Yaskawa servo motor - common faults and maintenance methods of servo drives

Create Date: 2024-8-30 12:03:23|Source: YASKAWA/Yaskawa

1. The LED light is green, but the motor does not move

(1) Cause of failure: The motor in one or more directions is prohibited from operating.

Solution: Check the +INHIBIT and –INHIBIT ports.

(2) Cause of failure: The command signal is not to the driver signal.

Solution: Connect the command signal ground to the drive signal ground.

2. After powering on, the LED light of the driver does not light up

Cause of failure: The power supply voltage is too low, less than the minimum voltage value requirement.

Solution: Check and increase the supply voltage.

3. When the motor rotates, the LED light flashes

(1) Fault cause: HALL phase error.

Solution: Check whether the phase setting switch of the motor is correct.

(2) Cause of failure: HALL sensor failure.

Solution: Detect the voltage of HallA, HallB, and HallC when the motor is rotating. The voltage value should be between 5VDC and 0.

4. The LED light is always kept red

Fault Cause: A fault exists.

Solution: Cause: Overvoltage, Undervoltage, Short Circuit, Overheating, Driver Prohibition, HALL Invalid.

5. The motor stalls

(1) Cause of failure: The polarity of the speed feedback is wrong.

Solution:

a. If possible, hit the position feedback polarity switch to another position. (Yes on some drives)

b. If using a speed tester, switch the TACH+ and TACH- on the drive.

c. If an encoder is used, switch the ENCA-ENCB and ENCB on the drive.

d. If in HALL speed mode, switch HALL-1 and HALL-3 on the drive, and then switch Motor-A and Motor-B.

(2) Cause of failure: When the encoder speed feedback, the encoder power supply loses power.

Solution: Check that the 5V encoder power supply is connected. Make sure that the power supply can provide enough current. If using an external power supply, make sure that the voltage is signaled to ground for the driver.

6. The motor runs faster in one direction than the other

(1) Cause of failure: The phase of the brushless motor is wrong.

Solution: Detect or detect the correct phase.

(2) Cause of failure: When not used for testing, the test/deviation switch hits the test position.

Solution: Put the test/deviation switch at the deviation position.

(3) Cause of failure: The position of the deviation potentiometer is incorrect.

Solution: Reset.

7. When the oscilloscope checks the current monitoring output of the driver, it is found that it is all noise and cannot be read

Cause of failure: The current monitoring output is not isolated from the AC power supply (transformer).

Solution: It can be detected and observed with a DC voltmeter.

8. How to deal with the motor deviation counter overflow error when the servo motor rotates at high speed?

(1) Cause of failure: motor deviation counter overflow error occurs when rotating at high speed;

Solution: Check whether the wiring of the motor power cable and encoder cable is correct, and whether the cable is damaged.

(2) Cause of failure: motor deviation counter overflow error occurs when long instruction pulse is input;

Solution: a. If the gain setting is too large, adjust the gain manually again or use the automatic gain adjustment function;

b. Extend the acceleration and deceleration time;

c. If the load is too heavy, it is necessary to re-select a motor with a larger capacity or reduce the load, and install a reducer and other transmission mechanisms to improve the load capacity.

(3) Cause of failure: motor deviation counter overflow error occurs during operation.

Solution: a. Increase the set value of the overflow level of the deviation counter;

b. Slow down the rotation;

c. Extend the acceleration and deceleration time;

d. If the load is too heavy, it is necessary to re-select a motor with a larger capacity or reduce the load, and install a reducer and other transmission mechanisms to improve the load capacity.

