Delta inverter fault alarm code and solution

Create Date: 2024-8-30 12:03:23|Source: Delta/Delta

The OCC AC motor driver detects an unusual overcurrent surge on the output side

                               Delta inverter fault alarm code and solution

See if the motor extra matches the communication motor drive extra

Check whether there is a short circuit between the communication motor driver U-V-W

Check whether there is a short circuit or grounding in the connection with the motor

Check whether the screws of the motor driver and motor are loose, lengthened, and accelerated at the moment

Check to see if the motor is overloaded

The OU communication motor driver detects the occurrence of overvoltage on the internal DC high-voltage side

Check whether the input voltage is within the additional input voltage range of the AC motor driver, and monitor whether there is a surge voltage

If the voltage on the DC high-voltage side of the AC motor driver is too high due to the motor inertia rising voltage, the deceleration room can be lengthened or a braking resistor can be installed (optional)

The OH AC motor driver detects that the internal temperature is too high and exceeds the maintenance level

Check to see if the ambient temperature is too high

Check the heatsink for foreign objects. Whether the fan is rolling or not

Check to see if there is enough ventilation space for the communication motor drive

The LU communicates that the DC high side inside the motor driver is too low

Check whether the input power supply voltage is normal

Check whether the load has a sudden heavy load, whether the three-phase single-phase power supply is in-force or under-phase

The OL output current exceeds the current acceptable by the AC motor driver, and is acceptable for 60 seconds if 150% of the additional current is output from the AC motor driver.

Check if the motor is overloaded

Reduced (07-02) torque, increased setpoint, increased communication motor driver output capacity

OL1 internal electronic thermodynamic post maintenance action

Check to see if the motor is overloaded

Check (07-00) if the additional current value of the motor is appropriate

Check the function settings of the electronic thermoelectric station

Add motor capacity

OL2 internal electronic thermodynamic post maintenance action

Check to see if the motor is overloaded

Check (07-00) if the additional current value of the motor is appropriate

Check the function settings of the electronic thermoelectric station

Add motor capacity

HPF.1 controller hardware maintenance circuit is abnormal, please send it back to the original factory

HPF.2 Controller Hardware Maintenance Circuit Abnormality CC (Current Clamping) Hardware Maintenance Circuit Abnormality, please send it back to the original factory

HPF.3 controller hardware maintenance circuit is abnormal OC hardware maintenance line abnormal, please send it back to the original factory

HPF.4 controller hardware maintenance circuit is abnormal, please send it back to the original factory

bb when the external multi-function input terminals (MI1 - MI6) are set

When it is functional, the communication motor driver aborts the output and the eradication signal source "bb" disappears immediately

OCA accelerates medium overcurrents

Check whether the screws communicating the motor driver and motor are loose

Check whether the wiring from U-V-W to the motor is poorly insulated

Add a speeding moment

Reduce (7-02) torque and increase the setpoint

Replace a larger output capacity communication motor driver

Overcurrent occurs during OUD deceleration

Check whether the wiring from U-V-W to the motor is poorly insulated

The deceleration time is extended

Replacement of large output capacity communication motor drivers

Overcurrent occurs during OCN operation

Check whether the wiring from U-V-W to the motor is poorly insulated

Check whether the motor is stalled

Replacement of large output capacity communication motor drivers

When the external EF terminal is closed, communicate with the motor driver to abort the output and eliminate the source of the fault, and then press the "RESET" button

EF When the external multi-function input terminals (MI1 – MI6) are set tightly

When EF1 is aborted urgently, the communication motor driver aborts the output After eradicating the source of the problem, press the "RESET" button

CF1 internal memory IC material writing abnormally sent to the factory for repair

CF2 Internal Memory IC Material Reading Abnormality Press the RESET key to reset the parameters to factory settings, if the method is invalid, send it to the factory for repair

CF3.3 Communication Motor Driver Detection Line Abnormality U-phase current sensor abnormality, please send it to the factory for repair

CF3.4 Communication Motor Driver Detection Line Abnormality V-phase current sensor abnormality, please send it to the factory for repair

CF3.5 AC Motor Driver Detection Line Abnormality W-phase current sensor abnormality, please send it to the factory for repair

CF3.6 Communication Motor Driver Detection Line Abnormality DC Voltage Measurement (DC-BUS) Detection Line Abnormality, Please send it to the factory for repair

CF3.7 Communication Motor Driver Detection Line Abnormality Isum Analog/Digital Line Abnormality, please send it to the factory for repair

CF3.8 Communication Motor Driver Detection Circuit Abnormality Abnormal temperature sensor, please send it to the factory for repair

GFF Grounding Maintenance Line Action. When the AC motor driver detects that the output terminal is grounded and the ground current is higher than 50% of the additional current of the AC motor driver. Note: This maintenance is for the communication motor drive, not the human body.

