The basic method and steps of inverter debugging - power inverter

Create Date: 2024-8-30 12:03:23|Source: LS/Power Generation

1. No-load energizing test of inverter

1. Ground the grounding terminal of the inverter.

2. Connect the power input terminal of the inverter to the power supply through the leakage maintenance switch.

3. Check whether the factory display window of the inverter is normal, if it is incorrect, it should be reset, otherwise it will be returned.

4. Be familiar with the operation keys of the inverter. The general inverter has 6 buttons, such as RUN, STOP, PROG, DATAPENTER, UP and ▲, and DOWN. In addition, some inverters also have function keys such as MONITORPDISPLAY, RESET, JOG, and SHIFT.

                                    The basic method and steps of inverter debugging - power inverter

2. The inverter runs with motor without load

1. To set the power and number of poles of the motor, the operating current of the inverter should be comprehensively considered.

2. Set the maximum output frequency, fundamental frequency, and torque characteristics of the inverter. The general inverter is equipped with a number of VPf curves for users to choose, and users should choose the appropriate VPf curves according to the nature of the load when using. In the case of fan and pump loads, the torque operation code of the inverter should be set to the variable torque and reduced torque operation characteristics. In order to improve the low-speed function when the inverter is started, so that the torque output of the motor can meet the requirements of production load starting, the starting torque should be adjusted. In the frequency conversion speed regulation system of asynchronous motor, the control of torque is more complicated. In the low frequency band, due to the influence of resistance and leakage reactance, if VPf is still maintained, the magnetic flux will be reduced, and the output torque of the motor will be reduced. For this reason, the voltage is appropriately compensated in the low frequency band to increase the torque. Generally, the inverter is manually set and compensated by the user.

3. Set the inverter to the built-in keyboard operation form, press the run key and stop button, and check whether the motor can start and stop normally.

4. Familiar with the maintenance code when the inverter runs faulty, investigate the factory value of the thermal maintenance relay, investigate the setting value of overload maintenance, and correct it when necessary. The operator of the inverter can set the electronic thermal relay function of the inverter according to the operating manual of the inverter. When the output current of the inverter exceeds its allowable current, the overcurrent maintenance of the inverter will cut off the output of the inverter. Therefore, the maximum threshold of the inverter's electronic thermal relay does not exceed the maximum allowable output current of the inverter.

3. Test run with load

1. Manually operate the operation stop button of the inverter panel, investigate the operation stop process of the motor and the display window of the inverter to see if there is any abnormal phenomenon.

2. If the inverter presents an overcurrent maintenance action during the process of starting the P abort motor, the deceleration time of P should be set from the beginning. The acceleration of the motor during acceleration and deceleration depends on the acceleration torque, while the frequency change rate of the inverter during the start and braking process is set by the user. If the moment of inertia of the motor or the load of the motor changes, when the speed is increased or decelerated according to the preset frequency change rate, it may not accelerate the torque enough, and then form a motor stall, that is, the motor speed is not coordinated with the output frequency of the inverter, and then overcurrent or overvoltage is formed. Therefore, it is necessary to reasonably set the acceleration and deceleration time according to the moment of inertia and load of the motor, so that the frequency change rate of the inverter can be coordinated with the speed change rate of the motor.

More on that
Inverter maintenance principle analysis and inspection method Inverter maintenance principle analysis and inspection method

Principle analysis is the most fundamental way to eliminate the problem, when other methods are difficult to see the effect, you can start from the basic principle of the circuit, step by step to view, and finally find out the cause of the problem. To use this method, it is necessary to have a clear understanding of the principle of the circuit, and to grasp the various ...

LS power generation low-voltage universal inverter vector control mode LS power generation low-voltage universal inverter vector control mode

The method of vector control frequency conversion speed regulation is to change the stator current Ia, Ib, Ic of the asynchronous motor in the three-phase coordinate system, after the three-phase - two-phase change, equivalent to the communication current Ia1Ib1 under the two-phase static coordinate system, and then after the directional rotation according to the rotor magnetic field, it is equivalent to synchronous rotation sitting.

Application of servo motor - LS power generation Application of servo motor - LS power generation

Quick to use: There are three cables necessary for the operation of the motor: power cable; Motor power line, motor encoder line. Control line interface X5: Servo enable necessary pin C24V power supply (7,41) Servo enable SR ...

Inverter life extension method - LS power generation Inverter life extension method - LS power generation

1. The inverter should not be installed on the equipment with a sensation, because the main circuit connection screw in the inverter is easy to loosen, and many inverters are damaged due to this reason. 2. Wiring problem: the input terminal of the inverter should be connected to a ...

Communication control of inverter - power inverter Communication control of inverter - power inverter

The communication control of the inverter is more complicated, so it is listed separately. The communication control of the inverter is a control method for the operation, speed regulation and status indication of the inverter through the communication interface of the inverter. ...

Dealing with intermittent shutdown fault measures - power generation Dealing with intermittent shutdown fault measures - power generation

Because the touch of the network adapter is not good, perhaps due to disturbance and other problems, the DP network that has been used for a long time may show a "transient disconnection" situation, that is, it will be disconnected by an occasional moment, and it will soon recover normally. If OB86 is not downloaded, the CPU will stop during a transient outage. Now all over the option to download a ...