9. How to deal with the servo motor not running when there is pulse output?

(1) Monitor the current value of the pulse output of the controller and whether the pulse output light is flashing, and confirm that the command pulse has been executed and the pulse has been output normally;

(2) Check whether the control cable, power cable and encoder cable from the controller to the driver are wired incorrectly, damaged or in poor contact;

(3) Check whether the brake of the servo motor with brake has been opened;

(4) Monitor the panel of the servo driver to confirm whether the pulse command is input;

(5) The Run command is normal;

(6) The control mode must be selected as the position control mode;

(7) Whether the input pulse type set by the servo drive is consistent with the setting of the instruction pulse;

(8) Make sure that the forward side drive is inhibited, the reverse side drive inhibition signal and the deviation counter reset signal are not entered, the load is disconnected and the no-load operation is normal, and the mechanical system is checked.
Yaskawa servo motor - common faults and maintenance methods of servo drives

More on that
Fault codes for Yaskawa servo drives Fault codes for Yaskawa servo drives

1. If the fault code on the Yaskawa servo drive is UV1, it means that the low voltage of the main circuit is lower than the low voltage standard of 200V, at this time, we need to check whether there is a problem with the wiring of the power supply; 2. If the ...

Parameter setting steps of Yaskawa H1000 inverter Parameter setting steps of Yaskawa H1000 inverter

1. No-load power-on test of inverter 1. Ground the grounding terminal of the inverter. 2. Connect the power input terminal of the inverter to the power supply through the leakage protection switch. 3. Check whether the factory display of the inverter display window is normal, if it is incorrect, it should be reset, otherwise ...

Yaskawa Robot's DeviceNet communication steps Yaskawa Robot's DeviceNet communication steps

1. Hardware installation @以下操作务必在安川机器人断电状态下执行. 1. Remove the corresponding screws and pull out the bus bracket. 2. Remove the front bezel 3. Insert the DeviceNet substrate and tighten the front plate screws. 4. Insert the board unit as a whole ...

Yaskawa Electric's development areas Yaskawa Electric's development areas

Drive control Yaskawa Electric's Drive Control Division has achieved a leading position in the industry by integrating and commercializing various innovations and the world's latest technologies into inverters. These technologies have penetrated into various fields as world standards, and the quality, performance, ...

Explain in detail the setting method of arc static during welding of Yaskawa welding robot Explain in detail the setting method of arc static during welding of Yaskawa welding robot

1. Conditions for the static characteristics of the arc of Yaskawa welding robots In the welding production process, once the electrode material, gas medium and arc length are maintained, as long as the arc of the Yaskawa welding robot can burn stably, the welding current and arc voltage will show corresponding changes.

Yaskawa Robotics - A detailed introduction to the robot's control and perception system Yaskawa Robotics - A detailed introduction to the robot's control and perception system

Control system The robot control system is the brain of the robot and is the main element that determines the function and function of the robot. The control system is to retract the command signal to the drive system and the implementation mechanism according to the input program, and control it. The main task of industrial robot control technology is ...

Yaskawa Servo Alarm C90 (AC9) Alarm Cause Analysis and Solution Yaskawa Servo Alarm C90 (AC9) Alarm Cause Analysis and Solution

1. Analysis of the causes of Yaskawa servo alarm C90 (AC9): 1. The encoder cable is broken or the encoder plug is made in poor process (there are also wiring errors in the alarm of the new machine); 2. The servo drive itself is faulty; 3. Environmental interference, caused by poor connection: ...

What industries can Yaskawa Robotics GP180 be used in? What industries can Yaskawa Robotics GP180 be used in?

1. Automobile manufacturing: In the automotive manufacturing industry, Yaskawa Robot GP180 can be used for welding, dispensing, cutting, and assembly, etc. 2. Electronics industry: In the electronics industry, Yaskawa Robot GP180 can be used for semiconductor chip production, mobile phone assembly, etc. 3. Food ...

How to deal with Yaskawa servo alarm 840? How to deal with Yaskawa servo alarm 840?

1. Encoder malfunction. When the power is turned on again and this alarm still occurs, it is possible that the servo motor is faulty, and the servo motor is replaced; 2. Encoder malfunction due to noise and other interference. Correct handling of the wiring around the encoder (separating the encoder cable from the servo motor ...

Yaskawa Robotics - the main functions and components of industrial robot controllers Yaskawa Robotics - the main functions and components of industrial robot controllers

The main functions of the industrial robot controller The controller mainly solves the forward kinematics and inverse kinematics of the robot to help the robot complete the trajectory planning. The controller of the industrial robot is composed of controller hardware and controller software.