Check whether there is a short circuit or grounding in the connection with the motor to confirm whether the IGBT power module is damaged

Check the output side wiring for poor insulation

The CFA automatic acceleration and deceleration mode failed

Communicate whether the motor drive is properly matched with the motor

The load recovery inertia is too large

The load changes are too abrupt

CE Communication Abnormality Check whether the communication signal is reversed (RJ11)

Check that the newsletter is in the correct format

CCODE software maintenance starts to show CcodE sent to the factory for repair

PcodE is revealed to be cipher-locked

ANLER analog signal faults

The PG return credit number is at fault

Check the parameterization (Pr 10-00) and the AVI/ACI route

View all possible faults between the time of system reaction and the moment of credit number detection (Pr 10-08)

Whether the PG card is wired correctly

PHR Underphase Maintenance Check if it's a three-phase input power

When the CEF external counter reaches the set point, an external anomaly error occurs

Look at the external counter trigger signal

Check the parameters Pr 03-39 and 03-11

AUE motor parameters automatically detect faults to check whether the motor is wired correctly

retry

Low Current View the load current

LC Check the parameters Pr 06-12, 06-15 settings
More on that
The difference between a general-purpose inverter and a vector inverter - Delta The difference between a general-purpose inverter and a vector inverter - Delta

There are two main differences between vector inverter and general inverter, the first is high control accuracy, and the other is high output torque at low speed. It can output 150%-200% of the rated torque. It should be vector frequency conversion is to decompose the motor current into D-axis current and Q-axis current, where D-axis current is excitation current ...

Inverter power-on panel without display fault analysis - Delta Inverter power-on panel without display fault analysis - Delta

In the inverter problem, it is often encountered that the energized panel does not appear. Generally speaking, the problem of the inverter panel not showing up is usually caused by three parts, one is the poor contact of the contactor, the second is the control panel of the inverter, and the third is the damage of the power module that supplies power to the control panel.

Delta's DTK series thermostat product model Delta's DTK series thermostat product model

DTK4848C01 High brightness LCD display, 48*48, Pt resistor/thermocouple input, 4-20mA output, 1 alarm DTK4848R01 High brightness LCD display, 48*48, Pt resistor/thermocouple input, relay output, 1 alarm DTK4848V01 Highlight ...

Precautions for the installation environment of the inverter - Delta inverter Precautions for the installation environment of the inverter - Delta inverter

(1) Ambient temperature: The inverter is the same as other electronic equipment, and has certain requirements for the ambient temperature, which is generally "-10-+40°C". Because the inverter is a high-power electronic equipment, it is easy to be affected by the operating temperature, but in order to ensure the safety of the inverter...

The basic methods and steps of inverter debugging - Delta inverter The basic methods and steps of inverter debugging - Delta inverter

1. No-load energizing test of inverter 1. Ground the grounding terminal of the inverter. 2. Connect the power input terminal of the inverter to the power supply through the leakage maintenance switch. 3. Check whether the factory display window of the inverter is normal, if it is incorrect, it should be reset, no ...

How to use Delta's inverter operation How to use Delta's inverter operation

(1) When the speed of the motor is controlled by the Delta inverter, the noise and temperature rise of the motor are higher than that of the frequency of the motor. When the motor is running at low speed, because the speed of the motor blades is low, the temperature rise of the motor becomes high.

Delta's PLC-Based motion controller AX3 series Delta's PLC-Based motion controller AX3 series

With the development of electronic semiconductor information technology, technologies such as the Internet of Things, big data, and cloud channels are showing a trend of hundreds of schools of thought, which also drives the rapid development of intelligent production. Intelligent production also puts forward new requirements for controllers: high speed, large capacity, miniaturization, networking...... In order to ...

The reason for the abnormal operation of Delta's inverter The reason for the abnormal operation of Delta's inverter

There are many setting parameters of the inverter, and each parameter has a certain selection scale, and the inverter can not operate normally due to the improper setting of a single parameter is often encountered in the application, therefore, the relevant parameters must be correctly set. ...