Safety precautions for LS inverters Safety precautions for LS inverters

1. When the power supply is now powered or the inverter is in operation, do not open the shell of the inverter. Otherwise, an electric shock may occur. 2. When the front cover of the inverter is opened, do not run the inverter. Otherwise, you may be subjected to ...

The five stages of mastery of PLC technology The five stages of mastery of PLC technology

One. Logical stage   The so-called logical stage is to be able to complete the general logical planning in the relay system, since it is a relay system, so the knowledge of power drag is the foundation of this stage. I personally summarize that the root of learning the relay system lies in the word "grab", the relay system ...

LS Electric has been selected as one of the "Top 100 Global Innovators" for 10 consecutive years. LS Electric has been selected as one of the "Top 100 Global Innovators" for 10 consecutive years.

In Clarivate's recent statement, LS Electric was named one of the top 100 innovators in the world. The trophy handover ceremony was held in Anyang, LS Electric R&D Park, with Kim Yeong-geun, Chief Technical Officer of LS Electric, and Ahn Seong-sik, CEO of Clarivate Korea, acting as representatives of both parties.

The application of the inverter to supply power to the motor has encountered a problem The application of the inverter to supply power to the motor has encountered a problem

A frequency converter is a device that converts power to other frequencies of power supply. The power frequency of our country is 50Hz, in the field of motors, in order to change the speed of the motor, or other performance changes, many motors choose inverter power supply. ...

After the contactor is energized, the start button continuously engages and disconnects ?—— LS generates power After the contactor is energized, the start button continuously engages and disconnects ?—— LS generates power

What is the reason why the contactor keeps engaging and disconnecting by pressing the start button after the AC contactor is energized? In my personal opinion, most of the situation is caused by the wrong coil voltage of the replacement AC contactor, or the purchase of ...

Analysis of the selection of major ventilator inverters - LS power generation Analysis of the selection of major ventilator inverters - LS power generation

Now enterprises need to use a lot of ventilator inverters, the larger the scale of the enterprise, the more production workshops, the more ventilator inverters will be used. However, no matter how large the enterprise, there is a primary ventilator inverter, the selection of this kind of inverter is very important, because if there is no ...

Introduction to electrical equipment - LS Electricity Introduction to electrical equipment - LS Electricity

According to the requirements of safe, high-quality, reliable and economical operation of the production, transforming, transportation, distribution and use of electric energy in power plants and substations, the following electrical equipment is mainly included. 1. Primary equipment Directly involved in production, ...

The difference between LS power inverter and servo The difference between LS power inverter and servo

An important difference between servo and frequency conversion is that frequency conversion can be without encoder, while servo must have an encoder for electronic commutation. 1. What the two have in common: The AC servo technology itself is to learn and apply the technology of frequency conversion, and the servo control of the DC motor is based on the ...

Inverter overvoltage fault analysis method - LS power generation Inverter overvoltage fault analysis method - LS power generation

The overvoltage of the inverter is manifested in the tributary voltage of the DC bus. Under normal conditions, the direct current of the inverter is the average value of the three-phase full-wave rectification. If calculated by 380V line voltage, the average DC voltage Ud=1.35U line=513V.

Introduction to the control method of LS power inverter Introduction to the control method of LS power inverter

Inverter control method: low-voltage general frequency conversion output voltage is 380-650V, output power is 0.75-400kW, operating frequency is 0-400Hz, and its main circuit adopts AC-DC-AC circuit. Its control methods have gone through the following five generations. 1U/f=C sine pulse width modulation ...

The inverter selects the appropriate peripheral equipment - LS power generation The inverter selects the appropriate peripheral equipment - LS power generation

After we have selected a suitable Variable-frequency Drive (VFD), we also need to consider whether we need to equip other peripheral equipment according to the actual situation of the site. The peripheral equipment selected by VFD mainly includes circuit breakers, reactors, contactors, braking resistors, etc. ...

LS has reached agreements with Doosan and Hanwha in Korea on a business model for vacuum power generation LS has reached agreements with Doosan and Hanwha in Korea on a business model for vacuum power generation

LS Electric recently signed an MOU agreement with Doosan Fuel Cell, Hanwha Power Systems, and Hanwha Asset Management in Seoul, Korea, to establish a business partnership for city gas companies to develop a fuel cell-vacuum power generation business model. Through this agreement, the two sides will expand the scope of cooperation ...

An internal component of LS's power circuit breaker An internal component of LS's power circuit breaker

1. Auxiliary contact: the contact mechanically linked with the main circuit of the circuit breaker and the closing mechanism is mainly used for the display of the circuit breaker and the closing status, and is connected to the control circuit of the circuit breaker through the opening and closing of the circuit breaker to control or interlock its related electrical appliances. For example, output to signal lights, relays, etc.

Precautions for the maintenance of the inverter of the tensile testing machine - LS generates electricity Precautions for the maintenance of the inverter of the tensile testing machine - LS generates electricity

In the course of regularly checking the variable-frequency drive (VFD) of the tensile testing machine, we can visually check the operating status directly from the outside. (1) The ambient temperature is normal, and it is required to be between -10°C and +40 ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top