The reason for the abnormal operation of Delta's inverter

Create Date: 2024-8-30 12:03:23|Source: Delta/Delta

There are many setting parameters of the inverter, and each parameter has a certain selection scale, and the inverter can not operate normally due to the improper setting of a single parameter is often encountered in the application, therefore, the relevant parameters must be correctly set.

                            The reason for the abnormal operation of Delta's inverter

1. Manipulation methods

i.e. speed control, rotation control, PID control, or other methods. After adopting the control method, static or dynamic identification is generally carried out according to the control accuracy.

2. Low operating frequency

That is, the small speed of motor operation, when the motor is operating at low speed, its heat dissipation function is very poor, and the motor will be operated at low speed for a long time, which will cause the motor to burn out. And at low speeds, the current in the cable will also increase, which will also cause the cable to heat up.

3. High operating frequency

The general frequency converter has a large frequency to 60Hz, and some even to 400 Hz, and the high frequency will make the motor work at high speed, which is for ordinary motors, and its bearings can not be operated at a long-term over-rated speed, whether the rotor of the motor can withstand such centrifugal force.

4. Carrier frequency

The higher the carrier frequency setting, the larger the higher harmonic component, which is closely related to the length of the cable, the heating of the motor, the heating of the cable and the heating of the inverter.

5. Motor parameters

The inverter sets the power, current, voltage, speed, and maximum frequency of the motor in the parameters, and these parameters can be directly obtained from the motor nameplate.

6. Frequency hopping

At a certain frequency point, there is a possibility of resonance, especially when the whole device is relatively high; When operating the compressor, avoid the surge point of the compressor.

7. Acceleration and deceleration moments

The acceleration time is the time required for the output frequency to rise from 0 to the highest frequency, and the deceleration time is the time required to decrease from the largest frequency to 0. Acceleration and deceleration times are usually confirmed by the rise and fall of the frequency setting signal. When the motor accelerates, the rise rate of the frequency setting must be constrained to avoid overcurrent, and when the motor is decelerating, the fall rate must be constrained to avoid overvoltage.

Speed up the time setting requirements: the acceleration current is constrained below the overcurrent capacity of the inverter, so that the overflow will not cause the inverter to trip; The key to setting the deceleration time is to avoid excessive voltage of the smoothing circuit, and not to cause the regenerative overvoltage to stall and trip the inverter. The acceleration and deceleration time can be calculated according to the load, but in the debugging, it is often used to set a longer acceleration and deceleration time according to the load and experience, and investigate whether there is an overcurrent and overvoltage alarm after starting and stopping the motor; Then the acceleration and deceleration time is gradually shortened, and the operation is not generated as the criterion, and the operation is repeated several times to confirm the best acceleration and deceleration time.

8. Torque increase

Also known as torque compensation, it is a method to increase the low-frequency scale f/V in order to compensate for the decrease in torque at low speed caused by the resistance of the stator winding of the motor. When set to active, the voltage at the time of acceleration can be actively increased to compensate for the starting torque, so that the motor can be accelerated smoothly. If manual compensation is used, the best curve can be selected according to the load characteristics, especially the starting characteristics of the load. Regarding the variable torque load, if it is not selected properly, the output voltage at low speed will be too high, and the electric energy will be wasted, and even the current will be large when the motor is started with load, and the speed cannot go up.

9. Electronic thermal overload maintenance

This function is set to maintain the overheating of the motor, which is that the CPU in the inverter calculates the temperature rise of the motor according to the operating current value and frequency, and then performs overheating maintenance. This function is only applicable to the occasion of "one to one", and in the case of "one to many", thermal relays should be installed on each motor.

Electronic Thermal Maintenance Setpoint (%) = [Motor Rated Current (A) / Inverter Rated Output Current (A)]×100%.

10. Frequency Constraints

That is, the upper and lower amplitudes of the output frequency of the inverter. Frequency constraint is a maintenance function to avoid misoperation or external frequency setting signal source problems, and the output frequency is too high or too low, so as to prevent damage to the equipment. In use, it can be set according to the actual situation. This function can also be used for speed limiting, such as belt conveyor, because the transport material is not too much, in order to reduce the wear and tear of machinery and belt, the inverter can be driven, and the upper frequency of the inverter is set to a certain frequency value, so that the belt conveyor can operate at a fixed, lower operating speed.

11. Bias frequency

Some are also known as error frequency or frequency error setting. Its purpose is to adjust the frequency to set the bump of the output frequency when the signal is low when the frequency is set by an external analog signal (voltage or current). When the frequency setting signal is 0%, the error value can be in the scale of 0 - fmax, and some inverters (such as Mingdianshe and Sanken) can also set the bias polarity. If the output frequency of the inverter is not 0Hz but xHz when the frequency setting signal is 0% in the debugging, then the bias frequency can be set to negative xHz to make the output frequency of the inverter 0Hz.