Delta's soft starter component role Delta's soft starter component role

The soft starter is a device used to control the start and stop of the motor, which is composed of a number of components, including the soft starter controller, the soft starter conditioner, the soft starter power supply, the soft starter input and output module, the soft starter interface module, etc. ...

Selection of braking resistors for Delta inverters Selection of braking resistors for Delta inverters

1. The necessity of braking resistance If the regenerative energy that occurs during deceleration and descent in the application is too large, there is a possibility that the voltage of the main circuit inside the inverter will rise, causing damage. Because usually the inverter has a built-in overvoltage maintenance function, the main circuit overvoltage (O...

The principle of Delta's inverter inverter The principle of Delta's inverter inverter

As far as I know, since the advent of active induction motors, there has been a variable frequency operation in the way of communicating generators. Change the rotational speed of the generator, and change its output frequency. Before the advent of high-speed transistors, this was one of the main ways to change the speed of the motor, but due to the decrease in the speed of the generator ...

A number of Delta's new high-end power supply products were unveiled at CMEF A number of Delta's new high-end power supply products were unveiled at CMEF

Delixi Electric's newly launched CDQ1F series PC-level excitation active transfer switch, with more complete specifications and stronger functions, the power-off time can be shortened to less than 0.1s, escorting the continuous use of electricity in important places! CDQ1F Active ...

Installation steps of motor protector – Delta Installation steps of motor protector – Delta

1. According to the requirements of the device parts, the method and the maintenance function are required, and the type of motor maintainer and its various maintenance action parameter settings are reasonably selected; 2. According to the requirements of the product instruction manual, the correct device should be connected correctly according to the purpose of each terminal, and the working power supply should be connected to the control ...

Analysis of communication problems of Delta inverters Analysis of communication problems of Delta inverters

Problem Clarification: Communication Transmission Timeout: The Modbus transmission between the VFD and the Keypad times out Solution: VFD does not respond to Keypad's communication commands. 1. Confirm the communication quality of the communication wiring and contacts. 2. Please use the RESET key to clear the Fault ...

Delta's C-series evolution is complete—C2000+ inverter Delta's C-series evolution is complete—C2000+ inverter

Those who know more about Delta's automation know that Delta's inverters have two main series: "M300" and "C2000". "Compact Inverter M300 Series": This series has been introduced many times before, including ...

Inverter environmental installation requirements and methods - Delta inverter Inverter environmental installation requirements and methods - Delta inverter

1. The environmental requirements of the inverter Ambient temperature - 10 °C - 40 °C; Ambient humidity: The relative humidity does not exceed 90% (no condensation); Other occasions that require no direct sunlight, no corrosive gas and flammable gas, and less dust, with an altitude of less than 1000m. ...

Precautions for Delta inverter C2000 series Precautions for Delta inverter C2000 series

1. Precautions for choosing a communication motor driver When using a large-capacity current transformer (more than 600kVA) and a phase-entering capacitor, the surge current on the input side of the power supply is too large, which may destroy the input side of the communication motor driver.

Delta's Amplon N series UPS ensures the safety of electricity consumption in pharmaceutical production lines Delta's Amplon N series UPS ensures the safety of electricity consumption in pharmaceutical production lines

In recent years, in response to the development trend of automation, informatization and intelligence, pharmaceutical companies have continuously innovated, transformed and upgraded, selected fully automated intelligent production lines, accelerated the upgrading of equipment in the pharmaceutical industry, and completed the use of smart pharmaceutical technology for green, safe, high-quality and low-consumption development in the pharmaceutical industry.

Analysis and correction of the cause of Delta servo drive alarm Analysis and correction of the cause of Delta servo drive alarm

Analyze and correct the cause of Delta servo drive alarms.   Control current and undervoltage protection. Alert Number: 11. Reason: The voltage at the end of the dynamic DC bus is lower than the specified value. Due to the instantaneous shortage of power supply capacity, the control voltage is too low. Measure: Measure the DC bus ...

Basic parameter setting of special inverter for wind turbine - Delta Basic parameter setting of special inverter for wind turbine - Delta

1. Control mode: i.e. speed control, torque control, PID control or other methods. After the control method is adopted, static or dynamic identification should generally be carried out according to the control accuracy. 2. Minimum operating frequency: That is, the minimum speed of the motor. When the motor is working at low speed, the ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top