In order to ensure that the instantaneous or short-delay overcurrent trip of the circuit breaker can operate reliably in the event of a slight short-circuit fault within its protection range under the small operation mode of the system. The sensitivity of circuit breaker protection must meet the requirements of the "Design Code for Low-voltage Power Distribution" (GB50054-2011), and its sensitivity should not be less than 1.3, that is, Sp=lk.min/Iop≥1.3. where lop is the action current of the instantaneous or short-delay overcurrent tripper, Ik.Min is the single-phase short-circuit current or two-phase short-circuit current at the end of the line protected by the circuit breaker in the system operation mode, and Sp is the sensitivity of the circuit breaker.
For selective circuit breakers with both short-delay and instantaneous overcurrent trippers, only the action sensitivity of the short-delay overcurrent tripper needs to be verified, and the sensitivity of the instantaneous overcurrent tripper is not required.
Selection and tuning of circuit breaker tripper:
(1) The setting of the action current of the instantaneous overcurrent tripper
Among the objects protected by the circuit breaker, there are certain electrical equipment, which will generate high peak current several times its rated current in a short period of time during the start-up process, so that the circuit breaker can withstand a large peak current in a short time. The operating current lop(o) of the instantaneous overcurrent tripper must avoid the peak current Ipk of the line, i.e. Iop(o) ≥Krel· Ipk。 where Krel is the reliability coefficient. When selecting the circuit breaker, attention should be paid to making the setting current of the instantaneous overcurrent tripper of the circuit breaker avoid the peak current, so as not to cause the malfunction of the circuit breaker.
(2) The setting of the action current and action time of the short-delay overcurrent tripper
The operating current lop(s) of the short-delay overcurrent tripper should also avoid the peak current Ipk of the line, i.e., Iop(s) ≥Krel· Ipk。 where Krel is the reliability coefficient. The action time of the short-delay overcurrent tripper is generally divided into 0.2s, 0.4s and 0.6s, which are determined according to the protection selectivity of the front and rear protection devices, and the action time of the previous protection should be one time difference longer than that of the later protection.
(3) The setting of the action current and action time of the long-delay overcurrent tripper
The long-delay overcurrent tripper is mainly used to protect against overload, so its action current Iop(l) only needs to avoid the load current of the line, that is, the current I30 is calculated, that is, Iop(l)≥Krel· I30。 where Krel is the reliability coefficient. The action time of the long-delay overcurrent tripper should avoid the duration of the allowable short-term overload, so as not to cause the malfunction of the low-voltage circuit breaker.
(4) The requirements for the action current of the overcurrent tripper and the protected line
In order to prevent the line from overheating or even fire caused by overload or short circuit, and the circuit breaker does not trip the accident, the action current lop of the circuit breaker overcurrent tripper should meet the requirements of the formula, lop ≤ Kol· Ial。 where Ial is the allowable ampacity of the insulated cable; Kol is the allowable short-term overload coefficient of insulated cables, and 4.5 is generally taken for instantaneous and short-delay overcurrent trippers; For long-delay over-current trippers, 1.1 is taken when short-circuit protection is done, and 1 is taken when overload protection is only done. If the above matching requirements are not met, the action current of the tripper should be selected instead, or the cross-sectional area of the wire or cable should be appropriately thickened.
|
More on that
|
At the same time, Eaton worked with partners to build Wuhan "Xiaotangshan" Hospital
Date: 2020/02/09
In order to fight the new crown pneumonia, Wuhan launched the construction of the "Xiaotangshan" model hospital on January 23 to concentrate on the treatment of new crown pneumonia cases. Since January 24, Eaton and its partners in Wuhan have been providing full support for the construction of "Huoshenshan" and "Leishenshan" hospitals.
|
|
Eaton Vehicle Group is tackling the coronavirus crisis with Industry 4.0 technologies
SHANGHAI, China – Eaton (NYSE: ETN), a global power management company, today announced that its Vehicle Group has been leveraging advanced Industry 4.0 technologies to help its global operations safely navigate the current pandemic crisis and continue to serve customers.
Eaton ...
|
|
Wisdom and co-creation of the road forward | The 2022 Eaton Critical Power Greater China Digital Intelligence Summit was successfully held
On August 23, the 2022 Eaton Critical Power Greater China All-Ecosystem Digital Intelligence Cloud Summit was successfully held. In the face of the green and high-quality development goal of data centers, Eaton has embarked on a new journey, focusing on the dual transformation of digitalization and green energy, and in-depth analysis of ...
|
|
Eaton's standardized, factory-based xStorage microgrid container energy storage system is built for industrial and commercial enterprises
Under the "dual carbon" goal, all industries are facing the dual pressure of energy demand and low-carbon development, and the microgrid system based on distributed renewable energy generation has attracted much attention. Enterprises use it to carry out low-carbon energy transformation, reduce energy costs, and improve the stability of new power systems.
|
|
Jiangtian Data joins hands with Eaton to build a giant low-carbon data center
There is a fish in the northern underworld, and its name is Kun.
The Kun is so big that I don't know how many thousands of miles it is......