12. Frequency setting signal gain

This function is only useful when setting the frequency with an external analog signal. It is used to compensate for the inconsistency between the externally set signal voltage and the internal voltage (+10V) of the inverter; When the imitation input signal is large (such as 10v, 5v or 20mA), find the frequency percentage that can output the f/V graph and set it as a parameter; If the external setting signal is 0 - 5V, if the output frequency of the inverter is 0 - 50Hz, the gain signal can be set to 200%.

13. Torque constraint

There are two types of driving torque constraint and brake torque restraint. It is based on the output voltage and current values of the inverter, and the torque is calculated by the CPU, which can significantly improve the shock load recovery characteristics during acceleration and deceleration and constant speed operation. The torque restraint function enables active acceleration and deceleration control. Assuming that the acceleration and deceleration time is less than the load inertia time, the motor can also be ensured to actively accelerate and decelerate according to the torque set value.

The driving torque function provides a strong starting torque, in the steady-state operation, the torque function will control the motor to deteriorate, and the motor torque is constrained within the largest set value, when the load torque suddenly increases, and even when the acceleration time is set too short, it will not cause the inverter to trip. When the acceleration time is set too short, the motor torque will not exceed the maximum set value. A large drive torque is good for starting, so it is better to set it to 80 - 100%.

The smaller the braking torque setting value, the greater the braking force, which is suitable for the occasion of rapid acceleration and deceleration, such as the overvoltage alarm phenomenon when the braking torque setting value is set too much. If the braking torque is set to 0%, the total amount of regeneration applied to the main capacitor can be close to 0, and then the motor can be decelerated to a stop without using a braking resistor when decelerating. However, on some loads, such as when the braking torque is set to 0%, there will be a short idling phenomenon when decelerating, resulting in repeated start of the inverter, a large fluctuation of the current, and in serious cases, the inverter will trip, which should be noted.

More on that
Use and maintenance of electric motors - Delta motors Use and maintenance of electric motors - Delta motors

The motor can be started after the work is completed before use, and attention should be paid to the investigation of the motor, transmission device, production machinery and line voltage and ammeter, if there is an abnormal phenomenon, it should be stopped immediately, the fault should be identified and swept away, and then it can be closed and started again. When the motor is running, ...

Precautions for long-term idle use of Delta inverter Precautions for long-term idle use of Delta inverter

If the inverter is to run the equipment again after being shelved for more than half a year, the probability of damage may be greatly increased due to many factors such as the placement environment, the service life of the inverter, and the load rate, and the failure usually presents the following problems: 1. After the equipment is powered on, it becomes ...

Installation requirements for inverter energy consumption braking - Delta inverter Installation requirements for inverter energy consumption braking - Delta inverter

(1) The wiring interval between the braking unit and the inverter, as well as between the braking unit and the braking resistor, should be as short as possible (the wire length should be less than 2m), and the wire cross-section should meet the requirements of the braking resistor discharge current. (2) The brake unit is working ...

Delta's inverter power-on debugging method Delta's inverter power-on debugging method

After the inverter is installed, disconnect the output of the inverter, use the diode file of the digital meter to measure the input and output of the inverter before the power is not turned on, ensure that there is no short circuit, and then turn on the working power supply of the inverter.

Delta's touch screen controls the inverter method Delta's touch screen controls the inverter method

1. The touch screen is controlled by PLC inverter 1. Now the general control of the inverter needs to use PLC to communicate with the inverter, read the information of the inverter, and then the touch screen communicates with the PLC in order to complete the control of the inverter to start, stop, and monitor the operation of the inverter.

The role and application of Delta's thermostats The role and application of Delta's thermostats

Delta's thermostat is a commonly used temperature control device, which can adjust the temperature according to the user's needs, and then achieve the intention of saving energy. The effect and use of Delta thermostats are also very widespread, so let's introduce the effects and uses of Delta thermostats. ...

Basic parameter setting of special inverter for wind turbine - Delta Basic parameter setting of special inverter for wind turbine - Delta

1. Control mode: i.e. speed control, torque control, PID control or other methods. After the control method is adopted, static or dynamic identification should generally be carried out according to the control accuracy. 2. Minimum operating frequency: That is, the minimum speed of the motor. When the motor is working at low speed, the ...

TIMTOS x TMTS 2022 - Delta's Exhibit Highlights TIMTOS x TMTS 2022 - Delta's Exhibit Highlights

Intelligent machining solution plan Intelligent machinery is an important step towards intelligent manufacturing, in order to help manufacturers improve productivity or complete a few diverse forms of production, Delta will exhibit the intelligent processing solution plan at TIMTOS x TMTS 2022, which will be used to communicate with industrial-grade managed Ethernet networking.

