 3. Which type of metal illuminated button needs an external resistor for step-down? FM16E 4. What is the material of the shell ...

ALH-0.66 series transformer FAQ ALH-0.66 series transformer FAQ

1. What is the maximum voltage that can be used for an ALH transformer? AC low voltage up to 720V 2. Is there a protective grade product for ALH transformers? II-P AND III-P are available in both protective grades 3. What is the maximum primary current of ALH transformer? The maximum primary side current is 8 ...

Siemens APT Relays – The difference between AC relays and DC relays Siemens APT Relays – The difference between AC relays and DC relays

1. Structural characteristics of AC relays The coil of the AC relay is shorter, and the wire diameter is thicker, mainly because the coil is passed through the alternating current, the reactance is larger, and the thick wire diameter can reduce the internal resistance and reduce the heat generation.

Siemens APT Pushbutton Switches – How Many Types of Pushbutton Switches Are There? Siemens APT Pushbutton Switches – How Many Types of Pushbutton Switches Are There?

There are several types of pushbutton switches: Pushbutton switches can be classified according to the way they are protected and how they are operated. It can be divided into open type and protected type, as well as waterproof type and anti-corrosion type, etc. And explosion-proof, knob-type, key-type, emergency-type, are also its ...

Siemens APT current transformer - inspection content of current transformer Siemens APT current transformer - inspection content of current transformer

1. Regularly check whether the current transformer is overheated, check whether there is discoloration in the terminal, and check whether there are sundries in the terminal box. 2. Check whether there is oil leakage in the oil level gauge in time to ensure that the oil level meets the use standard and there is no oil leakage.

Siemens APT current transformer – the difference between the ratio on a current transformer and the ratio on a watt-hour meter Siemens APT current transformer – the difference between the ratio on a current transformer and the ratio on a watt-hour meter

1. Differences in use The conversion ratio of the current transformer is inconsistent with the transformation ratio of the ammeter, which will lead to the inability to use the displayed value of the ammeter directly, and the proportional conversion must be carried out; If the transformer of ratio 5 is used on the meter of ratio 1, the secondary current of CT will generally exceed 1A, so that the transformer of 5 is used on a meter of 1 ratio. Than 1 ...

Siemens APT - AD16 series indicator frequently asked questions Siemens APT - AD16 series indicator frequently asked questions

1. Why does the indicator light still glow after the control power supply has been disconnected? This situation is caused by the presence of interference voltage, and this problem can be solved by ordering our anti-interference indicator light 2. What are the operating hours of the AD16 series indicators? More than 30000 small ...

Siemens APT Relays - Maintenance Methods for Solid State Relays Siemens APT Relays - Maintenance Methods for Solid State Relays

1. The influence of the ambient temperature The load capacity of the solid state relay is greatly affected by the ambient temperature and its own temperature rise, during the use of the device, it should be ensured that it has good heat dissipation conditions, the rated working current of more than 10A products should be equipped with radiators, and the products above 100A should be dissipated.

Siemens APT Relays – What are the types of protection relays? Siemens APT Relays – What are the types of protection relays?

Overcurrent Relay (OCR) It operates when a certain value or greater of current flows through. There are two elements: overcurrent detection (known as a timing element) and short-circuit current detection (as an instantaneous element). Earth Fault Overcurrent Relays (OCGR, GR) While...

Siemens APT Relays – The action of high and low voltage relays and how to adjust the low voltage side Siemens APT Relays – The action of high and low voltage relays and how to adjust the low voltage side

1. Disconnect the control power supply: Before making the low-voltage terminal contact adjustment, the control power supply should be disconnected first to avoid the current directly or indirectly passing through the relay contact, and avoid electric shock or damage to the relay. 2. Open the relay cover: Open the relay cover, you can see the inside of the relay.

Siemens APT Relays - Selection Method for Solid State Relays Siemens APT Relays - Selection Method for Solid State Relays

1. When selecting the solid-state relay used in the printed circuit board with small current specifications, because the lead terminal is made of high thermal conductivity material, the soldering should be carried out under the condition that the temperature is less than 250 °C and the time is less than 10S.

Siemens APT Relays – an introduction to the new type of relay Siemens APT Relays – an introduction to the new type of relay

The new relay refers to the electromagnetic relay developed and produced in order to meet the special requirements of the new and meet the use of special environmental conditions, its main characteristics are small size, light weight, vibration resistance, shock resistance, load range from low level load to 5A, 28 V rated load, product ...

What are the main problems with Siemens APT Relays – Solid State Relays? What are the main problems with Siemens APT Relays – Solid State Relays?

When the solid state relay is open and there is voltage at the load end, there will be a certain leakage current at the output end, and care should be taken to prevent electric shock when using or designing. When the solid-state relay fails to be replaced, the original model or the product with the same technical parameters should be selected as far as possible, so as to match the original application line and ensure that the system ...

Siemens APT relay - the use of solid state relay pay attention to five major matters Siemens APT relay - the use of solid state relay pay attention to five major matters

1. The resistive load should not exceed 60% of the rated current; 2. Overcurrent and load short circuit may cause permanent failure of the internal thyristor in SSR, so it is necessary to install a fuse or air switch, and a fuse can be used if the capacity is small; 3、 ...

Siemens APT current transformer - how to choose a current transformer? Siemens APT current transformer - how to choose a current transformer?

First, the principle of primary parameter selection of current transformer The rated primary current of the current transformer is determined by the actual load of the tested circuit, and the rated primary current of the current transformer should not be less than the rated primary current of the circuit.

Siemens APT Relays – What are the functions of relays? Siemens APT Relays – What are the functions of relays?

(1) Isolation between input and output circuits; (2) signal conversion; (3) Add output circuit; (4) repetitive signal; (5) Switch between different voltage or current loads; (6) Retain the output signal; (7) Locking circuit; (8) Provide remote control ...

Siemens APT limit switches – what are the limits used for? Siemens APT limit switches – what are the limits used for?

daily life There are many applications of travel switches, and it is found in many electrical appliances. So what does such a simple switch do? It mainly plays the role of chain protection. The most common example is its use in washing machines and tape recorders (VCRs). ...

Introduction to the advantages and disadvantages of Siemens APT relays - solid state relays Introduction to the advantages and disadvantages of Siemens APT relays - solid state relays

merit 1. High life, high reliability: solid state relay has no mechanical parts, the contact function is completed by solid devices, because there are no moving parts, so it can work in a high impact and vibration environment.

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top