The No. 1 data center of Jiangtian Data's Huanjing Big Data Industry Tianjin Base, which is painted with "Kun" on the exterior wall, is equipped with 5,500 cabinets, full of the transformation from the former "steel giant" to the current "data giant"...
|
|
Eaton introduces battery disconnect with the latest Breaktor circuit protection technology
According to foreign media reports, power management company Eaton announced that its electric mobility (eMobility) business unit has launched a battery disconnect device (BDU), which can be combined with the upgraded Breaktor circuit protection technology to protect the electric vehicle (EV).
|
|
Eaton's E-Cube Gen II creates a new future of green and efficient data centers
If we compare the network to a pipe, and data to a stream of water, with the advent of the era of data explosion, the pipeline is getting wider and wider, and the water flow is getting bigger and bigger; On the other hand, a large number of use scenarios require local water intake and water storage, and how can the data center as a reservoir continue to provide a solid guarantee, ...
|
|
Eaton Basman AEC-Q200 inductor series products inventory, covering various application scenarios in the automotive field
Current gasoline-powered cars are electronically powered. Electronic systems are playing an increasingly important role in modern vehicles. The various subsystems within it have very different power requirements and require a mix of components to improve power efficiency. Thanks to the charging of today's batteries ...
|
|
Eaton's innovative development of power supplies
1. Intelligence
According to the analysis of various information, the intelligent control system should monitor, analyze and solve the key data information in the power circuit in real time, and obtain the role of whether everything is normal in the work of each part of the power supply circuit. In the production of ...
|
|
Layout in the field of new energy commercial vehicles Eaton is poised to set off
As countries around the world have shifted to the development direction of carbon reduction and emission reduction, zero-carbon transformation has gradually become a global consensus, and major car companies have also responded and formulated new energy development plans. China has also put forward the "double carbon" strategy accordingly, and incorporated the "double carbon" strategy into the overall construction of ecological civilization.
|
|
Selection and tuning of circuit breakers
The selection of circuit breakers should be based on the specific use conditions to select the use category, select the rated working voltage, rated current, tripper setting current and other parameters, refer to the protection characteristic curve provided by the product sample to select the protection characteristics, and need to verify the short-circuit characteristics and sensitivity coefficient.
Break...
|
|
Eaton Electric debuted at the 2023 International Digital Energy Exhibition, marching towards a new era of digital energy
From June 29th to July 2nd, the 2023 International Digital Energy Exhibition with the theme of "Digitally Driven, Enabling the Future" was held in Shenzhen. Eaton Electric has created a full-scene exhibition space, bringing integrated optical storage and charging, green power energy storage, smart power distribution, and full-scene smart energy solutions.
|
|
Against the headwind, the 2020 Eaton Circuit Protection & Control Division Agent Conference was successfully held online
On May 15, 2020, Eaton, a global power management company, held the "Eaton Future - 2020 Eaton Circuit Protection and Control Dealer Conference" in the form of an online live broadcast, and hundreds of dealer partners from all over the country participated online.
At the conference, Eaton's Circuit Protection and ...
|
|
Eaton's UPS Product Experience Center in Asia Pacific is newly unveiled, with four highlights revealed!
Recently, Eaton's UPS Product Experience Center in Asia Pacific was grandly opened at its BA1 facility in Shenzhen. As a global power management company with more than 100 years of accumulation, Eaton has always been committed to continuous innovation in "electrification + digitalization" technology.
In the all-new UPS sub...
|
|
Eaton CEO visits China: Firm development strategy in China and long-term optimism about the Chinese market
As Eaton celebrates its 100th anniversary of listing on the New York Stock Exchange (NYSE), Craig Arnold, chairman and chief executive officer, recently visited China again. After three years, Luo De carried out a series of business activities during his visit to China and came to the front line to interact cordially with long-lost Eaton employees.
|
|
The difference between circuit breaker and air open
1. The air switch generally plays the role of "isolation" and "protection device" in the small current circuit, which is also called automatic switch and air circuit breaker.
2. The circuit breaker has a good arc extinguishing ability, and will automatically trip in the case of short circuit and high current; In high-voltage, high-current circuits ...
|
|
Full of honors! Eaton has won four awards in China's electrical appliance industry
On June 9th, the "2023 China Electrical Appliance Industry Series White Paper" conference hosted by Gewu Zhisheng was held in Shanghai under the guidance of China Electrical Equipment Industry Association.
|
|
The new national standard energy efficiency access requirements will be mandatory from November, and data centers are facing a big test to reduce PUE
From November 2, the "Data Center Energy Efficiency Limit and Energy Efficiency Grade" will be implemented nationwide, and the energy consumption measurement, energy efficiency calculation and assessment of the single or modular units of data center buildings using independent power distribution, air cooling and electric air conditioning will be carried out.
|
|
How to maintain your Eaton UPS power supply
1. How to maintain Eaton's UPS power supply?
1) Under normal circumstances, the battery is charged and discharged every 3~6 months, and the charging time of the standard machine after discharge should not be less than 10 hours.
2) UPS is idle for a long time and should be charged once every 3~6 months.
3) The temperature of the battery is required to be between 0 °C and 4 ...
|
|
Eaton Electric has launched a new generation of converged power modules, the Eaton Power Cube series of power modular solutions
In the context of the comprehensive construction of the "Eastern Data and Western Computing" and "Dual Carbon" strategies, and the sharp increase in the demand for computing power in the digital economy, PUE power consumption has become an obstacle that must be overcome for the sustainable development of data centers. The traditional construction mode of data center has low space utilization and poor system availability.
|
|