Yaskawa launches new products – the next-generation servo products Σ-X series and the new data collection controller YRM-X Yaskawa launches new products – the next-generation servo products Σ-X series and the new data collection controller YRM-X

  At 10 a.m. on December 23, 2022, Yaskawa Electric held an online new product launch conference and officially released the next-generation servo products Σ-X series and the new data collection controller YRM-X. Advanced and optimized motion performance and digital solutions starting with servo are the two major features of this new product.

Advantages of Yaskawa Industrial Robots Advantages of Yaskawa Industrial Robots

Advantages of Yaskawa Industrial Robots   Generalization Programmable industrial robots that support multiple degrees of freedom of motion make the application more flexible. Although not human, compared to many general-purpose industrial automation aircraft (a class dedicated to industrial applications or customized mechatronic solutions), ...

Summary of Yaskawa MOTOMAN Servo Drive Fault Repair Cases (5-7) Summary of Yaskawa MOTOMAN Servo Drive Fault Repair Cases (5-7)

5. After powering on, the LED light of the driver does not light up; Cause of failure: The power supply voltage is too low, less than the minimum voltage value requirement. Solution: Check and increase the supply voltage. 6. When the motor rotates, the LED light flashes; (1) Cause of failure: HALL phase ...

A robot village opened to commemorate the 100th anniversary of Yaskawa Electric A robot village opened to commemorate the 100th anniversary of Yaskawa Electric

Japan's Yaskawa Electric famously created the first all-electric industrial robot, Motoman, in 1977, headquartered in the city of Kita-Kyushu, since its establishment in 1915, has gone from being called "Yaskawa Electric Japan as an automobile manufacturer", "Yaskawa Electric Automation Company of Japan" to "...

YASKAWA The success of industrial automation starts here YASKAWA The success of industrial automation starts here

Founded in 1989, Yaskawa Motoman is a leading industrial robotics company in the Americas. With more than 400,000 Motoman industrial robots, 15 million servos and 26 million inverter drives installed worldwide, Yaskawa provides automation products and ...

Causes and solutions of Yaskawa servo drive alarm code 710 Causes and solutions of Yaskawa servo drive alarm code 710

Yaskawa servo drive alarm code 710 is overload (large load), the motor is overloaded for a few seconds to tens of seconds. Solution(s): 1. Change the mechanism, or the acceleration and deceleration mechanism. 2. Change the motor. 3. Exclusion order: (1) The load is really too large ...

The phenomenon that occurs when the various parts of Yaskawa inverter are damaged The phenomenon that occurs when the various parts of Yaskawa inverter are damaged

1) Main control board When the main control board is damaged, the operation panel may not be displayed, the motor may be sluggish, and there will be jitter during the operation, or there may be no action. External instructions are not acceptable, the multifunction input signal is not displayed (there is no change in U1-10). 2) Driver board ...

Yaskawa inverter – how to check for inverter failure Yaskawa inverter – how to check for inverter failure

1. Static test 1. Test the rectifier circuit Find the P and N ends of the DC power supply inside the inverter, adjust the multimeter to the resistance X10 gear, connect the red watch rod to P, and separate the black watch rod to R, S, T. Instead, take the black watch rod ...

Yaskawa inverter - maintenance method of low-voltage inverter Yaskawa inverter - maintenance method of low-voltage inverter

1. Countermeasures to the overheating problem of inverter 1. For places where the operating environment temperature of the inverter is high, it is recommended to reduce the temperature of the inverter and strengthen cooling and ventilation; 2. Increase the frequency of regular maintenance of inverter fans, air ducts, etc., so as to improve the operating environment of the inverter, so that the inverter ...

Yaskawa robot maintenance method Yaskawa robot maintenance method

1. When the oscilloscope checks the current monitoring output of the driver, it is found that it is all noise and cannot be read; Cause of failure: The current monitoring output is not isolated from the AC power supply (transformer). Solution: It can be detected and observed with a DC voltmeter. 2. Motor ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top