Delta touch screen models and advantages Delta touch screen models and advantages

Human Machine Interface (HMI) is a digital product that allows operators to communicate with automation equipment. The human-machine interface provides a variety of communication ports to facilitate communication with a variety of equipment, and the touch panel allows the operator to intuitively set parameters.

Delta's inverter and output reactor function Delta's inverter and output reactor function

input/output reactor for frequency conversion speed regulation; Because the inverter is often affected by the impact of inrush current and surge voltage in the process of driving the inverter motor operation governor, which will seriously damage the function and service life of the inverter and the motor, so it is necessary to install a transmission system in front of it.

Delta's MH300 series technical specifications Delta's MH300 series technical specifications

Outstanding drive characteristics The overload capacity is up to 150% / 60 seconds, 200% / 3 seconds, suitable for constant torque, variable torque, constant power and other loads Support induction motor, permanent magnet synchronous motor, optional PG card for high ...

The output of the inverter is not short-connected to the power frequency The output of the inverter is not short-connected to the power frequency

1. To switch the motor of the power frequency, the parking method is set to free parking, and it is important not to park softly 2. Intercept the contactor of the motor from the output end of the inverter, and the control stop button and the inverter parking button are the same composite button, that is, when the inverter is pressed, the inverter parking will be followed by the contactor line.

The benefits of using an inverter – Delta inverter The benefits of using an inverter – Delta inverter

1. Speed regulation of general motor: By changing the input voltage and frequency of the three-phase asynchronous motor, its speed can be controlled. Generally, when the motor is at low speed, the temperature rise becomes larger due to the decrease in the power of the cooling fan, and the motor load should be reduced according to the frequency. 2 ...

Delta's high-performance servo ASDA-A3 series is a new product Delta's high-performance servo ASDA-A3 series is a new product

With the rapid development of automation technology and shopping malls, customers have higher and higher requirements for the speed, accuracy and function diversification of servo products. In order to get used to the needs of shopping malls, recently, Delta launched the high-performance motion control high-end AC servo system ASDA-A3 series ...

Pulse control wiring method for Delta servo drives Pulse control wiring method for Delta servo drives

Parameter settings P1-XX are the basic parameters P1-00 pulse method selection, *** bit selection is 2, that is, pulse train + direction P1-00 signal logic picking, the third digit is selected as 0 or 1, which is the positive logic or anti-logic, X0XX or X1XX P1-01 Control form selection, pick ...

The peripheral equipment of the inverter governor - Delta The peripheral equipment of the inverter governor - Delta

When installing the inverter governor, it is necessary to first understand its use occasions and set up different peripheral equipment according to the needs of the site. The primary peripheral equipment of frequency governor is: air circuit breaker, electromagnetic contactor, communication reactor, braking resistor, DC reactor, output communication reactor, wireless ...

Precautions for long-term idle use of Delta inverter Precautions for long-term idle use of Delta inverter

If the inverter is to run the equipment again after being shelved for more than half a year, the probability of damage may be greatly increased due to many factors such as the placement environment, the service life of the inverter, and the load rate, and the failure usually presents the following problems: ...

Delta servo problem analysis Delta servo problem analysis

1: What is the difference between servo motor and general motor? The biggest difference between servo motors and general motors is the motor rotor and reaction equipment. The surface of the servo motor rotor is pasted with a strong magnetic plate, so that the magnetic field generated by the stator coil can control the orientation of the rotor, and the acceleration and deceleration characteristics are ...

The inverter needs to be equipped with a braking resistor-Delta The inverter needs to be equipped with a braking resistor-Delta

The inverter is equipped with a braking resistor, mainly to consume part of the energy on the DC bus capacitor through the braking resistor to avoid the voltage of the capacitor being too high. Theoretically, if the capacitor stores a lot of energy, it can be used to release it to drive the motor to avoid energy waste, but the capacity of the capacitor is limited.

Delta's inverter method to reduce the failure rate Delta's inverter method to reduce the failure rate

Daily inspection item 1 of Delta's inverter problem repair: Check whether there are any abnormal changes in the sound of the motor during operation, including whether there is vibration during the operation of the motor. Routine inspection item 2 of Delta inverter problem repair: Check out the inverter installation environment is ...

CATEGORIES BYPASS
Customer Service Center

Online Consultation:QQ


ContactContact

Contact: Manager Huang

Contact QQ: 3271883383

Contact number: 13522565663


Scan the code to add WeChat (please save the picture first on the mobile phone)

working hoursworking hours

Weekdays: 9:00-17:00

Holidays: Only emergencies are handled

Contact us

Contact us

Contact number QQ consultation
QQ consultation

3271883383

Company address
Back to top